• Title/Summary/Keyword: Indoor wiring system

Search Result 7, Processing Time 0.025 seconds

Extraction of Series Arc Signals Based on Wavelet Transform in an Indoor Wiring System

  • Ji, Hong-Keun;Cho, Young-Jin;Wang, Guoming;Hwang, Seong-Cheol;Kil, Gyung-Suk
    • Transactions on Electrical and Electronic Materials
    • /
    • v.18 no.4
    • /
    • pp.221-224
    • /
    • 2017
  • This paper dealt with the extraction of series arc signals based on wavelet transform in order to improve the accuracy of arc detection in indoor wiring systems. Three types of arc sources including a cord-cord, a terminal-cord, and an outlet-plug were fabricated to simulate typical arc defects. An arc generator fabricated according to UL 1699 was used to generate arcs. The optimal mother wavelet was selected as bior1.5 by calculating the correlation coefficients between the detected single current pulse and the wavelet. The detected arc current signals were then decomposed into eight levels using the discrete wavelet transform that implements the multi-resolution analysis method. By analyzing the decomposed components, the detail components D6, D7, and D8 were associated with arc signals, which were used for signal reconstruction. From the result, it was verified that the proposed method can be used for the extraction of the series arc signal from the AC mains, which is expected to be applied to further analysis of arc signals in indoor wiring systems.

Analysis for Electrical Fire Possibility Using Fuzzy Logic with Input Variables of Overcurrent and Saturation Time in the Indoor Wiring (전기배선에서 과전류와 포화시간을 입력변수로 갖는 퍼지기반 전기화재가능성 분석)

  • Kim, Eun-Jin;Kim, Doo-Hyun;Kim, Sung-Chul
    • Journal of the Korean Society of Safety
    • /
    • v.30 no.6
    • /
    • pp.34-39
    • /
    • 2015
  • The study is aimed to develop fuzzy logic system that has overcurrent and saturation time as input variable and possibility of electrical fire as output variable by making bad conductor area with physical damage to indoor wiring. Most previous studies focused on thermal characteristics depending on the current size and no study considered the current size and saturation time at the same time. Therefore, the paper made into account current value and saturation time together. To this end, it created bad conductor area half the size of IV conductor (1.6 mm) on purpose and transmit electrical current from 10A to 60A by unit of 2A to find out the thermal characteristics and saturation time for current. Based on the data that came out, the study applied fuzzy logic and established the current and saturation time as input variable and chance of fire as output variable. As a result, the center of area of the system that depended only on the existing current value was 75 while the system that applied both current and saturation time presented the chance of fire at 92. It is found that the chance of bad conductor area and deteriorated insulation of electrical wire had current and saturation time as important variables. The data can be used as basic data like deteriorated wire insulation or operation features of circuit breaker in investigating the cause of electrical fire.

A Study on the High Speed Interruption of Parallel Arcing (병렬아크의 고속차단에 관한 연구)

  • Kil, Gyung-Suk;Ji, Hong-Keun;Park, Dae-Won;Kim, Il-Kwon;Kim, Young-Il;Cho, Young-Jin
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.12
    • /
    • pp.95-100
    • /
    • 2008
  • Conventional Earth Leakage Circuit Breakers (ELCBs) have defects of a breaking failure or a long breaking-time against parallel arc current. In this paper, breaking characteristics of conventional ELCBs were analyzed by simulation of parallel arc in a low-voltage indoor wiring system, and an air-core current sensor and a signal converter being most available for parallel arc detection were developed and applied to a conventional ELCB. The proposed tripped the ELCB regardless of the location of parallel arc. The breaking-time was in ranges of $1.74{\sim}8.3[ms]$ depending on the phase of arc generation, which is about 5 times as fast as conventional ELCBs with the breaking-time of 50[ms].

A Study on the Series Arc Detection in Low-voltage Wiring Systems (저압배선계통에서 직렬아크의 검출에 관한 연구)

  • Kim, Il-Kwon;Park, Dae-Won;Choi, Su-Yeon;Park, Chan-Yong;Kim, Hwang-Kuk;Kil, Gyung-Suk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.21 no.2
    • /
    • pp.182-187
    • /
    • 2008
  • This paper dealt with the detection algorithm of series arcing, which is a cause of electric fires in low-voltage wiring systems. To find the distinguished electrical features of series arc, we simulated series arcing by the arc generator specified in UL1699. An electric heater, an inverter-controlled vacuum cleaner, and a phase-controlled incandescent lamp were used as loads to generate series arcing. A high-pass filter (HPF) with the low cut-off frequency of 3 kHz at -3 dB was fabricated and applied to separate the series arc signal from the AC voltage source. The experiment showed that the high frequency signal generates randomly during series arcing, and the phase-controlled incandescent lamp produces high frequency pulses even in normal state. In this case, the magnitude, the width, and the randomness of high frequency signal should be analyzed to estimate series arcing precisely.

