• Title/Summary/Keyword: FACTS(flexible ac transmission system)

Search Result 90, Processing Time 0.029 seconds

The Design and Implementation of TCSC Control Hardware for KERI Simulator (시뮬레이터급 TCSC 제어기 설계 및 구현)

  • Jeon J.H.;Kim K.S.;Kim J.W.;Chun Y.H.
    • Proceedings of the KIPE Conference
    • /
    • 2003.07a
    • /
    • pp.158-161
    • /
    • 2003
  • KERI simulator is a analog simulator for power system at KERI power system division lab. It consist of many power system components, which are a 380V 5kVA generators, scale-downed transmission line modules, transformers, switches, PACTS(Flexible AC Transmission System) devices. As a FACTS device module, 20kVA TCSC(Thyristor Controlled Series Compensator) module was designed and implemented. In this paper, we present the design and implementation of TCSC control hardware for KERI simulator

  • PDF

The Design and Implementation of 20kVA TCSC Simulator (20kVA 시뮬레이터급 TCSC 설계 및 제작)

  • Jeon J.H.;Kim K.S.;Kim J.W.;Chun Y.H.
    • Proceedings of the KIPE Conference
    • /
    • 2003.07a
    • /
    • pp.154-157
    • /
    • 2003
  • In this study, we design and implement the 20kVA TCSC(Thyrister Controlled Series Compensator) simulator It was tested on the KERI simulator The KERI simulator is a analog simulator for power system at the KERI power system division lab. It consist of many power system components, which are a 380V 5kVA generators, scale-downed transmission line modules, transformers, switches, FACTS(Flexible AC Transmission System) devices. In this paper, we present the design and implementation of 20kVA TCSC simulator and its basic test results.

  • PDF

A Study on the SVC System Stabilization Using a Neural Network (신경회로망을 이용한 SVC 계통의 안정화에 관한 연구)

  • 정형환;허동렬;김상효
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.14 no.3
    • /
    • pp.49-58
    • /
    • 2000
  • This paper deals with a systematic approach to neural network controller design for static VAR compensator (SVC) using a learning algorithm of error back propagation that accepts error and change of error as inputs, the momentum learning technique is used for reduction of learning time, to improve system stability. A SVC, one of the Flexible AC Transmission System(FACTS), constructed by a fixed capacitor(FC) and a thyristor controlled reactor(TCR), is designed and implemented to improve the damping of a synchronous generator, as well as controlling the system voltage.TO verify the robustness of the proposed method, we considered the dynamic response of generator rotor angle deviation, angular velocity deviation and generator terminal voltage by applying a power fluctuation and rotor angle fluctuation in initial point when heavy load and normal load. Thus, we prove the usefulness of proposed method to improve the stability of single machine-infinite bus with SVC system.

  • PDF

전력계통용 파워일렉트로닉스 기기

  • 대한전기협회
    • JOURNAL OF ELECTRICAL WORLD
    • /
    • s.277
    • /
    • pp.69-77
    • /
    • 2000
  • 최근 전력설비 운용상의 여러 가지 과제에 대한 유망한 해결책으로서 파워일렉트로닉스 기기를 사용한 FACTS(Flexible AC Transmission System)가 주목을 받고 있다. 그 중에서도 자려식 변환기를 사용한 FACTS기기는 계통의 유효전력$\cdot$무효전력을 계통의 상태에 의존하지 않고 자유롭게 제어할 수 있어, 계통운용의 유연성을 비약적으로 확대할 수 있는 가능성이 있다. 미쓰비시전기는 전력기기간 계통에서의 자려식 변환기 응용의 파이어니어로서 1991년 간사이전력(주) 태산개폐소에 80Mvar SVG(전지형 무효전력발생장치)를 납품하였으며 또한 자원에너지청의 ''연계강화기술개발'' 보조사업으로 도쿄전력(주)을 비롯하여 전력회사 각사, 전원개발(주)와 (재)전력중앙연구소의 지도 하에 3단자 BTB(Back to Back) 실증시스템용으로 세계 최초의 6인치 GTO(Gate Turn-off Thyristor)를 사용한 53MVA의 자려식 변환기를 제작납품하여 수백MVA 클래스의 자려식변환기 제작기술을 확립하였다. 또한 최근에는 동사가 개발한 신소자 GCT(Gate Commutated Turn-off Thyristor)는 지금까지 대용량 자려식 변환기의 커다란 과제였던 운전손실을 반감할 수 있을 것으로 기대되고 있다. 한편 배전 분야에서는 전압변동, 고조파, 순간전압강하 등의 과제가 증가하고 있어, 미쓰비시전기는 이에 응할 수 있는 파워일렉트로닉스 기기로서 콤팩트 SVG(Static Var Generator), SSTS(Solid-state Transfer Switch), 액티브필너를 다수 납품하여 전력품질문제 해결에 공헌하고 있다.

