초고압 XLPE 전력케이블 절연두께 저감화 (Reduction of Insulation thickness for EHV XLPE power cable)

  • 이기수;최웅;최영훈;최봉남;김도영;윤덕환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2271-2273
    • /
    • 1999
  • The manufacturing technology of XLPE power cable ( e.g. gas curing, triple common extrusion, clean room, super-clean compound, etc.) had been developed in 1960's and the design parameter of insulation thickness for EHV XLPE power cable at present was determined in 1960's. But, the quality of XLPE power cable has been improved up to now. The re-evaluation of design parameter for insulation thickness reductions is required and so we performed weibull plotting test using model cable. This paper describes the evaluation details of the insulation characteristics according to weibull plotting test.

  • PDF

초고압 지중 케이블 시스템에 대한 편단접지시의 보호대책 (A Protection Method with single-bonding system in EHV Underground Transmission Line)

  • 김장원;강덕환;박근룡;김영범
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1620-1622
    • /
    • 1998
  • The failure occurs in the system of the underground transmission line, the time of restoration is very long, the damage from stopping power supply is very serious and the cost of restoration is very great. because of these problems, the system and equipment must be protected from every electrical failure by installing protection unit. This study is summarized and compared the effects of configuration method of cable protection device with respect to surges in EHV (Extra High Voltage) underground transmission system.

  • PDF

초고압 절연체 XLPE의 침전극에 따른 전계분포와 AC 절연파괴특성 (Electric Field Distribution and AC Dielectric Breakdown Properties according to Needle Electrode in EHV Insulators of XLPE)

  • 안병철;홍진웅
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2006년도 영호남 합동 학술대회 및 춘계학술대회 논문집 센서 박막 기술교육
    • /
    • pp.136-139
    • /
    • 2006
  • 최근 전력수요의 급증과 더불어 기기의 소형화와 경랑화를 위해 고분자절연재료의 사용이 증가하였으며, 근래 들어 환경성의 문제가 거론되면서 반영구적인 절연재료의 요구가 급증하였다. 그로 인하여 초고압 케이블의 절연재료로서 가교폴리에틸렌이 사용되어지고 있다. 이에 본 논문에서는 초고압전력용 케이블에서 절연재료로 사용되고 있는 가교폴리에틸렌 (XLPE) 내부전계분포 및 파괴전압과의 상관관계를 알아보기 위해 케이블에 칩 전극을 삽입하여 두께를 0.5, 1, l.5 [mm] 변화시켜 파괴전계를 검출하였으며, 또한 와이블 해석을 통한 파괴전압의 척도파라미터룰 검출하여, 시뮬레이션 인가전압으로 사용하였다. 시뮬레이션 경계요소법 (BEM)을 이용한 3 차원 전계해석 프로그램으로 조사하였다.

  • PDF

파퍼실린더 직경이 초고압 GCB의 열적 차단성능에 미치는 영향 (Influence of Diameter of Puffer Cylinder on Thermal Interruption Capability of EHV GCB)

  • 오연호;송기동;최영길;이병윤;박경엽;신영준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 A
    • /
    • pp.37-39
    • /
    • 1998
  • This paper presents the pressure-rise of the puffer cylinder in a model gas circuit breaker and the analyzed results of thermal interruption capability in SLF(short line fault) to the diameter of the puffer cylinder. This paper can be applied to the design of the EHV interrupter.

  • PDF

코로나 잡음 특성을 고려한 초고압 송전선의 다중도체배열방식 연구 (A Study on Multi-conductor Bundle for EHV Transmission Line Considering Corona Noise Characteristics)

  • 민석원;박종근
    • 대한전기학회논문지
    • /
    • 제39권5호
    • /
    • pp.508-515
    • /
    • 1990
  • This paper describes the corona characteristics of conductor bundle for EHV transmission line. To reduce the corona noise, the asymmetric conductor bundle to minimize the electric field of the conductor surface is proposed. The charge simulation method is used to formulate the electric field of conductor surface and the optimal arrangement of subconductor to minimize it is selected to apply the nonlinear successive quadratic programming. Through the analytical comparison and the corona cage test, it is proved that the asymmetric conductor bundle proposed in this paper can reduce the average maximum electric field of the phase conductors and the corona noise more than the conventional symmetric conductor bundle and asymmetric conductor bundle by GE.

