• 제목/요약/키워드: Grounding System

검색결과 467건 처리시간 0.031초

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

  • Jung, Chae-Kyun;Jung, Yeon-Ha;Kang, Ji-Won
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권2호
    • /
    • pp.628-634
    • /
    • 2014
  • This paper investigates the transient characteristics of grounding systems used in under-ground distribution power cables. Recently, two kinds of grounding system are used for underground distribution cables in Korea. The first one is conventional multi-point grounding system, the other is newly proposed non-bundled common grounding system. The non-bundled common grounding system has an advantage the decreasing the power loss due to decrease of the shield circulation current. In this paper, the lightning overvoltage induced in neutral wire (in case of non-bundled common grounding system, overvoltage between opened neural wires and grounding in each phase) of these two kinds of grounding systems are estimated and compared by field tests and EMTP simulations. The EMTP simulation methods are firstly verified by comparison of measurement and simulation. Finally, the insulation level against lightning is expected by EMTP simulation results using verified model.

반구형 접지모의시스템을 이용한 접지전극의 형상에 따른 대지전위상승의 분석 (The Analysis of Ground Potential Rise for Shapes of Grounding Electrode Using Hemispherical Grounding Simulation System)

  • 길형준;최충석;이복희
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권7호
    • /
    • pp.319-325
    • /
    • 2005
  • In order to analyze ground potential rise of grounding system installed in buildings, the hemispherical grounding simulation system has been designed and fabricated as substantial and economical measures. Ground potential rise(GPR) has been measured and analyzed for shapes of grounding electrode using the system in real time. The system is apparatus to have a free reduced scale for conductor size and laying depth of a full scale grounding system and is constructed so that a shape of equipotential surface is nearly identified a free reduced scale with a real scale when a current flows through grounding electrode. The system was composed of a hemispherical water tank, AC Power supply, a movable potentiometer, and test grounding electrodes. The test grounding electrodes were fabricated through reducing grounding electrode installed in real buildings such as rod type, mesh grid type. When a mesh grid type was associated with a rod type, GPR was the lowest value. The proposed results would be applicable to evaluate GPR in the grounding systems. and the analytical data can be used 0 stabilize the electrical installations and prevent the electrical disasters.

탄소혼합물 접지전극의 접지임피던스의 특성 (Characteristics of Grounding Impedances of Carbon Compound Grounding Electrodes)

  • 이강수;이복희
    • 조명전기설비학회논문지
    • /
    • 제25권5호
    • /
    • pp.54-60
    • /
    • 2011
  • This paper presents characteristics of frequency-dependent grounding impedance and transient grounding impedance for the carbon compound grounding electrode used in the installation of computerized electronic equipment and lightning protection system. The frequency-dependent grounding impedances were measured by applying sinusoidal currents in the frequency range from 100 [Hz] to 10[MHz], and the transient grounding impedances were examined by subjecting the impulse current with the front-time between 1~80[${\mu}s$]. As a result, the ground resistance of the carbon compound grounding electrode is less than that of another type grounding electrodes. The transient grounding impedance is relatively low and the conventional grounding impedance is rather lower than the ground resistance. The frequency-dependent grounding impedance of the carbon compound grounding electrode is capacitive and the grounding impedance is decreased with increasing the frequency of injected currents. Therefore in the case that the carbon compound grounding electrode is jointly used with large-scaled grounding electrodes, it is possible to reduce the high frequency grounding impedance of the integrated grounding electrode system.

축소모델 기법을 이용한 대규모 접지계의 특성분석 (Characteristic Analysis elf Large Grounding system by Using Reduced Scale Model Method)

  • 장석훈;이재복;명성호;조연규;김점식
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권3호
    • /
    • pp.162-167
    • /
    • 2004
  • The scale model grounding systems to study the behavior of grounding system in uniform soils have been designed and fabricated. Constructional details and instrumentation have been discussed. To verify the accuracy of the results obtained from the experimental tests, they have been compared with computer calculation results. Also, in order to assess the effectiveness of bonding two grounding systems, grounding grid conductors which were downsized as a scale factor of 100:1 were analyzed by using the scale model method. A profile of GPR(Grounding Potential Rise) of each case was measured. The scale model grounding system presented in this paper can be valuable tool to analyze the ground potential profile and ground resistance of practical grounding system.

서울메트로 접지설비 표준화 방안 연구 (A Study on the Unification of the Grounding System of SeoulMetro)

  • 김균식;박한용;백유호
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2007년도 춘계학술대회 논문집
    • /
    • pp.1027-1036
    • /
    • 2007
  • Since the opening of the Seoul Metro in 1974, the electric railway passengers have been increased rapidly and as the advanced equipments(OC,PSD) were introduced, additional power facilities were built in a limited area for the comfortable transportation environment. Present grounding system were built according to old Electric equipment standards and all the electric signal, communication and electronic equipments were built only for the purposes of protecting building structure, people and electronic equipments. Grounding system which was additionally built in the limited area caused problems with the building structure and it caused secondary damages when earth fault happens. One of the problems is grounding system of the building structure; grounding system does not work properly since grounding equipments are not separated from each other. So, existing grounding system needs to be improved and unified grounding system in the building should be established. The purposed of this study is to analyze all the grounding systems that had been built in different year and to establish unified grounding system of Seoul Metro.

