• 제목/요약/키워드: Indoor wiring system

검색결과 7건 처리시간 0.024초

Extraction of Series Arc Signals Based on Wavelet Transform in an Indoor Wiring System

  • Ji, Hong-Keun;Cho, Young-Jin;Wang, Guoming;Hwang, Seong-Cheol;Kil, Gyung-Suk
    • Transactions on Electrical and Electronic Materials
    • /
    • 제18권4호
    • /
    • pp.221-224
    • /
    • 2017
  • This paper dealt with the extraction of series arc signals based on wavelet transform in order to improve the accuracy of arc detection in indoor wiring systems. Three types of arc sources including a cord-cord, a terminal-cord, and an outlet-plug were fabricated to simulate typical arc defects. An arc generator fabricated according to UL 1699 was used to generate arcs. The optimal mother wavelet was selected as bior1.5 by calculating the correlation coefficients between the detected single current pulse and the wavelet. The detected arc current signals were then decomposed into eight levels using the discrete wavelet transform that implements the multi-resolution analysis method. By analyzing the decomposed components, the detail components D6, D7, and D8 were associated with arc signals, which were used for signal reconstruction. From the result, it was verified that the proposed method can be used for the extraction of the series arc signal from the AC mains, which is expected to be applied to further analysis of arc signals in indoor wiring systems.

전기배선에서 과전류와 포화시간을 입력변수로 갖는 퍼지기반 전기화재가능성 분석 (Analysis for Electrical Fire Possibility Using Fuzzy Logic with Input Variables of Overcurrent and Saturation Time in the Indoor Wiring)

  • 김은진;김두현;김성철
    • 한국안전학회지
    • /
    • 제30권6호
    • /
    • pp.34-39
    • /
    • 2015
  • The study is aimed to develop fuzzy logic system that has overcurrent and saturation time as input variable and possibility of electrical fire as output variable by making bad conductor area with physical damage to indoor wiring. Most previous studies focused on thermal characteristics depending on the current size and no study considered the current size and saturation time at the same time. Therefore, the paper made into account current value and saturation time together. To this end, it created bad conductor area half the size of IV conductor (1.6 mm) on purpose and transmit electrical current from 10A to 60A by unit of 2A to find out the thermal characteristics and saturation time for current. Based on the data that came out, the study applied fuzzy logic and established the current and saturation time as input variable and chance of fire as output variable. As a result, the center of area of the system that depended only on the existing current value was 75 while the system that applied both current and saturation time presented the chance of fire at 92. It is found that the chance of bad conductor area and deteriorated insulation of electrical wire had current and saturation time as important variables. The data can be used as basic data like deteriorated wire insulation or operation features of circuit breaker in investigating the cause of electrical fire.

병렬아크의 고속차단에 관한 연구 (A Study on the High Speed Interruption of Parallel Arcing)

  • 길경석;지홍근;박대원;김일권;김영일;조영진
    • 조명전기설비학회논문지
    • /
    • 제22권12호
    • /
    • pp.95-100
    • /
    • 2008
  • 기존의 누전차단기는 병렬아크에 대해서 차단을 실패하거나 차단시간이 결어지는 결함이 있었다. 본 논문에서는 저압 옥내배선 계통에서 병렬아크를 모의하여 기존 누전차단기의 차단특성을 분석하고, 병렬아크 검출에 적합한 공심형 전류센서와 신호변환회로를 설계하여 기존 방식의 누전차단기에 적용하였다. 제안한 방식은 병렬아크의 발생위치와 관계없이 누전차단기를 동작시켰으며, 차단시간은 아크가 발생한 위상에 따라 $1.74{\sim}8.3[ms]$의 범위로 기존 차단기에 비해 약 5배 빠른 특성이다.

저압배선계통에서 직렬아크의 검출에 관한 연구 (A Study on the Series Arc Detection in Low-voltage Wiring Systems)

  • 김일권;박대원;최수연;박찬용;김황국;길경석
    • 한국전기전자재료학회논문지
    • /
    • 제21권2호
    • /
    • pp.182-187
    • /
    • 2008
  • This paper dealt with the detection algorithm of series arcing, which is a cause of electric fires in low-voltage wiring systems. To find the distinguished electrical features of series arc, we simulated series arcing by the arc generator specified in UL1699. An electric heater, an inverter-controlled vacuum cleaner, and a phase-controlled incandescent lamp were used as loads to generate series arcing. A high-pass filter (HPF) with the low cut-off frequency of 3 kHz at -3 dB was fabricated and applied to separate the series arc signal from the AC voltage source. The experiment showed that the high frequency signal generates randomly during series arcing, and the phase-controlled incandescent lamp produces high frequency pulses even in normal state. In this case, the magnitude, the width, and the randomness of high frequency signal should be analyzed to estimate series arcing precisely.

