• 제목/요약/키워드: Heat exchange control

검색결과 83건 처리시간 0.027초

Design and the characteristic analysis of experimental system for automatic control education

  • Kim, Dong-Hwa
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 2000년도 제15차 학술회의논문집
    • /
    • pp.350-350
    • /
    • 2000
  • Since the heat exchange system, such as the boiler of power plant, gas turbine, and radiator require a high rate heat efficiency and the efficiency of these systems is depended on the control methods. However, it is important f3r operator to understand control system of these systems. In order to properly apply control equipment to these process control systems, such as boiler, any other heat process, or process control system it is necessary to understand the basic aspects and operation principle of the process that relate control, interrelationships of the process characteristics, and the dynamics that are involved. Generally, PID controllers are used in these systems but it is difficult for engineer to understand the complex dynamics and the tuning method because of the coupling action and disturbance in the system loop. In this paper, we design an effective experimental system fur automatic control education and analyze its characteristics through experimental system and industrial plant control software to study how they can team automatic control system by experiments.

  • PDF

개량형 열회수 시스템의 열교환 성능 (Heat Exchange Performance of Improved Heat Recovery System)

  • 서원명;윤용철;권진근
    • 생물환경조절학회지
    • /
    • 제12권3호
    • /
    • pp.107-113
    • /
    • 2003
  • 본 연구에서는 온실의 온풍식 난방시스템 연통에 장착할 수 있는 폐열 회수기의 성능 개선을 목적으로 기 설계된 세 가지 열교환 장치와 기존의 장치에서 열교환 면적과 파이프의 두께 및 공기흐름 방향을 개량한 새 열교환 장치에 대해 열회수 성능을 실험적으로 비교 분석하였다. 그 결과 기존의 열 교환장치인 A형, B형 및 C형의 열회수 성능은 동일 송풍전입에서 각각 42.2%, 40.6% 및 54.4% 정도였으나 , 새로 개량된 D형은 69.2%로써 가장 현저히 높게 나타났다. 그러나 열회수용 공기의 흐름방향 변화에 따른 열회수 성능 개선효과 (A형 대비 B형)는 없는 것으로 나타나 적정 송풍기 용량이라면 직선형이 공기의 흐름방향 180${\circ}C$ 굴절시키는 헤어핀형보다 효과적인 것으로 판단된다. 결국 열회수 성능은 열회수 시스템의 열교환 면적과 열교환 파이프의 두께 및 풍속에 크게 좌우되는 것으로 나타났다. 따라서, 열교환 파이프의 내구성 등 을 고려하여 기능한 한 범위 내에서 열 교환면적을 증대시키거나 열교환 파이프의 두께를 앓게 하고 풍속을 증대시키는 것이 열회수 성능 개선효과와 직결됨을 알 수 있었다. 그리고 송풍기 용량이 필요이상으로 큰 경우, 소비전력이 많게 되는 등의 문제가 있기 때문에 적정용량 및 제품의 안정성을 고려하여 선택해야 할 것으로 판단되었다.

스마트폰을 이용한 열교환기 환기장치의 제어 및 계측 (Control and Monitor of Heat Exchange Ventilation Facility by Smart Phone)

  • 정명진;이진호;홍종성
    • 한국정보통신학회:학술대회논문집
    • /
    • 한국정보통신학회 2015년도 추계학술대회
    • /
    • pp.1027-1029
    • /
    • 2015
  • 열교환기 환기장치는 실내로부터 배출되는 고온의 배기류를 이용하여 내부 환기를 위하여 투입되는 차가운 외기를 가온시킨다. 이를 통해 환기로 인해 발생되는 에너지 비용의 절약을 도모할 수 있고, 차가운 외기의 유입으로 인한 열적 균일성 감소 및 그에 기인한 호흡기성 질병 발생을 미연에 방지하는 효과가 있다. 본 연구에서는 열교환기 환기장치의 원격제어 및 원격계측을 위한 제어 및 계측 시스템을 개발하고 개발된 열교환기 환기장치의 제어 및 계측 시스템을 육계 사육장에 설치하여 내부의 온도와 습도의 원격제어 및 원격계측을 통해 성능검증을 수행하였다. 성능검증실험에서 육계 사육장 내부에서 2도 이내의 온도 제어가 가능함을 확인하였다.