  • PDF

현장조사에 의한 접지시스템의 전기안전성 평가 (Assessment of Electrical Safety for Grounding System by Investigation on the Spot)

  • 길형준;김동우;김동욱;이기연;김향곤
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2008년도 춘계학술대회 논문집
    • /
    • pp.361-364
    • /
    • 2008
  • This paper deals with assessment of electrical safety for grounding system of buildings by investigation on the spot at construction site. The investigation was carried out for grounding method, grounding type, shape of grounding electrode, grounding for lightning protection system, continuity of steelwork in reinforced concrete structure and so on. The investigation on the spot was performed by researcher, engineer with over fifteen years of industry experience all over the country. As a result of investigation on the spot to 13 buildings, common grounding method was dominant. A new grounding system based on international standards includes unity grounding system, structure grounding utilizing steel reinforced concrete, equipotential bonding. use of surge protective device.

  • PDF

서울메트로 PSD장비 탄소접지모듈 설치 사례 (The example of the Carbon Grounding Modules installation for PSD systems at a subway station, Seoulmetro)

  • 정용기;현용섭;송병권;김용협
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2008년도 춘계학술대회 논문집
    • /
    • pp.292-298
    • /
    • 2008
  • Seoul Metro and Seoul Metropolitan Rapid Transit Corp. have started installing screen doors at subway platforms to improve the environment of subways and prevent passengers' accidents since 2006. They are still installing screen doors at subway platforms and Metropolitan Rapid Transit Corporations in other areas are also proceeding with installment of screen doors or making preparations for it. Grounding is necessary for installing PSD systems. In case that PSD grounding is connected with existing electrical equipment grounding system, it was decided to install separate grounding for safe operation of PSD system and passenger safety. However, it's very difficult to install new grounding at the subway station compound. A way to improve this condition is that we proceed with grounding by composing grounding station by carbon grounding rod. This paper will mainly deal with how to design and construct carbon ground rod, which has been applied to PSD system grounding since 2006, including its experimental examples. In this paper, ways to secure ground resistance below 5 ohms, which is resistance necessary for PSD grounding, and to compose grounding system were also discussed. Furthermore, a ground test to check the ability to fulfill a role of PSD grounding system was conducted. As a result of applying carbon grounding module, PSD system is being operated without any problem and the installment of PSD system will be continuously expanded in the future. It's also thought that a way to integrate grounding of each functional room which has been installed at the subway station compound and to arrange equipotential grounding should be reviewed and performed promptly.

  • PDF

낙뢰 Surge 방호를 위한, 독립접지를 공통접지로 개선하는 효율적인 방법에 대한 연구 (A Study on the Effective Surge Protection Method from Induced Lightning Surgeto Improve Isolate Grounding to Common Grounding)

  • 전형구;우제욱;서용준
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2011년도 정기총회 및 추계학술대회 논문집
    • /
    • pp.1459-1467
    • /
    • 2011
  • 본 논문은 낙뢰 Surge 방호를 위하여 독립접지를 공통접지로 개선하는 효율적인 방법을 제안하였다. 낙뢰 Surge 방호를 위해서는 등전위 이론에 근거하는 공통접지방식이 적합하고, 중성선이 있는 전원계통에서는 공통접지방식을 사용하는 것이 국제적으로 통용되는 기술규격이다. 따라서 낙뢰 Surge에 취약한 문제점을 갖고 있는 기존의 중성선이 없는 전원계통과 독립접지방식을 중성선이 있는 전원계통과 공통접지방식으로 개선을 하고, 정전압소자를 이용하여 낙뢰 Surge를 방호하는 효율적인 등전위 시스템 구축 방법을 제안한다.

  • PDF

낙뢰 Surge 방호를 위한, 독립접지를 공통접지로 개선하는 효율적인 방법에 대한 연구 (A Study on the Effective Surge Protection Method from Induced Lightning Surge to Improve Isolate Grounding to Common Grounding)

  • 우제욱
    • 한국항해항만학회:학술대회논문집
    • /
    • 한국항해항만학회 2013년도 추계학술대회
    • /
    • pp.215-218
    • /
    • 2013
  • 본 논문은 낙뢰 Surge 방호를 위하여 독립접지를 공통접지로 개선하는 효율적인 방법을 제안하였다. 낙뢰 Surge 방호를 위해서는 등전위 이론에 근거하는 공통접지방식이 적합하고, 중성선이 있는 전원계통에서는 공통접지방식을 사용하는 것이 국제적으로 통용되는 기술규격이다. 따라서 낙뢰 Surge에 취약한 문제점을 갖고 있는 기존의 중성선이 없는 전원계통의 독립접지방식을 중성선이 있는 전원계통의 공통접지방식으로 개선을 하고, 정전압소자를 이용하여 낙뢰 Surge를 방호하는 효율적인 등전위 시스템 구축 방법을 제안한다.

  • PDF

저압 전원계통 접지방식별 뇌서지보호성능 (Protection ability for lightning surge according to the grounding system of low voltage power systems)

  • 이복희;이규선;최종혁;유양우;김동성;강성만;안창환
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2009년도 추계학술대회 논문집
    • /
    • pp.343-346
    • /
    • 2009
  • The grounding system of low voltage power systems is TT grounding system in Korea. In order to follow the international standard, TN grounding system is adopted. However, the performance of grounding systems has not been evaluated. This paper deals with the experimental results of protection ability of grounding system when lightning surge invades to the neutral line of low voltage power system. As a result, the TT grounding system is most frail for the lightning surge and it does not protect the electrical devices. On the other hand, the TN grounding system perfectly protects the electrical equipment and prevents the electric shock for human through the equipotential bonding. In case of TN system with supplement grounding, it is very important to lower the supplement grounding resistance to protect the electrical equipment and electric shock for human.

  • PDF