• 제목/요약/키워드: Electric transmission tower foundation

검색결과 11건 처리시간 0.038초

암반 앵커기초로 시공된 송전철탑 구조물의 거동특성에 관한 연구 (Behavior of Electric Transmission Tower with Rock Anchor Foundation)

  • 김경열;홍성연;이대수
    • 한국지반공학회:학술대회논문집
    • /
    • 한국지반공학회 2010년도 추계 학술발표회
    • /
    • pp.605-614
    • /
    • 2010
  • In this paper, the initial behavior of transmission tower was analyzed. This tower was firstly constructed by rock anchor foundation in domestic 154 kV transmission line and wireless real-time monitoring system was installed to obtain the measured data for analysis of the structure behavior. For this purpose, 16 strain gauges was installed in anchors of foundation and strain gauges, clinometers, anemoscope and settlement sensors was installed at superstructure. As the results, the main factor which influence the behavior of superstructure is wind velocity, wind direction, rainfall and temperature change. Especially, the uplift load at stub of transmission structure revealed about 35.4 percentages of design load. Hereafter the long term stability will be analyzed.

  • PDF

가공송전철탑 경량화 설계에 관한 연구 (A Study of the Slim Design of Overhead Transmission Tower)

  • 이정원;이원교
    • 한국전기전자재료학회논문지
    • /
    • 제23권7호
    • /
    • pp.560-565
    • /
    • 2010
  • This paper presents the design factor of an overhead transmission tower structure in order to reduce the tower weight. The behaviour of transmission tower structures are affected by the horizontal angle of the tower structure, the equivalent wind pressure group, the slope of the main post of the tower, the separation of the internode and the use of high-strength materials in their construction. Tower weight can be reduced by approximately 30% reduce weight by means of optimal design based on a consideration of all the above factors. In addition, the design of the foundation of the tower with the shear key installation to increase horizontal support together with a modified angle of inclination to the ground can reduce by about 37% the amount of concrete used during construction. The area of ground disturbed by the construction of the tower foundation can thus be reduced by approximately 33%. Therefore it is possible to build an environmently-friendly T/L tower with the mechanical properties of existing towers.

가공 송전 철탑기초 설계 및 시공 방법 연구 - 심형기초를 중심으로 - (A Study on the Transmission Tower Foundation Design and Construction Method - A Focus of Cylindrical Foundation -)

  • 장석한;김희광;이강현;한경수;함방욱;정기선
    • 전기학회논문지
    • /
    • 제56권6호
    • /
    • pp.1031-1034
    • /
    • 2007
  • Electric transmission lines pass through a variety of area. Foundation supporting the conductors and tower are selected properly in accordance with external load, for example dead load, wind load, snow load, construction load etc, and topography and geology condition. Typical types of foundation are as follows: pad foundation for small load and hard soil or rock in mountainous area, pile foundation for medium or large load and soft soil in plain field area. This paper introduced cylindrical foundation design & construction for large load and mountainous area. This foundation failure mode against pulling-out show splitting failure by tensile force toward circumferential direction.

송전철탑의 기초침하에 대한 안정성 평가 (Stability evaluation of foundation settlement of power transmission tower)

  • 이대수;조화경;김대홍;함방욱
    • 한국지반공학회:학술대회논문집
    • /
    • 한국지반공학회 2005년도 춘계 학술발표회 논문집
    • /
    • pp.687-696
    • /
    • 2005
  • Safety diagnosis was conducted to evaluate the long-term stability evaluation of power transmission tower of which deformation of the upper structural elements occurred. To assess the cause of the structural deformation, field investigation including BIPS, down-hole test, concrete pile coring and finite element analysis were carried out. From these studies, the major cause of deformation was found due to the heavily fractured layer and weathered soil topography at the pile tip area. The cement-milk grouting method was proposed to reinforce these weak zone around the pile tip area. Also, the increase of cross-section and stiffness for steel members of upper tower structures was suggested. Instrumental monitoring was proposed as well to verify reinforcing effect.

  • PDF

가공송전선로의 철탑 접지저항 저감효과 분석 (Analysis of Grounding resistance reduction effect of Transmission tower)

  • 민병욱;김태영;박봉규;최진성;강연욱;박광욱;배현권
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.453-454
    • /
    • 2011
  • With the transmission line the ratio of lightning breakdown the while whole breaking down is occupying a high share with average 72%, is a tendency which increases continuously. In order decreasing the back flashover faults from like this lightning breakdown, it is very important to maintain grounding resistance of tower below target. In this paper, we synthetically analyzed the grounding resistance reduction effect of tower foundation and standard ground connection from construction site, and investigated efficiency for ways to increase the length of counter poise and expand the size of conductivity concrete materials.

  • PDF

항타 진동이 송전탑 기초에 미치는 영향 연구 (The Influence of Ground Vibration Caused by Pile Driving on Power Line Tower Foundation)

  • 박정봉
    • 화약ㆍ발파
    • /
    • 제27권2호
    • /
    • pp.42-47
    • /
    • 2009
  • 파일 항타, 발파 등의 공사시 발생하는 진동은 근거리에 위치한 송전탑 기초 및 철탑에 영향을 미치게 된다. 일반적으로 진동은 이격거리에 따라 전파특성이 다르게 나타나는데, 송전탑과 진동원의 이격거리에 따라 진동을 제어할 수 있는 공법으로 공사를 수행해야 한다. 본 연구에서는 송전탑 기초와 기초 주변 지반에 대하여 항타시 진동을 측정하였으며, 항타시 발생되는 진동이 기초지반과 송전탑 기초에 전파되는 특성을 지반의 탁월 주파수와 송전탑 탁월주파수와의 관계를 통하여 고찰하였다.