  • PDF

열교환기의 흐름개선을 통한 고효율 지열 히트펌프 시스템에 관한 연구 (A Study on High Efficiency Geothermal Heat Pump System by Improving Flow of Heat Exchanger)

  • 안성환;최재상;김상범;안형환
    • 한국가스학회지
    • /
    • 제21권4호
    • /
    • pp.42-46
    • /
    • 2017
  • 화석연료의 무분별한 사용으로 인한 이산화탄소의 대기 중 방출은 지구의 연평균 기온을 상승시키는 원인으로 작용하고 있다. 이를 해결하기 위한 대체에너지로써 지열은 연중 일정한 온도를 갖는 무한자원이다. 지열에너지를 널리 보급하기 위해서는 히트펌프의 성능과 지중열교환기의 열교환 효율이 매우 중요하다. 이에 본 연구는 히트펌프의 성능을 증가시키기 위해 팽창변을 이중으로 구성하고 지중열교환기의 열교환 효율을 높이기 위해 입출관과 유입관 사이에 간격유지부재를 사용하여 실험하였다. 실험한 결과 팽창변을 이중으로 구성하였을 때 냉난방 능력이 최대 11.4%가 증가됨을 얻을 수 있었고, 간격유지부재를 사용 시 열교환 효율이 17.5% 향상되었다. 이러한 결과를 토대로 지열시스템의 설치 시 히트펌프의 성능과 지중열교환기의 열교환 효율의 상승으로 인해 설치비용이 많이 절감될 것으로 판단된다.

Temporal and Spatial Characteristics of Sea Surface Winds over the Adjacent Seas of Korean Peninsular - Spectral Analysis.

  • Lee, Heung-Jae;Na, Jung-Yul;Han, Sang-Kyu
    • 한국해안해양공학회:학술대회논문집
    • /
    • 한국해안해양공학회 1995년도 정기학술강연회 발표논문 초록집
    • /
    • pp.20-25
    • /
    • 1995
  • Surface wind field over an ocean plays a very important role not only to generate wind-driven current, but also to control heat exchange between ocean and atmosphere. However, the surface wind-field used for the ocean circulation and heat exchange is usually estimated by indirect methods because of lack of observed wind data and incomplete spatial coverage. (omitted)

  • PDF

열회수장치에 의한 열회수성능 분석 (Analysis of Heat Exchanging Performance of Heat Recovering Device Attached to Exhaust Gas Duct)

  • 서원명;윤용철;강종국
    • 생물환경조절학회지
    • /
    • 제9권4호
    • /
    • pp.212-222
    • /
    • 2000
  • 본 연구는 온실 난방시스템의 연소 체임버에 부착된 연소가스 배출연통에 열회수기를 장착하여 배출가스로부터 열을 회수하는 열회수장치의 성능에 대해 실험·분석하였다. 열회수시스템은 LPG 연소 체임버와 두 개의 열회수기로 구성되어있다. 열회수기-A는 배기가스 연통에 직접 연결되어 있으며 열회수기-B는 열회수기-A에 직렬로 연결되어 있다. 회수되는 열량은 가스의 질량흐름율과 두 측점간의 엔탈피 차이로서 산정하였으며 5가지의 송풍전압별로 각 열회수기의 성능을 검토하였다. 각 열회수기의 공기튜브 다발에 공급된 공기와 튜브 다발에 가로질로 통과하는 연소가스간의 열교환, 열회수기 유·출입부간의 압력감소, 열회수기의 총열회수성능 등으로 온실의 연통을 통해 낭비되는 열을 회수하여 연료 절감 효과를 얻을 수 있는 최적의 열회수장치 설계용 기초자료 확보에 본 연구의 목적이 있다.

