• Title/Summary/Keyword: Fire Dynamics Simulator (FDS)

Search Result 141, Processing Time 0.026 seconds

COMPUTATIONAL SIMULATION OF FIRE SUPPRESSION SYSTEM FOR CABINS OF SHIPBOARD ENCLOSURE (선박 거주구역용 소화시스템의 전산 시뮬레이션)

  • Jung, I.S.;Chung, H.T.;Han, Y.S.
    • Journal of computational fluids engineering
    • /
    • v.21 no.4
    • /
    • pp.40-45
    • /
    • 2016
  • The numerical simulation has been performed to predict the performance of the fire suppression system for cabin of shipboard enclosure. The present study aims ultimately at finding the optimal parametric conditions of the mist-injecting nozzles using the CFD methods. The open numerical code was used for the present simulation named as FDS (Fire Dynamics Simulator). Application has been done to predict the interaction between water mist and fire plume. In this study, the passenger cabin was chosen as simulation space. The computational domains for simulation in the passenger cabin were determined following the fire scenario of IMO rules. The full scale of the flow field is $W{\times}L{\times}H=4{\times}3{\times}2.4m^3$ with a dead zone of $W{\times}L{\times}H=1.22{\times}1.1{\times}2.4m^3$. The water mist nozzle is installed in ceiling center of 2.3 m height from the floor, and there are six mattresses and four cushions in the simulation space. The combination patterns of orifices to the main nozzle and the position to install nozzles were chosen as the simulation parameters for design applications. From the present numerical results, the centered-located nozzles having evenly combined orifices were shown as the best performance of fire suppression.

ANALYSIS OF TURBULENT BOUNDARY LAYER OF NATURAL CONVECTION CAUSED BY FIRE ALONG VERTICAL WALL (수직벽 화재 자연대류에 의한 난류 경계층 열유동 특성 해석)

  • Jang, Yong-Jun;Kim, Jin-Ho;Ryu, Ji-Min
    • Journal of computational fluids engineering
    • /
    • v.21 no.4
    • /
    • pp.1-10
    • /
    • 2016
  • The analysis of characteristics of turbulent flow and thermal boundary layer for natural convection caused by fire along vertical wall is performed. The 4m-high vertical copper plate is heated and kept at a uniform surface temperature of $60^{\circ}C$ and the surrounding fluid (air) is kept at $16.5^{\circ}C$. The flow and temperature is solved by large eddy simulation(LES) of FDS code(Ver.6), in which the viscous-sublayer flow is calculated by Werner-Wengle wall function. The whole analyzed domain is assumed as turbulent region to apply wall function even through the laminar flow is transient to the turbulent flow between $10^9$<$Gr_z$<$10^{10}$ in experiments. The various grids from $7{\times}7{\times}128$ to $18{\times}18{\times}128$ are applied to investigate the sensitivity of wall function to $x^+$ value in LES simulation. The mean velocity and temperature profiles in the turbulent boundary layer are compared with experimental data by Tsuji & Nagano and the results from other LES simulation in which the viscous-sublayer flow is directly solved with many grids. The relationship between heat transfer rate($Nu_z$) and $Gr_zPr$ is investigated and calculated heat transfer rates are compared with theoretical equation and experimental data.

Numerical Study on the Attenuation Effect of Water Mist on Thermal Radiation (미세물분무에 의한 열복사 감쇠 효과에 대한 수치해석 연구)

  • Ko, Gwon Hyun
    • Fire Science and Engineering
    • /
    • v.34 no.4
    • /
    • pp.7-12
    • /
    • 2020
  • A numerical study was conducted to investigate the effects of the spray characteristics of water mist on the attenuation of thermal radiation. The attenuation process of the thermal radiation, generated from a hot surface panel, passing through the water mist was calculated via Fire Dynamics Simulator (FDS), and the effects of the flow rate, droplet mean diameter, and spray injecting angle of the water mist were analyzed. The results indicated that the increase in flowrate and decrease in droplet size led to an increase in the attenuation of thermal radiation. As the thermal radiation passed through the spray droplets, the effect of the spatial distribution of spray droplets was verified by calculating the thermal radiation attenuation at different spray injecting angles. The results indicated that the radiation attenuation increases as the spray angle increases. This implies that a wider distribution of spray droplets, irrespective of the droplet size and flowrate, increases the attenuation effect on thermal radiation.

