• Title/Summary/Keyword: Grounding test

Search Result 140, Processing Time 0.046 seconds

Transient impedance characteristics of counterpoise according to the soil structures (대지구조에 따른 매설지선의 과도접지임피던스 특성)

  • Lee, Bok-Hee;Li, Feng;Jung, Dong-Cheol;Kim, Ki-Bok;Cho, Sung-Chul
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.10a
    • /
    • pp.311-314
    • /
    • 2009
  • This paper presents the characteristics of grounding impedance of counterpoises buried at various soil structures. Grounding impedance measurements were made by the Fall-of-Potential method. The experiments were carried out in 50 m counterpoise of 25 $mm^2$ buried at a depth of 0.5 m. The test current was injected by the impulse generator having the front time of $1{\sim}60{\mu}s$. As a result, the soil structures greatly influences on the grounding impedance characteristics of counterpoise. The transient grounding impedances strongly depend on the injection mint and the front time of impulse current.

  • PDF

A Study on The Shunting Rates Evaluation of GIS type Grounding Systems (GIS형 접지계의 분류율 산정에 관한 연구)

  • Jung Gil-Jo;Kim Jae-Yee
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.4
    • /
    • pp.172-177
    • /
    • 2005
  • The testing and evaluating shunting rates of operating substations have become difficult recently due to various factors including increased fault current, limited area of urban substations and construction of substations in mountain location. In this paper, we have analysed the computation and measurement method of shunting currents that be applied grounding system maintenance of power substations. Also, simple and detailed test methods using 70Hz current injection are explained. A computer program is developed for a study on the shunting properties such as grounding impedance and shunting rates of grounding current, and the simulation results are compared with the measurement data to prove validity and effectiveness of the program and measurement method under commercial operation of a GIS type model substation respectively.

Measurement of Grounding Impedances in Large-scale Grounding Electrode Systems (대형접지전극시스템 접지임피던스의 측정)

  • Lee, Kyoung-Hoon;Choi, Jong-Hyuk;Choi, Young-Chul;Lee, Kyu-Sun;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.193-196
    • /
    • 2008
  • In these days, large structures are constructed and bonded with ground grid Because the distances between mesh and auxiliary electrodes are not enough in downtown areas, it is very difficult to measure the ground resistance of large scale grounding electrode systems. Actually the auxiliary electrodes for test are installed in grounding grid. This paper present the experimental results of ground resistance and impedance according to the location of auxiliary electrode. As a result, we get much lower resistances and impedances than real values the auxiliary electrodes are placed in the ground grid. In case that the auxiliary electrodes are located in the ground grid the resistances are very low and reactance only is inductive component.

  • PDF

Comparison of Theoretical Resu Its and Measured Data Using Hemispherical Water Tank Model for Potential Rise of Structure Grounding (구조체 접지의 전위상승에 대한 반구형 수조에 의한 측정값과 계산값의 비교)

  • Gil, Hyoung-Jun;Choi, Chung-Seog;Kim, Hyang-Kon;Han, Woon-Ki;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.111-114
    • /
    • 2005
  • This paper presents a comparison of experimental value by hemispherical grounding simulation system and calculated value by CDEGS program for ground potential rise of structure. When a test current flowed through structure grounding electrodes, ground potential rise was measured and analyzed for types of structure using the hemispherical grounding simulation system in real time, and was computed by means of CDEGS program. The model structures were designed and fabricated with two types on a scale of one-one hundred sixty. When the experimental data were compared with the theoretical values, the similar profile was shown. Therefore, the confidence of measurement was obtained. The distributions of ground surface potential are dependent on the resistivity and absorption percentage in concrete attached to structure.

  • PDF

Effects of Length of Down Conductor on Transient Ground Impedance (인하도선 길이에 따른 과도접지임피던스 특성)

  • Lee, B.H.;Jeong, D.C.;Lee, S.B.;Lee, T.H.;Jung, H.U.;Lee, K.S.;Lee, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2235-2237
    • /
    • 2005
  • This paper presents the transient impedance behaviors of grounding systems to lightning impulse current. The potential rise and effective impulse ground impedance of the test grounding electrodes were measured as a function of the rise time of impulse currents and lengths of down conductor. The transient ground impedances strongly depend on the configuration and size of grounding electrodes, the impulse current shapes and lengths of down conductor, and the inductance of reduce of grounding electrode inductance is an important factor to improve the transient ground impedance.

