• Title/Summary/Keyword: Generator Stator Winding

Search Result 124, Processing Time 0.022 seconds

Analysis of Insulation Characteristic for Small Hydro Generator (소수력발전기 절연특성분석)

  • Oh, Bong-Keun;Chang, Jeong-Ho;Lee, Kwang-Ho;Kang, Dong-Sik
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2008.05a
    • /
    • pp.142-145
    • /
    • 2008
  • Electrical insulation of small hydro generator stator winding is one of the most important parts in generator facilities. Some stator winding insulation problems can be identified through analysis of insulation diagnostic test. So, Diagnosis of stator winding insulation is an important measure of ensuring the safe operation and extending the remaining life of small hydro generator. This paper presents case studies of insulation failure in generator stator windings and the results of insulation diagnostic test for small hydro generator stator windings. Especially, Conducting the insulation diagnostic test before the generator installed in site is very important process to keep the good insulation condition in service.

  • PDF

An Experimental Study of Water Absorption Characteristics for Generator Stator Winding Insulation (발전기 고정자 권선 절연재 흡습 특성에 관한 실험적 연구)

  • Bae, Y.C.;Lee, D.S.;Kim, H.S.;Kim, Y.H.;Lee, H.
    • Proceedings of the KSME Conference
    • /
    • 2004.04a
    • /
    • pp.426-431
    • /
    • 2004
  • Leaking water coolant into stator electrical insulation is a growing concern for the aging water-cooled generator since leaks in the generator water-cooled stator winding can affect machine availability and insulation life. But a domestic techniques of such field are insufficient and depend wholly on GE or TOSHIBA technique. Therefore this paper introduces measuring principle and developed measuring system, which has been used to detecting wet absorption. We accomplished the experiment with a stator promotion of virtue which is used in actual power plant. Also, Experimental method of generator stator winding, which is investigated into wet absorption test.

  • PDF

Assessment of Insulation Condition in Operating Large Turbine Generator (운전중인 대형 터빈발전기에서 절연상태 평가)

  • 김희동
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.6
    • /
    • pp.324-329
    • /
    • 2004
  • Six stator slot couplers(SSC) and a flux probe sensor installed on the stator winding slots of large turbine generator. Assessment of insulation condition has been based upon the measurements of partial discharge(PD) of stator windings and shorted-turn of rotor windings in operating large turbine generator. The maximum PD magnitude(Qm), normalized quantify number(NQN), PD pattern and shorted-turn were measured using on-line insulation condition monitoring system. The NQN and Qm of slot PD side in the phase A are indicated the highest value in six SSC sensors. Monitoring system results showed that discharge at conductor surface and internal discharge were detected at the surface of stator winding and in voids of the groundwall insulation. Insulation of stator and rotor windings in large turbine generator was judged to be in good condition.

On-line partial discharge measurement techniques of hydro-generator windings (수력 발전기 권선에서의 운전중 부분방전 측정기법)

  • 황동하;김진봉;김용주;박명수;김택수
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.45 no.2
    • /
    • pp.294-300
    • /
    • 1996
  • In hydro-generator, a groundwall insulation of stator windings gradually deteriorates due to mechanical, thermal, electrical and environmental stresses. These stresses combine to result in loose windings, delamination of the stator insulation and/or electrical tracking of the endwinding, all of which can lead to stator insulation failures. Conventionally, off-line tests such as partial discharge measurement, DC/AC current and .DELTA.tan.delta. tests has been used for estimation of winding condition. However, off-line test requires large power supply and generator outage. In addition, major cause of insulation problems such as loose wedges and slot dischages may not be found with off-line diagnoses. This paper introduces the on-line partial discharge measurement techniques using frequency spectrum analyzer(FSA) for the generator stator windings. The experimental results from the UIAM #1 hydro-generator confirms a optimistic application of on-line generator diagnosis method as a reliable tool for evaluation of winding condition.

  • PDF

Assessment of Insulation Condition in Gas Turbine Generator Stator Windings (가스터빈 발전기 고정자 권선의 절연상태 평가)

  • Kim, Hee-Dong;Yang, Gyu-Hyun;Ju, Young-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.8
    • /
    • pp.1423-1428
    • /
    • 2010
  • The results of off-line and on-line diagnostic tests performed on the stator winding of an air-cooled gas turbine(G/T) generator are reported in this paper. Off-line diagnostic tests included measurements of the ac current, dissipation factor(tan${\delta}$), and partial discharge(PD). Six epoxy-mica capacitors were installed in the three phases of G/T generator for performing on-line diagnostic testing with the turbine generator analyzer(TGA). The TGA showed that the normalized quantity number(NQN) and the PD magnitude($Q_m$) were high in phase A of the stator winding. Internal discharges were generated in phases B and C, and slot discharge occurred in phase A. According to the trend analyses of the NQN and $Q_m$ values available for insulation condition assessment for G/T generator stator windings, it was concluded that phases B and C were in good condition, whereas phase A has been significantly deteriorated.