Large Eddy Simulation of Backdraft Using the Eddy Dissipation Concept Combustion Model (Eddy Dissipation Concept 연소모델을 적용한 백드래프트 대와동모사 연구)

  • Ha, Suim;Oh, Chang Bo
    • Fire Science and Engineering
    • /
    • v.33 no.5
    • /
    • pp.48-54
    • /
    • 2019
  • A Large Eddy Simulation (LES), adopting the Eddy Dissipation Concept (EDC) 1-step model, was successfully performed for backdraft phenomena. The activation energy of the finite chemistry reaction in the EDC 1-step model was adjusted to simulate the backdraft. The prediction of the EDC 1-step model was similar to that of the Mixing-Controlled Fast Chemistry (MCFC) model, except when the backdraft occurred. The EDC 1-step model could be used to simulate the experimental peak pressure, but not the first peak pressure of the backdraft.

Analysis of Prediction Results and Grid Size Dependence According to Changes in Fire Area (화원면적 변화에 따른 격자 크기 의존도 및 예측결과 분석)

  • Yun, Hong-Seok;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.33 no.6
    • /
    • pp.9-19
    • /
    • 2019
  • In fire simulations for building fire safety evaluation, changes in the fire area and grid size can significantly influence the prediction results. Therefore, the effects of area changes of the fire source with identical maximum heat release rates on the prediction results of a compartment fire were investigated. The dependence of the prediction results on the grid size using the identical fire area was also examined. No significant changes were observed in the thermal and chemical characteristics of the fires with variable grid sizes, even though the fire area was changed when six or more grids were set based on the fire diameter. In addition, changes in the fire area caused significant differences in the prediction of major physical quantities associated with available safety egress time (ASET) within a compartment. However, the fire area changes did not considerably influence the overall fire characteristics outside the compartment after reaching a certain distance from the opening.

A study on grid aspect ratio of fire dynamics simulator (FDS의 격자 종횡비에 관한 연구)

  • Kim, Won Ouk;Park, Woe-Chul
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.39 no.9
    • /
    • pp.923-928
    • /
    • 2015
  • The FDS is one of the most used programs for fire analysis and needs an optimal grid selection for an accurate analysis. This study selected various grid aspect ratios (ARs) for selection of optimal grid and analyzed them with FDS v 6.1.2. A calculation time of 10 min. was used, which is enough to obtain the time average value of temperature changes. Temperature, visibility, and the time average value of mass balance are obtained from 200-600 s, which is a period of maintaining quasi-steady state. Two polyurethane fires of 1 [MW] and 2 [MW] in two enclosures of $10{\times}10{\times}3[m^3]$ and $20{\times}20{\times}3[m^3]$ were considered. Time variations of heat release rates, temperature, visibility, and mass balance were compared for ARs from 1-6. The heat release rates were accurate for all aspect ratios regardless of fire and enclosure sizes. The quasi-steady state temperature and visibility were well predicted for $AR{\leq}5$. Temperature drop and skewness of mass conservation, however, increased with increasing aspect ratio. Therefore, careful investigation of the grid size is recommended in performance-based design when $AR{\geq}3$, where temperature and visibility in early stage of a fire are important parameters. For accurate simulations of enclosure fires, grid sizes of 0.1~0.2 [m] and smaller in the vertical direction and $AR{\leq}2$ are recommended.

A Study on the Adequacy of the Installation Location of the Air Supply Damper of the Attached Actual Smoke Facility (부속실제연설비 급기댐퍼의 설치위치 적정성 연구)

  • Yang, Sung-Hoon
    • Proceedings of the Korean Society of Disaster Information Conference
    • /
    • 2022.10a
    • /
    • pp.193-194
    • /
    • 2022
  • 본 연구에서는 특별피난계단의 전실에 설치되는 부속실제연설비가 화재 시 발생한 연기가 부속실 내로 역류하지 않는 급기댐퍼의 적정한 설치위치를 알아보고자 하였으며, 이를 확인하기 위하여 FDS(Fire Dynamics Simulator)을 사용 하였다. 시뮬레이션 Case 총 15가지로 구분하고, 방연풍속은 총 64개의 지점에서 측정하는 시뮬레이션을 수행하였다. 시뮬레이션 결과 출입문 상부 및 하부에서 역 기류가 발행하는 Case가 있었으며, 대부분 출입문 하부에서의 연기 유입이 예상되는 경우가 많았다. 방연풍속은 측정 포인트 64점에서 관련기준에 단 한 곳도 미달하지 않고 만족하는 경우는 총 단 4가지 Case로서 매우 제한적인 것을 알 수 있었다. 그만큼 급기댐퍼의 위치 및 급기방향에 따라 부속실 제연설비의 성능이 다양하게 나타날 수 있다는 것이다. 본 연구를 바탕으로 앞으로 실물실험을 통하여 구체적인 자료가 입증되길 바라고, 더불어 부속실 제연설비의 성능을 개선하는 데 있어 도움이 되었으면 한다.

