• 제목/요약/키워드: High-Voltage Circuit Breaker

검색결과 136건 처리시간 0.026초

Three-phase Making Test Method for Common Type Circuit Breaker

  • Ryu, Jung-Hyeon;Choi, Ike-Sun;Kim, Kern-Joong
    • Journal of Electrical Engineering and Technology
    • /
    • 제7권5호
    • /
    • pp.778-783
    • /
    • 2012
  • The synthetic short-circuit making test to adequately stress the circuit breaker has been specified as the mandatory test duty in the IEC 62271-100. The purpose of this test is to give the maximum pre-arcing energy during making operation. And this requires the making operation with symmetrical short-circuit current that is established when the breakdown between contact gap occurs near the crest of the applied voltage. Also, if the interrupting chamber of circuit breakers is designed as the type of common enclosure or the operation is made by the gang operated mechanism that three-phase contacts are operated by one common mechanism, three-phase synthetic making test is basically required. Therefore, several testing laboratories have developed and proposed their own test circuits to properly evaluate the breaker performance. With these technical backgrounds, we have developed the new alternative three-phase making circuit.

PTFE 용삭을 고려한 초고압 복합소호 차단기의 성능 예측 (Prediction of Performance considering Ablated PTFE in High Voltage Self-blast Circuit Breaker)

  • 김진범;권기영;이학성
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2008년도 춘계학술대회논문집
    • /
    • pp.695-698
    • /
    • 2008
  • Self-blast circuit breakers utilize the energy dissipated by the arc itself to create the required conditions for arc quenching during the current zero. During the arcing period, high pressure, temperature and radiation of the arc could burn in pure SF6 gas and PTFE nozzle. Ablated nozzle shape and $SF_6$-PTFE mixture vapor affect the performance of an self-blast circuit breaker. After a number of tests, nozzle in circuit breaker is disassembled, a section of ablated nozzle is investigated precisely. Using computational fluid dynamics, the conservation equation for the gas and temperature, velocity and electric fields within breaker is solved. Before applying a section model, developed program is verified with experimental data. Performance of ablated nozzle shape is compared with original model through analysis program.

  • PDF

Weil-Dobke 합성단락시험로의 최적화 연구 (A Study on Optimization of the Weil-Dobkes Synthetic Short-Circuit Tests)

  • 김맹현;고희석
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제50권6호
    • /
    • pp.287-292
    • /
    • 2001
  • This paper deals with the configuration, operating principles, systematic calculation method of parameter and optimization method of test circuit for parallel current injection method, series voltage injection method and hybrid synthetic test method as the method for performance test of circuit breaker with extra high interrupting capacity. The test method depicted above is applied to short-circuit making and breaking test (operating sequence :Os CdOs, Od-CdOs) and out-of-phase tests(operating sequence :Os, CdOs) for performance test of the newly-developed 420kV, 50kA and 800kV 50kV puffer-type gas circuit-breaker according to IEC 60056 and IEC 60427. The testing results, evaluation of equivalence for test and analyzed results are also presented in this paper.

  • PDF

EMTP/RV를 이용한 22.9kV GIS 모델링과 과도회복전압 해석 (22.9kV GIS Modeling and Transient Recovery Voltage Analysis Using EMTP/RV)

  • 정태영;백영식;정기석;박지호;서규석
    • 전기학회논문지
    • /
    • 제59권7호
    • /
    • pp.1199-1205
    • /
    • 2010
  • The recent power system is required to a large size of facilities and high power technology according to increasing power demand. However, it could lead to spoiling the beauty of city and environment problem. The miniaturized facilities with large capacity such as GIS have been required in recent power system. The GIS(Gas Insulated Substation) using the SF6 insulation gas enables to miniaturize facilities with large capacity with high insulation performance. However, the substation installed GIS has required to new design model which is different from the conventional substation. The TRV(Transient Recovery Voltage) analysis on simple circuit may applied by differential equation. However, in case of relatively complicated system, EMTP(Electro Magnetic Transients Program) mainly has been used to design and simulate for transient analysis. This paper mainly design the 22.9 kV GIS system and analyze the transient recovery voltage of main circuit breaker using EMTP/RV. It also enables to easily design the other substation installed GIS with same maker and voltage level because the proposed GIS model consists of separated modules such as busbar, circuit breaker, bushing, CT, PT etc. Eventually, it contributes to comfortably compare the interrupting performance of circuit breaker and system TRV corresponding to the substation system configuration.

고압진공차단기의 정격전류상승을 위한 GAE해석 (Parametric Study and Optimized Thermal Design of a High-Voltage Vacuum Circuit Breaker)

  • 안희섭;이종철;최종웅;오일성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.39-42
    • /
    • 2002
  • In this study, the computational heat transfer of the high-voltage vacuum circuit breaker was investigated. Higher normal current-ratings and stabilized thermal characteristics become more important in existing circuit breakers in order to satisfy market needs. Increases in current-ratings have an even greater effect on the Joule heating in the main circuit of the breakers. The thermal design must account for this increase in heat produced for the breaker to meet various temperature-rise limits set by industry standards. We are studying to enhance the normal current-ratings without major frame change of our present production models. As the method used in this research, we performed the computational analysis using the commercial Package, ICEPAK. We could get optimized thermal design suitable for 25% upgraded normal current-ratings through parametric study.