Control and Implementation of Dual-Stator-Winding Induction Generator for Variable Frequency AC-Generating System

  • Bu, Feifei;Hu, Yuwen;Huang, Wenxin;Shi, Kai
    • Journal of Power Electronics
    • /
    • v.13 no.5
    • /
    • pp.798-805
    • /
    • 2013
  • This paper presents the control and implementation of the dual-stator-winding induction generator for variable frequency AC (VFAC) generating system. This generator has two sets of stator windings embedded into the stator slots. The power winding produces the VFAC power to feed the loads, and the control winding is connected to the static excitation controller to control the generator for output voltage regulation with speed and load variations. On the basis of the idea of power balance, an instantaneous slip frequency control (ISFC) strategy using the information of both the output voltage and the output power is used in this system. A series of experiments is carried out on a 15 kW prototype for verification. Results show that the system has good static and dynamic performance in a wide speed range, which demonstrates that the ISFC strategy is suitable for this system.

Water Absorption Sensor of Generator Stator Bar Insulation using Cross Capacitance (크로스 커패시턴스를 이용한 발전기 고정자 권선 절연물 흡습 측정 센서)

  • Bae, Yong-Chae;Kim, Hee-Soo;Lee, Doo-Young;Lee, Wook-Ryun;Lee, Rae-Deok
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.10
    • /
    • pp.1972-1977
    • /
    • 2011
  • The mechanical integrity of generator stator windings is one of the critical point because the electric power is generated and conducted to power system through these windings. To cool down the heat emitted from generator winding during its operation, a majority of generators use de-mineralized water characterized by high cooling efficiency. Contrary to such the excellent cooling efficiency, however, the damaged bar insulations attributed to the absorption of cooling water in the generator stator winding lead to highly time- and cost consuming efforts as well as to service deterioration due to unexpected forced outage of generator. It is described that the new design of water absorption sensor using cross capacitance for generator in power plant in order to increase the reliability of water absorption diagnostics for generator stator bar insulation.

Microstructure Analysis of Large Turbine Generator Stator Insulations (대형 터빈발전기 고정자 권선의 미세구조 분석)

  • Kim, Hee-Dong;Ju, Young-Ho;Song, Seong-Il
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1452-1454
    • /
    • 2002
  • Large turbine generator(rated 22kV) has failed in the stator winding area during normal operation. The capacitance and tan${\delta}$ were measured by Schering bridge in the zone 1, 2 and zone 3-6 stator windings. The capacitance and tan${\delta}$ in the zone 1, 2 of stator winding were higher than those of zone 3-6 in the stator winding. Experiments on microstructure property were conducted in the zone 1, 2 and zone 3-6 insulations, which were drawn out from stator windings of the large turbine generator. Microstructure analysis was characterized using scanning electron microscope(SEM). SEM results indicated that several isolated delaminations occurred at the interface of mica/epoxy insulations. Both thermal and mechanical aging cause the delamination.

  • PDF

A Study on the Evaluation Criteria for the Remaining Life of Hydro-Generator Stator Insulation (수력 발전기 고정자 권선의 절연수명 평가기준 설정에 관한 연구)

  • Hwang, D.H.;Kim, Y.J.;Kim, J.B.;Park, M.S.;Kim, H.G.;Lee, S.J.
    • Proceedings of the KIEE Conference
    • /
    • 1996.07c
    • /
    • pp.1769-1773
    • /
    • 1996
  • The remaining life of generator stator winding has been the controversial issue amomg many experts in this area. The report from Japan claims that they can predict the remaining life of generator winding, while the North American has the negative opinion about it. This study aimed at verifying the validity of both Japanese criteria and North American argument on evaluation of generator winding insulation. Non destructive and destructive tests were performed on two hydro-generators. The test results showed that the trend analysis of stator winding insulation was the better option.

  • PDF

A Study on Insulation Diagnosis by Partial Discharge Spectroscopy of Generator Stator Winding (발전기 고정자 권선의 부분방전 특성을 이용한 절연진단 연구)

  • Kang, D.S.;Kim, Y.J.;Kim, K.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1993.07b
    • /
    • pp.584-587
    • /
    • 1993
  • Mica, which have a good thermal and electrical characteristics, while will cleave easily at these layers. In order to bond mica materials soldily, mica/epoxy composite insulation materials were developed for generator stator winding. There are lots of problems such as delamination and partial discharge of these insulation materials caused by mechanical, electrical and thermal aging. Several experiments have been conducted in order to find the useful diagnostic parameters from the partial discharge phenomena by applying a new measurement techniques. this paper deals with the partial discharge pulse characteristics, which may be a useful diagnostic concept in predicting insulation condition of generator stator insulation materials. Long term insulation aging test shows that partial discharge phase angle an magnitude are identified as one of the main key techniques for insulation diagnosis on generator stator winding.

  • PDF