  • PDF

The Radiation Safety Management in the Animal Hospital Using Inspection Standard of Diagnosis Radiation System (진단용 방사선발생장치의 검사기준을 적용한 동물병원의 방사선 안전관리)

  • Kim, Sang-Woo;Rhim, Jea-Dong;Han, Dong-Kyoon;Seoung, Youl-Hun
    • Journal of the Korea Safety Management & Science
    • /
    • v.12 no.4
    • /
    • pp.73-80
    • /
    • 2010
  • The purpose of this study was to investigate the actual conditions of radiation safety supervision in animal clinics using inspection standard of X-ray generator for diagnosis. The surveys for inspection standard system, equipment condition, and safety supervision were carried out in 18 animal clinics randomly. The inspection standard included reproducibility of dose exposure, kVp, mAs, collimator accuracy test, collimator luminance test, X-ray view box luminance test, grounding system equipment test and external leakage current test. The surveys of equipment condition and safety supervision used one-on-one interview with 5 points measurement. As a result, 44.44% of reproducibility of dose exposure was proper, 81.25% of kVp test was good, and 100% of mAs test was appropriate. Also, 66.66% of collimator accuracy test was proper, 61.11% of collimator luminance test was good, 53.13% of X-ray view box luminance test was suitable. In addition, only 5.55% of grounding system equipment and ground resistance was proper, 63.64% of external leakage current test was appropriate in grounding system equipment test. The 100mA electric capacity of X-ray generator for diagnosis was popular with 44.44%, and its 55.56% was purchased used equipment. Monthly average of less than 50 times (61.11%) was top frequency in use, and no animal clinic had a thermo-luminescence dosimeter(TLD). The 16 animal clinics with radiation safety zone and 2 without radiation safety zone were appeared.

A study for numerical simulation about grounding of 105k tanker (LS-DYNA3D를 이용한 좌초 선박 손상평가)

  • Han, Dae-Suk;Rim, Chae-Whan;Lee, Tak-Kee;Lee, Jae-Myung
    • Journal of Navigation and Port Research
    • /
    • v.31 no.3 s.119
    • /
    • pp.213-221
    • /
    • 2007
  • Recently, environmental design are becoming a matter of grave concern in shipbuilding. Out of these concern, oil spilt which is induced by grounding accidents is very critical reason of the ocean pollution. Therefore, a series qf quarter of 105k tanker model grounding simulations were conducted to analyze it's characteristics for the accident. ship get using LS-DYNA3D. In this paper, to conduct whole simulations, a meshsize convergence test was carried out to determine appropriate meshsize for grounding test. After the series analysis. These results were analyzed as each case.

Establishment of EMTP Modeling Method Using Searching Coil Test for HVDC Submarine Cables (써칭코일 시험을 통한 HVDC 해저케이블 EMTP 모델링 기법 정립)

  • Jung, Chae-Kyun;Park, Hung-Sok;Yang, Byeong-Mo;Kang, Ji-Won;Lee, Jong-Beom
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.9
    • /
    • pp.1593-1599
    • /
    • 2010
  • This paper describes the EMTP modeling method using searching coil test for HVDC submarine cables. HVDC submarine cables consist of conductor, lead sheath and amore. It is different from general cable which is composed with just conductor and aluminium sheath. Therefore, the transient characteristics are totally different between HVDC submarine cable and general cable. However, the study on HVDC cable modeling and transient are insufficient. In this paper, EMTP modeling is performed according to grounding interval and grounding resistance, then they are compared with real test results by searching coil test.

Study on the Between the Grounding Resistance and Grounding Electrode using Mesh Grounding Electrodes and a Shielding Panel (메쉬접지전극과 차폐패넬을 이용한 접지저항 및 접지전극간의 영향에 관한 연구)

  • Leeg, Chung-sik;Cho, Moon-taek;Na, Seung-kwon
    • Journal of Advanced Navigation Technology
    • /
    • v.19 no.3
    • /
    • pp.230-236
    • /
    • 2015
  • In this paper, the electric potential of electrode surface is investigated by assuming them as two dimensional sets of point current sources. And, the simulated water tank is manufactured as a reduced scale of the earth. Henceforth, the adequate model electrode for test is decided to decrease experimental errors relevant to the limitation of the size of the water tank. The one of important things of this work, the deduction method of the potential interference factor is proposed, which used as the criterion of the potential interference according to the shape of conductors and the laying conditions, when multiple grounding conductors are situated at the same resistance grounding area. Also, the validity of this theory is verified from a numerical simulation of the grounding electrode to be used in experiments, and this study is realized by the verified theory and the simulated experiments.

Resistive Grounding Technique of Heat Sink for Reducing Radiation Noise

  • Ahn, Chang-Hoi;Oh, JaeHyun
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.5
    • /
    • pp.1724-1728
    • /
    • 2014
  • Heat sink has been used to help an electrical device operate in normal temperature condition. But heat sink radiates unwanted electromagnetic wave, which may cause electromagnetic interference problem. A resistance loaded grounding technique is proposed to reduce electromagnetic wave radiation by a heat sink. Numerical simulations are accomplished to find optimal loading resistance. Also electromagnetic fields radiated by from a heat sink are measured and compared with the simulation results. The test results verify the usefulness of the proposed technique.