Characteristics of Grounding Impedances of Carbon Compound Grounding Electrodes

탄소혼합물 접지전극의 접지임피던스의 특성

  • Received : 2011.01.18
  • Accepted : 2011.03.29
  • Published : 2011.05.31

Abstract

This paper presents characteristics of frequency-dependent grounding impedance and transient grounding impedance for the carbon compound grounding electrode used in the installation of computerized electronic equipment and lightning protection system. The frequency-dependent grounding impedances were measured by applying sinusoidal currents in the frequency range from 100 [Hz] to 10[MHz], and the transient grounding impedances were examined by subjecting the impulse current with the front-time between 1~80[${\mu}s$]. As a result, the ground resistance of the carbon compound grounding electrode is less than that of another type grounding electrodes. The transient grounding impedance is relatively low and the conventional grounding impedance is rather lower than the ground resistance. The frequency-dependent grounding impedance of the carbon compound grounding electrode is capacitive and the grounding impedance is decreased with increasing the frequency of injected currents. Therefore in the case that the carbon compound grounding electrode is jointly used with large-scaled grounding electrodes, it is possible to reduce the high frequency grounding impedance of the integrated grounding electrode system.

Keywords

References

  1. R Kosztaluk, M. Loboda, D. Mukhedkar, “Experimental Study of Transient Ground Impedances”, IEEE Tras. PAS, Vol.100, No.11, pp.4653-4660, 1981 https://doi.org/10.1109/TPAS.1981.316807
  2. B. R. Gupta and B. Thapar, “Impulse impedance of grounding grids”, IEEE Trans. Vol.PAS-99, No.6, pp.214-218, 1980. https://doi.org/10.1109/61.108910
  3. S. Visacro, “A didactic general approach of grounding behavior for lightning currents”, Proceedings of the 27th ICLP-. International Conference on Lightning Protection, Avignon, France, Vol. 1, pp. 508-513, 2004.
  4. 이복희, 이승칠, “접지의 핵심 기초 기술” 도서출판 의제, pp.1-23, 1999.
  5. Leonid Grcev, “High frequency performance of ground rods in highly resistive soil”. International Conference on Grounding and Earthing. pp.85-89, 2000.
  6. L Grcev, “Modeling of grounding systems for better protection of communication installations against effects from electric power system and lightning”, IEE Conf. Pub., No. 484, pp. 461-468, 2001. https://doi.org/10.1049/cp:20010637
  7. IEEE Std 81.2-1991, “IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems”, IEEE Inc., pp. 4-15, 1991.
  8. 최종혁, 최영철, 이복희, “수직 접지전극의 접지임피던스 측정에서 도전유도에 의한 오차 평가”, 전기학회 논문지, Vol. 58, No. 9, pp.1778-1783, 2009.
  9. Bok-Hee Lee, Dong-Cheol Jeong, Su-Bong Lee and Keun-Chul Chang, “Effective Impulse Impedances of Deeply Driven Grounding Electrodes”, KIEE Int. Trans. on EA, Vol.4-C, N0.5, pp.207-214, 2004
  10. Silverio Visacro, “A Comprehensive Approach to the Grounding Response to Lightning Currents”, IEEE Trans. on P.D., Vol. 22 No. 1, January, 2007 https://doi.org/10.1109/TPWRD.2006.876707
  11. S. Visacro, G. Rosado, “Response of Grounding Electrodes to Impulsive Currents: An Experimental Evaluation”, IEEE Trans. on E.C., Vol. 51, No. 1, pp. 161-164, 2009 https://doi.org/10.1109/TEMC.2008.2008396
  12. Leonid Grcev, “Impulse Efficiency of Ground Electrodes”, IEEE Trans. on P.D. Vol. 24, No. 1, pp.441-451, 2009. https://doi.org/10.1109/TPWRD.2008.923396
  13. 이복희, 정동철, 이수봉, “봉상 접지전극에서 전류유입 위치에 따른 임펄스접지임피던스 특성”, 조명.전기설비학회 논문지, Vol.19, No.1, pp.94-100, 2005.
  14. Y.Chen and P.Chowdhuri, “Correlation between laboratory and field tests on the impulse impedance of rod-type ground electrodes”, IEE Proc.-Gener. Transm. Distrib. Vol. 150. No. 4, pp.420-426, July 2003. https://doi.org/10.1049/ip-gtd:20030246
  15. KS C IEC 62305-1, 피뢰시스템-제1부: 일반원칙, pp.3-15, 2007.