Abstract
This paper describes electric shock accidents on a 4.16 kV class circuit breaker for power plant. Electric shock accidents mostly involve damage of human life, in comparison with electrical fire, rate of human death tend to be higher in electric shock accidents. Specially, in a high voltage facilities rate of human death comprised about 43.7% by electric shock accidents. If electric shock accidents happen in a 4.16 kV class circuit breaker for power plant, then the power plant discontinue power production. Electric shock accidents in a power plant have a great ripple effect such as an electric power shortage. In this paper, we analyzed electric shock accidents on a 4.16 kV class circuit breaker for power plant. From the analysis results, we confirmed a cause of electric shock accidents on a 4.16 kV class circuit breaker, it happened by defect of interlock equipment or occurrence of breakdown between first feeder contactor and shielding plate. In order to reduce electric shock accidents on a 4.16 kV class circuit breaker, the power plant should consider improvement of interlock equipment and insulation of feeder contactor in circuit breaker.
Keywords
electric shock; 4.16 kV circuir breaker; feeder contactor; shielding plate; power plant;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 National fire data system Korea, 2012 Fire Statistics, 2012.
2 Massimo Mitolo, "Shock Hazard in the Presence of Protective Residual Current Devices", IEEE Trans. on Industry Applications, pp. 1552-1557, 2010.
3 D.-W. Kim, "Electrical Disaster Prevention Methods through the Analysis of 2011 Statistics in Korea", Safety World, pp. 7-10, 2102.
4 S. -W. Choi, "A Study on the In-depth Analysis of Cause and Characteristic for Recent Electric Shock Accident", Journal of the Korean Society of Safety, Vol. 29, No. 2, pp. 7-11, 2014.   과학기술학회마을   DOI
5 Y. -J. Cho, et al, "An Electric Shock by an Electric Leakage of a Traffic Signal Pole", Korean Journal of Forensic Science, Vol. 5, No. 2, pp. 135-142, 2004.
6 Korea Electrical Safety Corporation, A Statistical Analysis on the Electrical Accident, No. 22, 2012.
7 D.-W. Kim, et al, "Statistical Analysis on the Electrical Shock in Korea 2011", 2012 Fall Conference of Korean Institute of Illumination and Electrical Installation Eng., pp. 29-30, 2012.
8 D.-W. Kim, et al, "Prevention Techniques of Electrical Fire and Electrical Shock Caused by Leakage Current", Journal of Korean Institute of Illumination and Electrical Installation Eng., Vol. 27, No. 6, pp. 82-87, 2013.   과학기술학회마을   DOI