Abstract
The study about three-phase synthetic making test using DC power has been performed in order to increase the making test capacity on Vacuum Circuit Breaker. And, it made possible to solve the limitations that short-circuit testing facilities can not fulfill the testing requirements of VCB exceeding three-phase 36[kV] 31.5[kA]. By using DC power and high speed spark-gap switch, this method made the equivalence with the pre-arc that occurred during the making process under the fault condition of power system. As results, KERI(Korea Electrotechnology Research Institute) could have capacity to carry out type test for VCB under three-phase 52[kV] 40[kV], which satisfies the IEC Standard.
Keywords
Short-Circuit Generator; Synthetic Making Test; Medium Voltage Circuit Breaker; Pre-Arc; DC Power;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Guy St-Jean, "Ren Fu Wang, Equivalence Between Direct and Synthetic Short-Circuit Interruption Tests on HV Circuit Breakers", IEEE Power Engineering Review, pp. 45-46, July 1983.
2 Rene Peter Paul Smeets, Wim A. van der Linden, "Verification of the Short-circuit Current Making Capability of High-Voltage Switching Devices", IEEE Transaction on Power Delivery, Vol.16, No.4, Oct. 2001. pp.611-618.   DOI
3 K. Suzuki, S. Nishiwaki, H. kawano. K, Kudo, K. Miyazaki, N. Miyake, H. Ikeda, "CHARACTERISTIC OF LARGE CURRENT MAKING SWITCH TO VERIFY MAKING PERFORMANCE OF HIGH VOLTAGE SWITCHGEAR", Gas Discharges and their Applications, 17th International Conference of IEEE, 7-12. Sept. 2008, pp.541-544.
4 IEC 62271-100 Ed. 2.0, High-voltage switchgear and controlgear-Part 100: Alternating-current circuit-breakers, April 2008.
5 IEC 62271-101 Ed. 1.1, High-voltage switchgear and controlgear - Part 101: Synthetic testing, Nov. 2010.
6 STL guide to the interpretation of IEC 62271-100 and IEC 62271-101, June 2009.