  • PDF

저압 배선용 차단기용 섬유강화 복합재료 개발(I) (Development on the fiber-reinforced materials for low-voltage circuit breakers(I))

  • 이창용;송태헌;김진수;김덕중;이두희;이관희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.127-129
    • /
    • 2002
  • A new type of fiber-reinforced polymeric materials for the main body and the arc chamber of the low-voltage circuit breakers was developed. The tensile and the flectional strength of the three kinds of thermoplastic resins for the cover of MCCBs(Molded case circuit breakers) increase much higher than those made of BMC that has been used. In a high current-breaking test, an experimental MCCB with the new insulating material showed no-cracks on the bodies.

  • PDF

발전소용 4.16 kV급 차단기에서 감전사고 사례 분석 (Analysis of Electric Shock Accident on 4.16 kV Class Circuit breaker for Power Plant)

  • 박남규;송재용;김진표;고재모
    • 한국안전학회지
    • /
    • 제29권4호
    • /
    • pp.54-60
    • /
    • 2014
  • This paper describes electric shock accidents on a 4.16 kV class circuit breaker for power plant. Electric shock accidents mostly involve damage of human life, in comparison with electrical fire, rate of human death tend to be higher in electric shock accidents. Specially, in a high voltage facilities rate of human death comprised about 43.7% by electric shock accidents. If electric shock accidents happen in a 4.16 kV class circuit breaker for power plant, then the power plant discontinue power production. Electric shock accidents in a power plant have a great ripple effect such as an electric power shortage. In this paper, we analyzed electric shock accidents on a 4.16 kV class circuit breaker for power plant. From the analysis results, we confirmed a cause of electric shock accidents on a 4.16 kV class circuit breaker, it happened by defect of interlock equipment or occurrence of breakdown between first feeder contactor and shielding plate. In order to reduce electric shock accidents on a 4.16 kV class circuit breaker, the power plant should consider improvement of interlock equipment and insulation of feeder contactor in circuit breaker.

직류전원을 이용한 배전급 차단기의 등가 3상 합성투입시험법 (Equivalent three-phase synthetic making test for medium voltage circuit breaker of distribution system using DC power)

  • 박병락;조만영;김진석;신희상;김재철
    • 조명전기설비학회논문지
    • /
    • 제25권7호
    • /
    • pp.105-113
    • /
    • 2011
  • The study about three-phase synthetic making test using DC power has been performed in order to increase the making test capacity on Vacuum Circuit Breaker. And, it made possible to solve the limitations that short-circuit testing facilities can not fulfill the testing requirements of VCB exceeding three-phase 36[kV] 31.5[kA]. By using DC power and high speed spark-gap switch, this method made the equivalence with the pre-arc that occurred during the making process under the fault condition of power system. As results, KERI(Korea Electrotechnology Research Institute) could have capacity to carry out type test for VCB under three-phase 52[kV] 40[kV], which satisfies the IEC Standard.

개극시간 조정회로를 삽입한 축소형 가스절연 차단기 (Compact Gas-Insulated Circuit-Breaker adopting opening-time control circuits)

  • 김정배;김두성;서경보;양대일;송원표;김맹현;고희석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.485-487
    • /
    • 2004
  • High-voltage gas-insulated circuit-breaker must interrupt short-circuit current successfully when breakdown occurs in electric power system. Among many test-duties, Basic Terminal fault T100a(BTF T100a) is the one of the severest duties because of its high DC component of short-circuit current. In this paper, we developed 245kV 50kA gas circuit breaker using control circuits to reduce DC component while interrupting short-circuit current, then got good performance through high-power tests in Korea Electrotechnology Research Institute(KERI) and KEMA

  • PDF

진공차단기 스위칭 써지 특성 해석 및 저감 방안 (Surge Characteristics Analysis and Reduction Method of Vacuum Circuit Breaker)

  • 김종겸
    • 전기학회논문지
    • /
    • 제62권2호
    • /
    • pp.190-195
    • /
    • 2013
  • Vacuum circuit breaker(VCB) has been widely used for interruption of load current and fault current for high voltage motor in the industrial field. Its arc extinguishing capability is excellent compared to other breakers. But it has the potential to cause multi reignition surge by high extinguishing capability. Surge voltage is generated by the opening and closing of VCB. Multi reignition surge of VCB is steep-fronted waveform. It may have a detrimental effect on the motor winding insulation. So, most of users install a protection device to limit steep-front waveform at the motor terminal or breaker side. So, most of users install a protection device at the motor terminal or breaker side. This protective device is surge absorber(SA) such as ZnO and RC type. In this study, we analyzed whether there is any effect when two type SA is applied to the VCB multi reignition surge. We confirmed that ZnO SA is slightly more effective than RC SA for reduction of multi reignition surge.