유닛형 경량철골 천정시스템 개발에 관한 연구 (A Study of the Development of a Modular, Lightweight Steel Ceiling System)

  • 김혜연;배상환
    • 설비공학논문집
    • /
    • 제29권5호
    • /
    • pp.269-277
    • /
    • 2017
  • This study consists of an analysis of pre-existing ceiling construction systems as well as the development of a replacement unitary, lightweight steel ceiling system and related legal standards. Based on the material conditions and progression of the study, appropriate components were chosen and details were modified by mock-up test. A final study model was evaluated for performance and adaptability based on four parameters (indoor environment, constructability, budget economy, and aesthetics) and compared to the pre-existing ceiling system. As a result of the initial study, a lightweight steel design was created consisting of a reinforced structure with modular bars and entry holes for components. This system was hung directly on the suspension structure. The new design increased lighting and acoustic performance adapted to an indoor environment. Moreover, the speed of construction was increased by approximately 30%, the cost was decreased by approximately 20%, and ceiling aesthetics were improved.

옥내 배선계통에서 직렬 아크의 검출과 판별 (Detection and Identification of the Series Arc in an Indoor Wiring System)

  • 김우현;왕국명;길경석;지홍근
    • 한국전기전자재료학회논문지
    • /
    • 제31권6호
    • /
    • pp.412-416
    • /
    • 2018
  • Most series arcs lead to electrical fires that cannot be interrupted by circuit breakers, because the arc's current is outside the breaker's operating range. In this paper, experiments were conducted on the detection and identification of series arcs to prevent electrical fires. Plugs and outlets specified in KS C 8305 were deteriorated to replicate arc faults commonly found in fields. The characteristics of series arcs resulting from various types of loose connections were determined by analyzing the frequency spectra and phase distributions of detected arc pulses. The results showed that the simulated arc defects used in this study were more similar to actual arc phenomena than the existing arc generator specified in UL 1699. In addition, loose connections, such as wire-wire, terminal-wire, and outlet-plug, can be identified by phases of $0^{\circ}$, $180^{\circ}$ and $360^{\circ}$, respectively. These phases can be detected by a band pass filter with a frequency range of 5~10 MHz, which can be used as the trip signal for circuit breakers.

승압형 컨버터를 활용한 비접촉식 전력변환 시스템 (contactless power conversion system using the Boost converter)

  • 이승준
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2003년도 추계학술대회 논문집
    • /
    • pp.214-217
    • /
    • 2003
  • The connectorless power supply system on that multi-contact causes confidence when the wiring reconstructed in the rear. As you see above, contact points between sets and indoor space cause inferior function of audio frequency so it needs to be eliminated. This paper explains the structure of connectorless power supply to supply the system with power crossing the air gap in the part of inductively in the connectorless power supply of both magnetic and electrical model. To get maximum output of electrical load, compensating capacitor compensates to show inter-inductance, lequeage-inductance reducing the track-inductance and access the conditions for resonance. At that time it accesses the maximum electric power. The small change of the value of compensating capacitor causes the changes of maximum electric power. Here the power electronics technology is used not only in the industrial machinery but also in the home appliances so the switching power supply is used to actualize the miniaturization, lightweight, and high efficiency. Generally the condenser input methods are widely used in the rectification circuit of switching power supply, but condenser input method generate great quantity of high frequency components because with this method the current flows in the power input filtering condenser only around value of peak of ac input voltage. To solve these problems, installation of power factor improve circuit on the front of filtering capacitence was considered. Several methods were suggested regarding, but the active filter method which makes smalliging and highly power factor possible are the produce main stream. IC for power factor improvement can be utilized by CMOS process proposing low power consumption. When the high power factor is considered seriously in the power factor improvement circuit, active filter method is selected. In the active filter method, the boost converter is used. Regarding this ·the boost converter is needed.

  • PDF