기초침하에 의해 손상된 송전철탑 구조물의 구조성능개선 (Structural Restoration for the Electric Power Transmission Tower Damaged by Foundation Settlements)

  • 이호범;박종권;김일수;장일영;송재호
    • 한국구조물진단유지관리공학회 논문집
    • /
    • 제17권2호
    • /
    • pp.83-93
    • /
    • 2013
  • 일반적으로 송전철탑 부재들의 보강은 적절한 그라우팅재를 활용한 인젝션과 구조 보강재 부착을 이용한 단면 확장에 따른 강성보강 방식을 주로 사용한다. 이와 같은 그라우팅 인젝션 및 단면보완은 주로 축력능력을 확장시키는 데에 의미를 갖는다. 그렇지만 보다 안정적 상태를 유지케 할 수 있는 보강방안이 적극 요구되는데 그 방법은 좌굴에 의해 손상을 받은 부재를 원상태의 길이로 환원시키고, 또한 내부적 보강효과를 동시에 갖는 새로운 부재로 교체하는 것이다. 본 연구에서는 기초침하로 구조적 손상을 받은 송전철탑의 손상회복을 위한 실증적 과정으로 우선 현장에서의 손상도 확인점검과 손상상태 및 회복상태에 대한 수치 해석적 결과를 도출하였고, 새롭게 고안한 잭킹시스템을 이용하여 보강된 부재를 교체하는 과업을 수행하였다. 이 결과는 송전철탑 유지관리의 차원상승 효과를 갖게 한다.

송전선로 철탑기초의 접지저항 해석 (Analysis of the Earth Resistance for the Tower Footing of T/L)

  • 이현구;하태현;배정효;김대경
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.344-346
    • /
    • 2001
  • The sharing of common corridors by electric power transmission lines and pipelines is becoming more common place. However, such corridor sharing can result in undesired coupling of electromagnetic energy from the power lines to the near facilities. During a fault on any of the transmission lines, energization of the earth by supporting structures near the fault can result in large voltages appearing locally between the earth and the steel wall of any nearby pipeline. This paper presents the outline of the tower footings for the transmission lines having been used in KEPCO and analyzes the earth resistance for operation method of the tower footing, that is contact presence for the anchor and reinforcing rob of the tower and foundation presence of the underground wiring.

  • PDF

천공수 산출기법에 의한 암반발파 철탑기초공법에 관한 연구 (A Study on the Bedrock Blasting Method for Transmission Tower Foundation using the Drilling Hole Calculation Technique)

  • 김점식;권세원;박용범;권신원;문성원;신운용;박용철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.669-670
    • /
    • 2007
  • 본 논문은 천공수 산출기법에 의해 천공수를 산출하여 크롤러드릴을 이용한 기계천공으로 1회에 필요한 깊이를 천공하고, 장약공과 무장약공을 구분하여 장약 및 전색을 하고, 지발뇌관에 의한 순차적 발파 시공방법에 관한 것으로 현장 적용시 심빼기 발파효과와 동시에 무장약공에 의한 2차 자유면을 얻는 효과로 진동, 소음, 비석을 줄이고 암반지대의 정밀한 철탑기초굴착이 가능한 기술에 관한 연구이다.

  • PDF

해상송전철탑 구조물의 주기점검을 통한 경년열화 변화특성 (Aging Deterioration for Electric Power Transmission Tower on Offshore Through Periodic Inspections)

  • 이호범;장일영
    • 한국구조물진단유지관리공학회 논문집
    • /
    • 제16권4호
    • /
    • pp.25-33
    • /
    • 2012
  • 해상송전철탑 구조물에 있어서 구조 및 재료 손상에 대해 주기적으로 안전점검을 실시하고, 그 결과를 이용한 수명관리(life management)의 시행은 적극 추천되는 일이다. 본 연구에서는 영흥도 시화호 내에 있는 총 6개의 해상송전철탑에 대해서 강재부재에 대해 3가지, 콘크리트 기초에 대해 5가지, 해수 중 강관파일 및 해수 자체에 대해 4가지 형태의 열화점검을 각각 수행하였다. 강재에 대한 점검 항목들은 외관조사, 부재두께, 도막상태 등에 대한 것이고, 콘크리트 기초에 있어서는 균열형상, 압축강도, 중성화깊이, 염화물 함유량 등에 대한 항목, 그리고 해중 강관파일에 있어서의 전위 및 양극조사에 따른 부식정도, 동영상 촬영 및 해수의 수질환경성 평가 등에 대한 항목이다. 이와 같은 정기적 열화점검은 연속 3년 동안 매년 10월경에 동일위치에 대해 평가하였다. 결과적으로 본 연구에서는 이러한 자료를 체계적으로 활용함으로써 해상송전철탑 안전성 유지관리에 유익하게 적용될 수 있는 새로운 열화지표를 개발하였다.