• 제목/요약/키워드: Electric power transmission

검색결과 1,072건 처리시간 0.028초

가공송전선로의 AAR 적용 시 Risk Tolerance 분석을 이용한 계절별 최대 허용전류 산정 및 적용에 관한 연구 (Study on the Estimation of Seasonal Ambient Current for the Application of Ambient Adjusted Line Rating(AAR) in Overhead Transmission Lines Using Risk Tolerance(RT) Method)

  • 이재걸;배영재;송지영;신정훈;김용학;김태균;윤용범
    • 전기학회논문지
    • /
    • 제66권1호
    • /
    • pp.7-15
    • /
    • 2017
  • Ambient Adjusted line Rating(AAR) method for overhead transmission lines considering Risk Tolerance(RT) was proposed in this paper. AAR is suitable for system operators to plan their operation strategy and maintenance schedule because this can be designed as a seasonal line rating. Several candidate transmission lines are chosen to apply the proposed method in the paper. As a result, it is shown that system reliability was significantly enhanced through maximizing transfer capability, solving the system constraints.

송전선로 드론 순시·정밀점검 운용 및 공공용 드론길 구축방안에 대한 연구 (Drone Operation Scheme for Patrolling & Inspecting Power Transmission Lines and on Public Drone Road Construction)

  • 우정욱;박준영;김석태;이재경;류서현
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제6권3호
    • /
    • pp.271-278
    • /
    • 2020
  • KEPCO Research Institute developed a GIS-based autopilot drone inspection system for electric power facilities and since its pilot application in 2017, it has been successfully used to detect defects in power transmission lines. This paper presents how to operate this system in the field of power line inspection. Power transmission lines are located in a wide variety of environments such as plains, mountains, river crossings, sea crossings, and industrial areas. Among these, some transmission lines are difficult for human workers to access because of their geographies and some should be checked more often due to their severe contamination. Considering these field conditions, we classified drone operation in two categories to increase its effectiveness and efficiency - patrol surveillance and detailed inspection tasks. This paper describes the detailed procedures of the two tasks above and their field application experiences. In addition, this paper newly proposes how to construct public drone roads by using the information of KEPCO's power transmission lines.

가공송전선로 점검 및 진단기술에 대한 해외기술동향 (New Technical Trend of Inspection and Test of Transmission Line)

  • 신태우;장석한;김무수;민병욱;최진성;윤근화;권연한;정두옥;방항권;최한열
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.315-317
    • /
    • 2008
  • Recently, a new construction of transmission line has been through quite hard situation due to demands for a new construction of transmission line have been saturated in south korea and also difficulties of purchasing the routes. In addition, the demands for electricity have been decreased in all of advanced countries of the world due to slowdown of the rate of economic growth. So they are trying to find a way to utilize a existing transmission line by extending the durable period. Therefore this is necessary to apply an applicable technology on domestic markets such as inspection, examination, maintenance of existing transmission lines by introducing advanced countries's example which shall be based on Japan's electric power companies.

  • PDF

신재생에너지 예측을 위한 송전선로의 계량 데이터 계산 방법 (Calculation Method of Dedicated Transmission Line's Meteological Data to Forecast Renewable Energy)

  • 백자현;김현진;최순호;박상호
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제8권2호
    • /
    • pp.55-59
    • /
    • 2022
  • This paper introduce Renewable Energy forecasting technology, which is a part of renewable management system. Then, calculation method of dedicated transmission line's meteorological data to forecast renewable energy is suggested. As the case of dedicated transmission line, there is only power output data combined the number of renewable plants' output that acquired from circuit breakers. So it is need to calculate meteorological data for dedicated transmission line that matched combined power output data. this paper suggests two calculation method. First method is select the plant has the largest capacity, and use it's meteorological data as line meteorological data. Second method is average with weight that given according to plants' capacity. In case study, suggested methods are applied to real data. Then use calculated data to Renewable forecasting and analyze the forecasting results.

A Study on the Reliability Evaluation of a Transmission System

  • Seungpil Moon;Jinboo Choo;Kim, Kyeongho;Donghoon Jeon;Park, Jaeseok
    • KIEE International Transactions on Power Engineering
    • /
    • 제3A권3호
    • /
    • pp.119-123
    • /
    • 2003
  • Successful operation of power systems under the deregulated electricity market depends on the management of the transmission system reliability. Quantitative evaluation of the transmission system reliability is an important issue. Particularly, the nodal reliability indices can be of value in the management and control of congestion and reliability of the transmission system under the deregulated electricity market. In this study, a method developed for the reliability evaluation of the transmission system is presented. The Monte Carlo methods are used because of their flexibility when complex operating conditions are being considered. The usefulness and effectiveness of the proposed method are illustrated by a case study with the KEPCO system.

