A Characteristic analysis of EHV insulators on long-term outdoor tests

송전용 애자의 장기실증시험 분석

  • Published : 2004.05.07

Abstract

Experimental equipments for long-term outdoor tests of EHV insulators in outdoor were constructed. The testing insulators have been energized with 89 [kV] phase-to-ground AC voltage under identical condition at station, and the investigation was carried out for leakage current and various environments such as temperature, relative humidity and wind velocity. The test results of leakage current wave trends have forms on distorted waves including harmonics. The porcelain and glass insulators have low leakage current in case of daytime because moisture and humidity have relative low values. In comparison with these conditions, high leakage current was shown at dawn and rainy day due to high humidity. However, leakage current of polymer insulators was shown approximately $129[{\mu}m]$ without relation to the weather due to hydrophobicity on their surface.

Keywords