  • PDF

멀티형 공조시스템의 증발기 과열도에 관한 실험적 연구 및 냉매유량 제어 (Experimental Study of the Superheat and Control of the Refrigerant Flow-Rate in the Evaporator of a Multi-type Air-Conditioning System)

  • 김태섭;홍금식;손현철
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 2000년도 제15차 학술회의논문집
    • /
    • pp.221-221
    • /
    • 2000
  • The heat exchange part in a modern multi-type air-conditioning system employs multiple-pass heat exchangers. The heat-transfer performance of an each pass in such an exchanger depends strongly on the length of the two-phase region and the mass flow of the refrigerant. The total length and diameters of the pipes, the exit conditions, and the arrangement of each pass as well as the geometrical shape of the distributor at the branching sections are considered to be major factors affecting the heat-transfer performance. The refrigerant commonly used in these systems is HCFC-22. The two objectives of this paper are to investigate the characteristics of the refrigerant flow rate and the superheat in the evaporator of a multi-type air-conditioning system for a single or simultaneous operating conditions and to control the superheat and the refrigerant flow rate of the evaporator.

  • PDF

한국형발사체 3단 터빈배기부 개념설계 (Conceptual Design of Turbine Exhaust System for 3rd stage of Launch Vehicle)

  • 신동순;김경석;한상엽;방정석;김현웅;조동혁
    • 한국추진공학회:학술대회논문집
    • /
    • 한국추진공학회 2017년도 제48회 춘계학술대회논문집
    • /
    • pp.1068-1071
    • /
    • 2017
  • 3단 터빈배기부 구성은 터빈 플랜지, 열교환기, 배기덕트와 추력노즐로 이루어진다. 냉가스 가압 방식에 비하여 열교환기 가압 방식을 사용함으로서 추진제탱크 가압을 위한 헬륨가스 자체 무게와 저장 탱크 무게가 감소하는 장점이 있기 때문에 발사체에 열교환기를 사용한다. 가스발생기는 추진제 연료과농 조건에서 연소가 이루어지며, 연소가스 중에 그을음이 많이 포함되어 있기 때문에 열교환 효율이 감소하는 것을 고려하여 열교환기를 설계해야 한다. 본 논문에서는 터빈배기부 구성품 배치, 열교환기 내부 구조 및 제작성을 고려한 설계기법, 기 설계된 노즐 설계를 바탕으로 3단 터빈배기부 재 노즐 설계 형상에 대한 장점을 기술하였다.

  • PDF

개량형 열회수 시스템의 열교환 성능 실험 (Heat Exchange Performance of Improved Heat Recovery System)

  • 서원명;윤용철;권진근;박성우
    • 한국생물환경조절학회:학술대회논문집
    • /
    • 한국생물환경조절학회 2003년도 춘계 학술대회 논문집
    • /
    • pp.152-156
    • /
    • 2003
  • 우리나라 시설원예 면적은 최근 정체되는 기미를 보이긴 하지만, 아직도 시설원예 면적이 50,000ha 이상에 달하고 난방면적도 점점 증가되어 전체 면적 중에 난방면적이 차지하는 비율은 현재 12,300ha 정도인 24%이다. 난방기의 보급기의 보급도 매년 증가하여 '00년말 현재 127,560대 정도이다. 최근 국내 버섯 재배면적의 42% 차지하는 느타리(큰느타리 포함)버섯 재배사도 연중재배를 위하여 난방을 실시하는 농가가 점점 늘고 있고, 특히 새송이(큰느타리) 버섯 재배사의 대부분은 간이형 온실에서 냉난방 설비를 갖추어 연중재배를 하고 있다. (중략)

  • PDF