• Title/Summary/Keyword: GIS(Gas Insulated Substation)

Search Result 49, Processing Time 0.035 seconds

A Study on the Algorithm for Detection of Partial Discharge in G15 Using Wavelet Transform (웨이브렛 변환을 이용한 GIS의 부분방전 검출 알고리즘에 관한 연구)

  • 강진수;김철환
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.52 no.1
    • /
    • pp.25-34
    • /
    • 2003
  • Gas insulated switchgear(GIS) is an important equipment in a substation. It is highly desirable to measure a partial discharge(PD) in GIS which is a symptom before insulation breakdown occurs. The issue is that the PD signal is weak and sensitive to external noise. In this paper, the algorithm for detection of PD in GIS using wavelet transform is proposed. The wavelet transform provides a direct quantitative measure of spectral content, "dynamic spectrum", in the time-frequency domain. The recommended mother wavelet is 'Daubechies' wavelet. 'db4', the most commonly applied mother wavelet in the power quality analysis, can be used most properly in disturbance phenomena which occurs rapidly for a short time. Through the procedure of wavelet transform, noise extraction and reconstruction, the signal is Analyzed to determine the magnitude of PD in GIS. In experimental results, we can know that partial discharge is exactly detected in combination of Dl and D2 using wavelet transform.transform.

Lightning protection in an 154kV GIS connected by oil-filled cables (O.F. Cable에 연결된 154kV GIS의 뇌보호)

  • 정태호
    • 전기의세계
    • /
    • v.29 no.5
    • /
    • pp.315-320
    • /
    • 1980
  • It has been appeared and widely used today SF6 Gas Insulated Substation(Hereafter called GIS) for the power supply to the densely populated area due to the superior insulation withstand ability of SF6 Gas. And to maximize the compact effect of this substation, it is normal practice to connect underground cables. If it is possible to elieminate the redundant lightning arresters using the physical characterestics of travelling waves in underground cables, economical advantages can be obtained together with easy maintenances. It is presented in this paper the possiblity of eliminating the transformer protection lightning arresters under some conditions for the 154kV GIS's (BIL:750kV) which Korea Electric Co. plans to construct using the general purpose digital computer program.

  • PDF

Digital Time-Domain Simulation of Ferroresonance of Potential Transformer in the 154 kV GAS Insulated Substation

  • Shim, Eung-Bo;Woo, Jung-Wook;Han, Sang-Ok
    • KIEE International Transactions on Power Engineering
    • /
    • v.11A no.4
    • /
    • pp.9-14
    • /
    • 2001
  • This paper reports a set of digital time-domain simulation studies conducted on 154 kV wound Potential Transformer(PT) int he 154 kV Gas Insulated Substation(GIS). The Electro-Magnetic Transient Program(EMTP) is used to develop the PT model and conduct the transient studies. The accuracy of the PT model is verified through comparison of the EMTP simulation results with those obtained from the field test results. The investigations shows that the developed model can accurately predict PT transient resonance, especially, the phenomenon of ferroresonance. The model is developed not only to determine impact of transients on PT response but also to design ferroresonance suppressor devices of PT. And it can also be used to predict PT transient response on power system monitoring and protection scheme.

  • PDF

The Study of The Calibration Method for The UHF PD Detection in GIS (GIS에서 UHF 부분방전 검출법의 교정방안 연구)

  • Lee, W.Y.;Chong, J.K.;Choi, Y.K.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2290-2292
    • /
    • 1999
  • The Ultra-High Frequency(UHF) method for detecting a partial discharge in Gas-Insulated Substation(GIS) has some advantages compared to a conventional method(IEC 270) but there is a shortage in view of a quantitative analysis. Therefore, this paper describes the implementation of a calibrator and the calibration process based on it. And its characteristics are confirmed through the experiment using the 362kV GIS chamber.

  • PDF

Performance Verification and Improvement of UHF Sensor for the Increasement of the Partial Discharge Detection Reliability (부분방전검출 신뢰도 향상을 위한 UHF 센서개선 및 성능검증)

  • Kim, Won-Gyu;Kim, Min-Soo;Baek, Young-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.10
    • /
    • pp.1461-1466
    • /
    • 2014
  • GIS(Gas Insulated Switchgear) is important power apparatus which have strong dielectric strength, supply electric power and is a part of the power system. Most substation type is configured as GIS. Recently, because of continuous increasement of GIS demand resulted from high quality & big capacity of electric power, the necessity of the preventive & diagnosis system is being expanded gradually. GIS partial discharge occurred on the UHF band is detected effectively by the method to IEC 60270 that recommend to be able to detect the apparent minimum discharge, 5 pC. Additionally, the UHF sensor should be installed to detect PD signal if Partial discharge signal, 5 pC occur in every part of GIS. Currently PD diagnosis system applying UHF sensor for GIS with various voltage level like 154 kV, 345 kV, 765 kV have been operated. And it is necessary to measure and analyze insulation breakdown phenomenon of inside GIS exactly. In this paper, we proposed Fat-dipole patch UHF sensor that is developed and more sensitive, excellent wide-range characteristic than the exising UHF sensor. And we performed KERI (Korea Electrotechnology Research Institute) reference test, which showed the excellent result for the all tests.