  • PDF

The analysis of Kangjin UPFC faults (강진 UPFC 고장실적 분석)

  • Kim S.Y.;Lee W.K.;Chang B.H.;Jeon Y.S.;Lee S.I.;Bae J.H.
    • Proceedings of the KIPE Conference
    • /
    • 2006.06a
    • /
    • pp.450-452
    • /
    • 2006
  • 한전 전력연구원은 1990년대부터 FACTS(유연송전시스템 : Flexible AC Transmission System)을 연구해 온 이래 80MVA UPFC(종합조류제어기 : Unified Power Flow Controller)를 2003. 5월 신강진전력소관내 강진변전소에 준공하였다. 효성과 지멘스의 기술제휴를 통해 개발된 강진변전소 UPFC를 통해 FACTS 엔지니어링, 제어 알고리즘 및 유지보수 기술이 확보되었다. 초창기 안정화운전 기간동안 제어핵심기술과 일부예비품의 미확보가 가용율(Availability)에 큰 영향을 미쳤으나, 현재 강진 UPFC는 안정적으로 운전되고 있다. 본 논문에서는 그 동안의 강진 UPFC의 고장내용을 종합분석하고, 가용율을 정리하였다.

  • PDF

UPFC Modelling on RTDS (RTDS(Real Time Digital Simulator)를 이용한 UPFC(Unified Power Flow Controller) 모델링)

  • 김광수;이상중
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2001.11a
    • /
    • pp.47-50
    • /
    • 2001
  • In order for effective operation of existing power systems, introduction of the so-called FACTS(Flexible AC Transmission System) such as SVC and UPFC etc, is unavoidable. The UPFC(Unified Power Flow Controller) is composed of STATCOM(Static Compensator) and SSSC(Static Synchronous Series Compensator), and is used to control the magnitude and phase angle of injected sources which are connected bothin series and in parallel with the transmission line to control the power flow and bus voltages. This paper presents a UPFC simulation on RTDS. The voltage and phase angle of a system have been analyzed by regulating the firing angle inside the UPFC.

  • PDF

Dynamic Characteristics Analysis of Multi-bridge PWM Inverter SSSC (다중브리지 PWM 인버터로 구성된 SSSC의 동특성 분석)

  • 한병문;박덕희;김성남
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.50 no.6
    • /
    • pp.296-302
    • /
    • 2001
  • This paper proposes a SSSC based on multi-bridge inverters. The dynamic characteristic of the proposed SSSC was analyzed by EMTP simulation and a scaled hardware model, assuming that the SSSC is inserted in the transmission line of the one-machine-infinite-bus power system. The proposed SSSC has 6 multi-bridge inverters per phase, which generates 13 pulses for each half period of power frequency. The proposed SSSC generates a quasi-sinusoidal output voltage by 90 degree phase shift to the line current. The proposed SSSC does not require the coupling transformer for voltage injection, and has a flexibility in operation voltage by increasing the number of series connection.