A Study of the Development of a Modular, Lightweight Steel Ceiling System (유닛형 경량철골 천정시스템 개발에 관한 연구)

  • Kim, Hyeyeon;Bae, Sanghwan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.29 no.5
    • /
    • pp.269-277
    • /
    • 2017
  • This study consists of an analysis of pre-existing ceiling construction systems as well as the development of a replacement unitary, lightweight steel ceiling system and related legal standards. Based on the material conditions and progression of the study, appropriate components were chosen and details were modified by mock-up test. A final study model was evaluated for performance and adaptability based on four parameters (indoor environment, constructability, budget economy, and aesthetics) and compared to the pre-existing ceiling system. As a result of the initial study, a lightweight steel design was created consisting of a reinforced structure with modular bars and entry holes for components. This system was hung directly on the suspension structure. The new design increased lighting and acoustic performance adapted to an indoor environment. Moreover, the speed of construction was increased by approximately 30%, the cost was decreased by approximately 20%, and ceiling aesthetics were improved.

Detection and Identification of the Series Arc in an Indoor Wiring System (옥내 배선계통에서 직렬 아크의 검출과 판별)

  • Kim, Woo-Hyun;Wang, Guoming;Kil, Gyung-Suk;Ji, Hong-Keun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.31 no.6
    • /
    • pp.412-416
    • /
    • 2018
  • Most series arcs lead to electrical fires that cannot be interrupted by circuit breakers, because the arc's current is outside the breaker's operating range. In this paper, experiments were conducted on the detection and identification of series arcs to prevent electrical fires. Plugs and outlets specified in KS C 8305 were deteriorated to replicate arc faults commonly found in fields. The characteristics of series arcs resulting from various types of loose connections were determined by analyzing the frequency spectra and phase distributions of detected arc pulses. The results showed that the simulated arc defects used in this study were more similar to actual arc phenomena than the existing arc generator specified in UL 1699. In addition, loose connections, such as wire-wire, terminal-wire, and outlet-plug, can be identified by phases of $0^{\circ}$, $180^{\circ}$ and $360^{\circ}$, respectively. These phases can be detected by a band pass filter with a frequency range of 5~10 MHz, which can be used as the trip signal for circuit breakers.

contactless power conversion system using the Boost converter (승압형 컨버터를 활용한 비접촉식 전력변환 시스템)

  • Lee S. J.
    • Proceedings of the KIPE Conference
    • /
    • 2003.11a
    • /
    • pp.214-217
    • /
    • 2003
  • The connectorless power supply system on that multi-contact causes confidence when the wiring reconstructed in the rear. As you see above, contact points between sets and indoor space cause inferior function of audio frequency so it needs to be eliminated. This paper explains the structure of connectorless power supply to supply the system with power crossing the air gap in the part of inductively in the connectorless power supply of both magnetic and electrical model. To get maximum output of electrical load, compensating capacitor compensates to show inter-inductance, lequeage-inductance reducing the track-inductance and access the conditions for resonance. At that time it accesses the maximum electric power. The small change of the value of compensating capacitor causes the changes of maximum electric power. Here the power electronics technology is used not only in the industrial machinery but also in the home appliances so the switching power supply is used to actualize the miniaturization, lightweight, and high efficiency. Generally the condenser input methods are widely used in the rectification circuit of switching power supply, but condenser input method generate great quantity of high frequency components because with this method the current flows in the power input filtering condenser only around value of peak of ac input voltage. To solve these problems, installation of power factor improve circuit on the front of filtering capacitence was considered. Several methods were suggested regarding, but the active filter method which makes smalliging and highly power factor possible are the produce main stream. IC for power factor improvement can be utilized by CMOS process proposing low power consumption. When the high power factor is considered seriously in the power factor improvement circuit, active filter method is selected. In the active filter method, the boost converter is used. Regarding this ·the boost converter is needed.

  • PDF