The Development and the Performance Test of Bay Controller for the High-Voltage Gas Insulated Switchgear (초고압 가스절연개폐기의 베이 컨트롤러 개발 및 성능시험)

  • Woo, Chun-Hee;Lee, Bo-In
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.2
    • /
    • pp.179-184
    • /
    • 2010
  • The digital substation automation system has contributed hugely to increasing the stability of power systems by providing not only protection and control of power systems but diagnostic features alongside them. Digital substation automation systems in the scale of substations consist of integrated operation systems and intelligent electronic devices. The main intelligent electronic devices currently in use are digital protection relays and the bay controllers in Gas insulated switchgears. Proficiently accomplishing the coordination of protection within the power system as a means of ensuring reliability and contriving for the stability of power supply through connection of function, the application of bay controllers is crucial, which collectively manage the protection relay at the bay level in order to achieve both. In this research, the bay controllers to be used in high-voltage Gas insulated switchgear has been localized, and in particular, the logic function and editor required in order to minimize the complicated hardware-like cable connections in the local panel have been developed. In addition, to ensure the strength and reliability of the bay controller hardware developed herein, the type tests from KERI have been successfully completed.

Construction of 154kV Intelligent Substation for Verification Test (154kV급 실증시험용 인텔리전트 변전소 구축)

  • Chung, Y.H.;Kim, M.S.;Kim, J.B.;Lee, H.S.;Choi, I.H.;Lee, D.I.
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.456-457
    • /
    • 2006
  • We have carried out the construction of the 154kV intelligent substation with KEPRI. The Intelligent substation is built in Gochang testing facility of KEPCO and consists of electronic instruments for GIS(gas insulated switchgear), digital control panel, remote monitoring and diagnosis system, and digital relay system. Rogowski coil type CT(RCT) and capacitive voltage divider(CVD) are introduced compared with the instrument transformer of conventional type. Digital control Panel(DCP) replaces the LCP(local control panel) which is drived for mechanical operation. For the monitoring of the condition of GIS and TR, various sensors are used. In this Paper, we mention the synopsis and report the progress state of project.

  • PDF

Construction of 154kV Intelligent Substation for Verification Test (154kV급 실증시험용 인텔리전트 변전소 구축)

  • Chung, Y.H.;Kim, J.B.;Lee, H.S.;Choi, I.H.;Lee, D.I
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.661-662
    • /
    • 2007
  • We have carried out the construction of the 154kV intelligent substation with KEPRI. The intelligent substation is built in Gochang testing facility of KEPCO and consists of electronic instruments for GIS(gas insulated switchgear), digital control panel, remote monitoring and diagnosis system, and digital relay system. Rogowski coil type CT(RCT) and capacitive voltage divider(CVD) are introduced compared with the instrument transformer of conventional type. Digital control panel(DCP) replaces the LCP(local control panel) which is drived for mechanical operation. For the monitoring of the condition of GIS and TR, various sensors are used. In this paper, we mention the synopsis and report the progress state of project.

  • PDF

The Development of 800kv 50kA 8000A Gas Insulated Switchgear (800kV 50kA 8000A 가스절연개폐장치(GIS) 개발)

  • Nam, K.C.;Yoon, J.H.;Choi, B.H.;Lee, H.W.;Heo, J.C.;Park, S.J.;Ban, S.G.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1804-1806
    • /
    • 2002
  • KEPCO has a plan to operate 765kV electric power network from June, 2001, by the KEPCO's plan. We have developed the extra-high voltage class equipments for 765kV substation. Inpecial, we have proceeded the developments of 800kV Gas Insulated Switchgear from January 1998 to now. Until now we completed the test of a general characteric tests of GIS, the short-circuit test of GCB. DS. ES. HSGS.

  • PDF

Computer Aided Identification of Inter-Layer Faults in Gas Insulated Capacitively Graded Bushing during Switching

  • Rao, M.Mohana;Dharani, P.;Rao, T. Prasad
    • Journal of Electrical Engineering and Technology
    • /
    • v.4 no.1
    • /
    • pp.28-34
    • /
    • 2009
  • In a Gas Insulated Substation (GIS), Very Fast Transients (VFTs) are generated mainly due to switching operations. These transients may cause internal faults, i.e., layer-to-layer faults in a capacitively graded bushing as it is one of the most important terminal equipment for GIS. The healthiness of the bushing is generally verified by measuring its leakage current. However, the change in current magnitude/pattern is only marginal for different types of fault conditions. Leakage current monitoring (LCM) systems generate large amounts of data and computer aided interpretation of defects may be of great assistance when analyzing this data. In view of the above, ANN techniques have been used in this study for identification of these minor faults. A single layer perceptron network, a two layer feed-forward back propagation network and cascade correlation (CC) network models are used to identify interlayer faults in the bushing. The effectiveness of the CC network over perceptron and back propagation networks in identification of a fault has been analysed as part of the paper.