• 제목/요약/키워드: Installation resistance

검색결과 442건 처리시간 0.027초

현장조사를 통한 건축물 접지저항 측정용 전극 설치의 개선에 관한 연구 (A Study on the Improvement of Electrode Installation for Measurement of Ground Resistance through Investigation on the Spot in Buildings)

  • 길형준;김동우;길경석
    • 조명전기설비학회논문지
    • /
    • 제25권5호
    • /
    • pp.92-97
    • /
    • 2011
  • This paper deals with the improvement of electrode installation for measurement of ground resistance through investigation on the spot in buildings. The investigation was carried out for an earthing terminal board for measurement of ground resistance, installation of auxiliary electrode, etc. The criteria value is set up by measuring method of ground resistance in international standard. In case of inadequate installation of auxiliary electrode, a relative error is analyzed and adequate installation method of auxiliary electrode is proposed. As a consequence, it is necessary to write direction of ground and equipment, and separate auxiliary electrode for measurement of ground resistance in order to minimize measuring error.

End shape and rotation effect on steel pipe pile installation effort and bearing resistance

  • Saleem, Muhammad A.;Malik, Adnan A.;Kuwano, Jiro
    • Geomechanics and Engineering
    • /
    • 제23권6호
    • /
    • pp.523-533
    • /
    • 2020
  • The current study focuses on the effect of the end shape of steel pipe piles on installation effort and bearing resistance using the pressing method of installation under dense ground conditions. The effect of pile rotation on the installation effort and bearing resistance is also investigated. The model steel piles with a flat end, cone end and cutting-edge end were used in this study. The test results indicated that cone end pile with the pressing method of installation required the least installation effort (load) and showed higher ultimate resistance than flat and cutting-edge end piles. However, pressing and rotation during cutting-edge end pile installation considerably reduces the installation effort (load and torque) if pile penetration in one rotation equal to the cutting-edge depth. Inclusion of rotation during pile installation reduces the ultimate bearing resistance. However, if penetration of the cutting-edge end pile equal to the cutting-edge depth in one rotation, the reduction in ultimate resistance can be minimized. In comparing the cone and cutting-edge end piles installed with pressing and rotation, the least installation effort is observed in the cutting-edge end pile installed with penetration rate equal to the cutting-edge depth per rotation.

Analysis of Thermal Characteristics and Insulation Resistance Based on the Installation Year and Accelerated Test by Electrical Socket Outlets

  • Kim, Kyung Chun;Kim, Doo Hyun;Kim, Sung Chul;Kim, Jae Ho
    • Safety and Health at Work
    • /
    • 제11권4호
    • /
    • pp.405-417
    • /
    • 2020
  • Background: Electrical socket outlets are used continuously until a failure occurs because they have no indication of manufacturing date or exchange specifications. For this reason, 659 electrical fires related to electrical socket outlets broke out in the Republic of Korea at 2018 only, an increase year on year. To reduce electrical fires from electrical socket outlets, it is necessary to perform an accelerated test and analyze the thermal, insulation resistance, and material properties of electrical socket outlets by installation years. Methods: Thermal characteristics were investigated by measured the temperature increase of electrical socket outlets classified according to year with variation of the current level. Insulation resistance characteristics was measured according to temperature for an electrical socket outlets by their years of use. Finally, to investigate the thermal and insulation resistance characteristics in relation to outlet aging, this study analyzed electrical socket outlets' conductor surface and content, insulator weight, and thermal deformation temperature. Results: Analysis showed, regarding the thermal characteristics, that electrical socket outlet temperature rose when the current value increased. Moreover, the longer the time that had elapsed since an accelerated test and installation, the higher the electrical socket outlet temperature was. With respect to the insulation resistance properties, the accelerated test (30 years) showed that insulation resistance decreased from 110 ℃. In relation to the installation year (30 years), insulation resistance decreased from 70 ℃, which is as much as 40 ℃ lower than the result found by the accelerated test. Regarding the material properties, the longer the elapsed time since installation, the rougher the surface of conductor contact point was, and cracks increased. Conclusion: The 30-year-old electrical socket outlet exceeded the allowable temperature which is 65 ℃ of the electrical contacts at 10 A, and the insulation resistance began to decrease at 70 ℃. It is necessary to manage electrical socket outlets that have been installed for a long time.

전기콘센트의 사용환경과 전류값에 따른 열적특성 및 절연저항 분석 (Analysis of Thermal Characteristics and Insulation Resistance based on Usage Environment and Current Value of Electrical Socket Outlet)

  • 김경천;김두현;김성철
    • 한국안전학회지
    • /
    • 제34권5호
    • /
    • pp.22-30
    • /
    • 2019
  • In 2018, overload, overcurrent, insulation aging, and a contact failure caused 659 electric fires. There is almost no failure of electrical socket outlets during their manufacturing or installation period. After several months or several years, overload or overcurrent of electrical socket outlets leads to a contact failure or short circuit which causes an electric fire. Therefore, this paper analyzed for thermal characteristics based on a current value and the change in insulation resistance along with a temperature rise caused by electrical socket outlets and the state of laboratory use in workplaces. As a results, regarding the thermal characteristics based on the current value of each installation year, a temperature increase was related to a current value, an installation year, and whether the contact unit is corroded. Insulation resistance began to decrease when a temperature increased to a certain level. With a lapse of installation year, the temperature at which insulation resistance began to decrease was lowered. This paper can be applicable for the survey data about electrical socket outlet induced fire accidents and management guidelines.