  • PDF

Measurements of the Heat Release Rate and Fire Growth Rate of Combustibles for the Performance-Based Design - Focusing on the Plastic Fire of Commercial Building (성능위주설계를 위한 가연물의 열발생률 및 화재성장률 측정 - 판매시설의 플라스틱 화재를 중심으로 -)

  • Jang, Hyo-Yeon;Nam, Dong-Gun
    • Fire Science and Engineering
    • /
    • v.32 no.6
    • /
    • pp.55-62
    • /
    • 2018
  • To improve the prediction result with enhanced reliability of domestic Performance-Based Design (PBD), actual scale fire tests were carried out on products made of plastics from sales facility combustibles. The commercial buildings were separated into single and multiple combustibles for the experimentation of fire spread caused by the sales shelves where the various combustible materials are displayed. A according to the maximum heat release rate, exposed area and weight of the combustible material, the results revealed a linear relationship of as 93% and 89%. In addition, analysis of the gas concentrations for various combustibles showed that $CO_2$ has a linear relationship, whereas the CO concentration indicated exponential function. These results can be applied to reliable fire source information in PBD of plastic fire source in commercial buildings. This may be applied as fire source information representative of a plastic fire in commercial buildings through additional experiment using the area of the shelf in actual commercial buildings.

Numerical Study on the Effect of Heat Release Rate and Interior Opening on Fire Flow Velocity in the Case of Interior Fire in an Apartment Building (공동주택 화재 시 화재크기 및 실내 개구부 크기가 화재풍속에 미치는 영향에 관한 수치해석적 연구)

  • Seo, Chanwon;Shin, Weon Gyu
    • Fire Science and Engineering
    • /
    • v.28 no.5
    • /
    • pp.37-43
    • /
    • 2014
  • In the case of interior fire in an apartment building, contamination of vestibule area by fire smoke before air fan operating when fire doors are open makes the evacuation of people very difficult. In order to investigate the effect of heat release rate (HRR) and interior opening on fire flow velocity, numerical simulations using Fire Dynamics Simulator were carried out. In simulations, actual dimensions and configuration of an apartment building were considered and interior leakage and HRR were varied. From simulation results, it was found that fire flow velocity distribution is significantly influenced by HRR and interior opening resulting in the change of the location of a neutral plane. Also, it is shown that there is a larger difference of the fire flow velocity between upper and lower part of the fire door when the neutral plane becomes closer to the ceiling.

Risk Evaluation and Analysis on Simulation Model of Fire Evacuation based on CFD - Focusing on Incheon Bus Terminal Station (CFD기반 화재 대피 시뮬레이션 모델을 적용한 위험도 평가 분석 -인천터미널역 역사를 대상으로)

  • Kim, Min Gyu;Joo, Yong Jin;Park, Soo Hong
    • Spatial Information Research
    • /
    • v.21 no.6
    • /
    • pp.43-55
    • /
    • 2013
  • Recently, the research to visualize and to reproduce evacuation situations such as terrorism, the disaster and fire indoor space has been come into the spotlight and designing a model for interior space and reliable analysis through safety evaluation of the life is required. Therefore, this paper aims to develop simulation model which is able to suggest evacuation route guidance and safety analysis by considering the major risk factor of fire in actual building. First of all, we designed 3D-based fire and evacuation model at a subway station building in Incheon and performed fire risk analysis through thermal parameters on the basis of interior materials supplied by Incheon Transit Corporation. In order to evaluate safety of a life, ASET (Available Safe Egress Time), which is the time for occupants to endure without damage, and RSET (Required Safe Egress Time) are calculated through evacuation simulation by Fire Dynamics Simulator. Finally, we can come to the conclusion that a more realistic safety assessment is carried out through indoor space model based on 3-dimension building information and simulation analysis applied by safety guideline for measurement of fire and evacuation risk.