  • PDF

Sensitivity Analysis of Power System Including Series FACTS Device Based on RCF Method (직렬형 FACTS 설비를 포함하는 전력시스템의 RCF 해석법에 기초한 감도해석)

  • Kim, Deok-Young
    • Journal of the Korea Institute of Information and Communication Engineering
    • /
    • v.15 no.3
    • /
    • pp.624-631
    • /
    • 2011
  • In this paper, the RCF method is used in sensitivity analysis problems of the discrete power systems including both series FACTS equipments such as TCSC in transmission lines and generator controllers such as Exciter and PSS in generator terminal. To apply the RCF method in small signal stability problems of discrete power systems, state transition equations of controllers and TCSC are derived and the sensitivity calculation algorithm using state transition equations in discrete time domain is devised. The results of eigenvalue analysis showed that the variations of eigenvalues after periodic switching operations of TCSC can be calculated exactly by the RCF method and the change of firing angles in TCSC have important effect to determine the stability of power systems.

The First Introduction of UPFC to the KEPCO Power Network in Korea : Pilot Plant (UPFC의 국내 계통 적용에 관한 연구 : Pilot Plant)

  • Yoo, H.H.;Kim, J.M.;Lee, H.S.;Lim, S.J.;Kim, S.Y.
    • Proceedings of the KIEE Conference
    • /
    • 2002.11b
    • /
    • pp.307-311
    • /
    • 2002
  • 최근의 전력 공급 시장에서는 전력 공급의 유연성을 확보함과 동시에 고품질의 전력을 높은 신뢰성을 가지면서 수용가에 공급하는 송전기술에 대한 관심이 높아지고 있다. 이러한 시장의 요구에 부응하여 송전 시스템의 유효전력 및 무효전력을 능동적으로 제어할 수 있는 FACTS(Flexible AC Transmission System) 기기의 개념이 도입되었다 FACTS기술의 개념은 기존에 수동적으로 제어하였던 선로의 전압, 임피던스 및 위상각을 능동적으로 제어함으로써 전력공급의 유연성 및 신뢰성을 높이는 것이다 국내에서는 과거 일련의 project를 통하여 인버터형 FACTS 기기외 국내 적용을 위한 연구를 수행해 왔으며, 그 결과를 토대로 한전 전력연구원, (주)효성, 미국 Siemens사 및 국내 연구소와 협동연구의 형태로 한전의 154kV 계통에 적용되는 80MVA급 UPFC(Unified Power Flow Controller) pilot plant project를 진행하고 있다. 본 pilot plant project를 통하여 인버터형 FACTS 기기인 UPFC를 실제계통에 설치, 운영함으로써 향후 한국의 기간 계통인 345kV 송전 시스템에 적용할 시스템의 사양 및 운용전략을 도출할 계획이다. 본 논문에서는 국내 계통의 특징, pilot plant가 설치될 지역의 계통현황 및 기기의 사양을 소개하고 기기의 현장 설치 및 시험 진행 상황에 대하여 설명하였다.

  • PDF

Modeling and Analysis of the KEPCO UPFC System by EMTDC/PSCAD

  • Yoon, Jong-Su;Kim, Soo-Yeol;Chang, Byung-Hoon;Lim, Seong-Joo;Choo, Jin-Boo
    • KIEE International Transactions on Power Engineering
    • /
    • v.3A no.3
    • /
    • pp.148-154
    • /
    • 2003
  • This paper describes the development of KEPCO's 80MVA UPFC electromagnetic transient model and the analysis of its performance in the actual Korean power system. KEPCO's 80MVA UPFC is currently undergoing installation and will be ready for commercial operation from the year 2003. In order to apply a new FACTS device such as the UPFC to the actual power system, the utility needs, in advance, both load flow stability studies and transient studies. Therefore, KEPRI, the research institute of KEPCO, developed a detailed transient analysis model that is based on the actual UPFC S/W algorithm and H/W specifications. This simulation model is implemented by an EMTDC/PSCAD package. The results of the simulation show the effectiveness of UPFC operation in the KEPCO power system.