±500kV HVDC 2회선 송전선로의 전기환경특성 예측 및 평가 (Prediction and Analysis of Electrical Environmental Characteristics under ±500kV HVDC Double Bipole Transmission Line)

  • 우정민;주문노;신구용;권구민;최우정;이재현
    • 전기학회논문지
    • /
    • 제67권4호
    • /
    • pp.554-560
    • /
    • 2018
  • Since Korea has a small land area, it is expected to construct the conductor return type with neutral wire in the case of ${\pm}500kV$ HVDC double bipole transmission line. Therefore, in order to apply ${\pm}500kV$ HVDC double bipole transmission line with neutral wire in Korea, it is necessary to develop technology for insulation and environmental designs. In this study, radio interference, audible noise, electric field and ion current density according to the polarity arrangement were compared and assessed in the ${\pm}500kV$ HVDC double bipole transmission line with the conductor return method. And the optimum configuration of HVDC double bipole transmission line was determined from the viewpoint of electrical environment.

345KV 송전선로의 송전용량 증대를 위한 STACIR 전선교체기술 (A Study on replacing transmission lines with STACIR for increasing power transmission capacity in the 345kv transmission system)

  • 김영한;방항권;조대성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 C
    • /
    • pp.1103-1105
    • /
    • 1998
  • It is becoming more and more difficult to construct new transmission lines because of many social problems. According to the load increase, Some of existing transmission lines will be heavy loaded over the limit. To solve this situation, one of method is peformed by replacing existing ACSR transmission lines with STACIR for increasing power transmission capacity in the 345kv transmission system. This paper presents several techniques for design and construction of transmission line replacement based on the actual experience in the 345kv Shinseongnam-Shinsiheung and Shinseongnam-Shinyeongseo transmission lines.

  • PDF

Primary Restorative Transmission Line Selection for Myanmar's Electric Power System

  • Kim, Yong-Hak;Song, In-Jun;Jang, Byung-Tae;An, Yong-Ho
    • Journal of Electrical Engineering and Technology
    • /
    • 제5권2호
    • /
    • pp.191-196
    • /
    • 2010
  • Power system restoration following a massive or complete blackout starts with energizing the primary restorative transmission system. During this primary restoration process, unexpected overvoltage may happen due to nonlinear interaction between the unloaded transformer and the transmission system. In the case of the Myanmar electric power system, there are so many wide outage experiences, including complete blackout cases, caused by 230kV line faults and so on. Consequently, Myanmar's system operators have been well trained to deal with wide blackouts. Howver, system blackout restoration has been conducted by relying on the experience of only a few specialists. So, more scientific analysis is required to meet the requirements necessary to ensure fast and reliable system restoration. This paper presents analytical results on the primary restorative transmission system of Myanmar, focusing on the problems during the early restoration process. Methodologies are presented that handle load pick-up, terminal voltage and the reactive capability limitation of black-start generators to compensate the Ferranti effect. Static and dynamic simulation with the PSSolution and EMTDC programs respectively for the six cases are performed in order to select the primary restorative transmission lines.

송전선로의 전자계 크기 측정 및 분석 (Measurement and Analysis of Electric and Magnetic Fields Near Overhead Transmission Lines)

  • 김상범;조성배;신구용;이동일;김정부
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 E
    • /
    • pp.1908-1910
    • /
    • 1997
  • The electric and magnetic fields (EMFs) near 345/154 kV overhead transmission lines were measured. The average values of maximum electric field and magnetic field for 44 transmission lines were 1.11 kV/m and 24.5 mG, respectively. These values were lower than any standards of advanced countries. The EMFs of distribution lines and substation, and electric appliances were also measured and compared with those of transmission lines.

  • PDF

An Inner-spherical Continuously Variable Transmission for Electric Bicycles

  • Park, Moon-Woo;Lee, Hyoung-Woo;Park, No-Gill
    • International Journal of Precision Engineering and Manufacturing
    • /
    • 제9권1호
    • /
    • pp.7-11
    • /
    • 2008
  • A new continuously variable transmission (CVT) for electric bicycles was developed using a traction drive mechanism with inner and outer spherical rotors. This electric bicycle CVT permits three propulsion modes: human-power only, motor-power only, or a combination of motor power and human power. In addition, the electric bicycle CVT has high power efficiency, large torque capacity, improved drivability, and good packageability. A prototype was manufactured based on a conceptual design, a performance analysis, and a detailed design. This prototype has a rated power of 250 W and input motor speed of 20 rad/s for an overall speed ratio in the range 0.3-1.2. A bench test was conducted to measure the power transmission performance of the prototype.