수조모델 실험에 의한 접지저항 추정 (presumption of Earth Resistance by Water Tank Model)

  • 고희석;최종규;김주찬;이충식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2002년도 학술대회논문집
    • /
    • pp.125-131
    • /
    • 2002
  • It is very important to assume potential distribution to be generated in electrode environs and grounding resistance by current beforehand, when incoming at grounding electrode to plan efficient grounding facilities In this paper, we analyzed grounding resistance through a simulation experiment by a water tank scaled model electrode of the rectangular earth plate, a theoretical Calculation result of the rectangular earth plate and measurement of grounding resistance buried rectangular earth plate analysing earth surface potential.

  • PDF

지오신세틱스 전단거동의 해석학적 고찰 (Interpretational Consideration of Geosynthetics Shear Behaviors)

  • 전한용;김초롱
    • 한국지반공학회:학술대회논문집
    • /
    • 한국지반공학회 2010년도 추계 학술발표회
    • /
    • pp.293-302
    • /
    • 2010
  • 2 types of geogrids and geotextiles was used to evaluate shear behaviors after installation damage test. Shear behaviors were compared after installation damage test and coefficient of resistance to direct sliding($f_{ds}$) was estimated by theoretical shear analysis. Shear strength of damaged geogrid decreased under high normal stress of 150kPa and shear strength of geotextile decreased with increasing normal stress. It is seen that $f_{ds}$ values after installation damage decreased than before installation damage through comparison calculated $f_{ds}$ by direct theoretical shear analysis. $f_{ds}$ values to be calculated by theoretical shear analysis were changed with before and after installation damage.

  • PDF

병렬 접속에 의한 접지저항에 관한 연구 (A Study on Grounding Resistance by Parallel Connection)

  • 고희석;최종규;류희석;김주찬
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2002년도 학술대회논문집
    • /
    • pp.307-312
    • /
    • 2002
  • For accuracy of an experiment, measure changing of grounding resistance by short period after construction and investigated the efficiency of grounding's different methode of parallel connection. We could confirm on measurement's accuracy, error through comparing the theoretical value and measured value. Therefore, reduction ratio can be expected from execution measurement to receive a target resistance value. By the result, we could evaluate the method of rod grounding electrode's proper execution

  • PDF

운전중인 전력설비의 접지저항 측정방법 (A measuring Method of Ground Resistance for Energized Power Systems)

  • 이복희;김성원;엄주홍;이승칠
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2000년도 학술대회논문집
    • /
    • pp.77-81
    • /
    • 2000
  • The purpose of this paper is to describe a new measuring method of ground resistance for the grounding system in energized power equipment and substations. It is very difficult to measure the accurate ground resistance in energized power equipment and substations because of the noise conducted from all external connections to the grounding system and harmonics components caused by unbalanced loads and overloads. The ground resistance that is measured with existing methods includes not only the effect of desired signals but also noise components for the measurement period in grounding system. The measured value of ground resistance can entirely be different from actual value. In this paper, to eliminate 60[Hz] power system interference and harmonic components the low-pass filter method was used in the measurement of ground resistance.

  • PDF

전류 및 전위 보조전극을 수직으로 배치하는 전위강하법을 이용한 접지저항의 측정 (Measurement of the Ground Resistance using the Fall-of-Potential Method with the Vertically-placed Current and Potential Auxiliary Electrodes)

  • 이복희;김기복;김유하
    • 조명전기설비학회논문지
    • /
    • 제26권3호
    • /
    • pp.53-60
    • /
    • 2012
  • The fall-of-potential method is commonly used in measuring the ground resistance of large-scaled grounding system and the current and potential auxiliary electrodes are horizontally arranged. Because the distances between the ground grid to be tested and auxiliary electrodes are limited in downtown areas, it is very difficult to measure accurately the ground resistance of large-scaled grounding system. In this paper, the fall-of-potential method of measuring the ground resistance with the vertically-placed current and potential auxiliary electrodes was examined and discussed. The validity and good accuracy of the proposed method of measuring the ground resistance were confirmed through various simulations and actual tests carried out in uniform and two-layer soil structures.

도전성 팽창 접지저감재의 접지저항 저감 효과 (The Ground Resistance Reduction Effect of o Conductive Expansion Ground Resistance Reducing Material)

  • 김종욱;김경철;최종기;강민규;백남웅
    • 조명전기설비학회논문지
    • /
    • 제22권2호
    • /
    • pp.155-161
    • /
    • 2008
  • 접지시스템은 고장전류나 상시 전류를 낮은 저항의 대지로 흘러 보낸다. 접지전극 주변에 접지저감재를 매설하면 접촉 면적을 증가시켜 낮은 접지저항을 얻을 수 있다. 접지전극의 접촉면적을 확대시키면 접지저항값이 낮아진다는 특성을 이용하여 접지 시공시 팽창 특성을 가진 도전성 팽창 접지저감재를 개발하였다. 본 논문에서는 실험을 통하여 도전성 팽창 접지저감재가 일반 접지저감재보다 접지저항 저감 효과가 뛰어남을 검증하였다.