A measuring Method of Ground Resistance for Energized Power Systems

운전중인 전력설비의 접지저항 측정방법

  • Published : 2000.11.01

Abstract

The purpose of this paper is to describe a new measuring method of ground resistance for the grounding system in energized power equipment and substations. It is very difficult to measure the accurate ground resistance in energized power equipment and substations because of the noise conducted from all external connections to the grounding system and harmonics components caused by unbalanced loads and overloads. The ground resistance that is measured with existing methods includes not only the effect of desired signals but also noise components for the measurement period in grounding system. The measured value of ground resistance can entirely be different from actual value. In this paper, to eliminate 60[Hz] power system interference and harmonic components the low-pass filter method was used in the measurement of ground resistance.

Keywords