  • PDF

송전용 애자의 인공오손시험 기법과 누설전류 특성 (Artificial contaminated test method and leakage current characteristics of EHV insulators)

  • 최인혁;정윤환;최장현;이동일
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 춘계학술대회 논문집
    • /
    • pp.386-391
    • /
    • 2004
  • To find out the reason of accident by being stained of insulators, this paper researched and analyzed the result of electrical characteristic test and field test of EHV insulator through artificial contaminated method. The best way to evaluate contaminated level of insulator surface is getting a contamination data by regional groups continually. But it is needed a lot of time and manpower. To overcome those difficulties, this research introduced ESDD(equivalent salt deposit density) measurement method which is adapted to the international codes of IEC and compared the relation between experimental test results which contaminated insulators by going through stain procedure and electrical measurement results.

  • PDF

송전용 애자의 장기실증시험 분석 (A Characteristic analysis of EHV insulators on long-term outdoor tests)

  • 최인혁;최장현;정윤환;이동일
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 춘계학술대회 논문집
    • /
    • pp.392-396
    • /
    • 2004
  • Experimental equipments for long-term outdoor tests of EHV insulators in outdoor were constructed. The testing insulators have been energized with 89 [kV] phase-to-ground AC voltage under identical condition at station, and the investigation was carried out for leakage current and various environments such as temperature, relative humidity and wind velocity. The test results of leakage current wave trends have forms on distorted waves including harmonics. The porcelain and glass insulators have low leakage current in case of daytime because moisture and humidity have relative low values. In comparison with these conditions, high leakage current was shown at dawn and rainy day due to high humidity. However, leakage current of polymer insulators was shown approximately $129[{\mu}m]$ without relation to the weather due to hydrophobicity on their surface.

  • PDF

초고압 송전용 자기애자의 인공오손법을 통한 누설전류 분석 (A Leakage Current Analysis of EHV Porcelain Insulators by Artificial Contamination Method)

  • 최인혁;최장현;정윤환;이동일
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 춘계학술대회 논문집 방전 플라즈마 유기절연재료 초전도 자성체연구회
    • /
    • pp.65-68
    • /
    • 2004
  • This paper researched leakage current characteristics of artificially contaminated EHV insulators through construction of long-term testing facility. Insulators were contaminated and classified into the ESDD contaminated levels under IEC standards method. As the test results of contaminated insulators was carried out several experiments, leakage current greatly increased during initial rainfall. After contaminated insulators were naturally washed by rain, leakage current was not increased.

  • PDF

EMTP/TACS를 이용한 초고압선로 HSGS-적응재폐로 방식의 구현 (Implementation of HSGS-Adaptive Reclosing Scheme for EHV Transmission System using EMTP/TACS)

  • 최보수;채명석;임한석;신중린
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 추계학술대회 논문집 학회본부
    • /
    • pp.106-108
    • /
    • 1996
  • This paper presents the Implementation and performance simulation of HSGS(High Speed Ground Switch)-Adaptive scheme for EHV transmission. EMTP/TACS(Transient Analysis of Control System) functions are combined and used for the implementation and simulation. The simulation results are compared with those for the conventional reclosing scheme and discussed.

  • PDF

자계-열계를 결합한 초고압 GIS용 모선의 온도상승 예측 (Prediction of Temperature Rise in EHV GIS Bus Bar by Coupled Magneto-Thermal F.E A)

  • 김중경;민경조;김한균;한성진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 B
    • /
    • pp.990-992
    • /
    • 2005
  • This paper presents a new magneto-thermal finite element analysis for predicting the temperature rise of the EHV GIS bus bar. The power losses of a bus bar calculated by the magnetic field analysis are used as the input data to predict the temperature rise for the thermal analysis. The heat-transfer coefficients on the boundaries are analytically calculated by applying the Nusselt number considering material constant and model geometry for the natural convection. The temperature distribution in a bus bar by coupled magneto-thermal finite element analysis shows good agreement with the experimental data.

  • PDF