• Title/Summary/Keyword: Dielectric breakdown

Search Result 648, Processing Time 0.032 seconds

Dependence of Dielectric breakdown of Thin Poly (Vinylidene Fluoride) Film on Temperature (Poly (Vinylidene Fluoride) 박막의 절연파괴와 온도의존성)

  • Kim, Dong-Wook;Park, Dae-Hee
    • Proceedings of the KIEE Conference
    • /
    • 1989.07a
    • /
    • pp.380-382
    • /
    • 1989
  • Dielectric breakdown strength (Eb) of thin Poly(Vinylidene Fluoride ; PVDF) film is studied in the temperature range between 4.2 K and 400 K. The results of this study can be summerized as follows. 1) Temperature dependence of dielectric breakdown strength (Eb) can be devided into high and low temperature regions. The critical temperature (Tc) at which two regions are devided depends on applied voltage. 2) Dielectric breakdown strength (Eb) by pulse voltage is higher than that by DC voltage. Especially this difference is remarkable at low temperature.

  • PDF

An Analysis of Insulating Reliability in Polyethylene for High Frequency Molding Materials (고주파 성형 재료용 폴리에칠렌의 절연 신뢰도 분석)

  • Park, Geon-Ho;Kim, Ki-Joon;Wang, Jong-Bae;Shin, Chul-Ki;Kim, Jin-Sa;Lee, Joon-Ung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.10a
    • /
    • pp.64-67
    • /
    • 2000
  • In this study, the DC dielectric breakdown of polyethylene used for clothing material of cable was experimented and then its data were simulated by Weibull distribution probability. The dielectric breakdown characteristics in polyethylene were examined and various effects of the DC dielectric breakdown on polyethylene were also discussed.

  • PDF

The variation of water absorption rate and DC dielectric breakdown strength of Epoxy composites due to filler content (충진재 함량 변화에 따른 에폭시 복합재료의 흡수율과 직류 절연파괴강도의 변화)

  • Lee, D.J.;Kim, T.Y.;Shin, S.K.;Kim, M.H.;Kim, K.H.;Kim, J.H.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2349-2351
    • /
    • 1999
  • In this paper, the variable absorption rates and DC dielectric breakdown strength of epoxy composites were measured at boiling absorption condition in order to observe the influences of moisture in out door use. Also, in order to improve withstand voltage properties at moisture absorbtion condition. IPN (interpenetrating polymer network) method which had been already reported, was introduced and the influence was investigated. As a result, it was confirmed that the moisture absorption rate was increased and DC dielectric breakdown strength was degraded with boiling time and filler content increasing. On the other hand, it was confirmed that moisture absorption rate and DC dielectric breakdown strength degrading rate were lowered by the improvement of adhesion strength In IPN specimens.

  • PDF

The variations of AC dielectric breakdown strength of epoxy composites due to boiling absorption (비등흡수에 따른 에폭시 복합체의 교류 절연파괴강도의 변화)

  • 이덕진;김경민;김탁용;손인한;신성권;김경환;김재환
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.05a
    • /
    • pp.529-531
    • /
    • 1999
  • In this Paper, the variable dielectric breakdown strengths of epoxy composites were investigated at belling absorption condition in order to observe the influences of moisture in out door use. Also. in order to improve withstand voltage properties at moisture absorbtion condition, IPN(interpenetrating polymer network) method was Introduced and the Influence was investigated. As Adding filler(SiO$_2$) classified by o(phr), 50(phr) and 100[phr] to two kinds of matrix resin, six kinds of specimens were manufactured. As a result, it was confirmed that dielectric breakdown strength wer degraded with boiling time and filer content increasing. But, it was confirmed that dielectric breakdown strength degrading rate were lowered by the Improvement of adhesion strength in IPN specimens.

  • PDF

직류 전계하 LLDPE/EVA혼합필름의 절연파괴특성

  • 고시현;김형주;이종필;신현택;이충호;홍진웅
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.65-68
    • /
    • 2000
  • Polyethylene, has long history and is widely used, was researched due to good electrical properties by many authors. But PE under stress has the critical defects of space charge accumulation and tree growth, so various methods such as catalyst, additives and blend to improve these problems have been execute, of which we selected blending method. As in our previous papers we investigated electrical conduction, dielectric and AC dielectric breakdown characteristics, we did DC dielectric breakdown characteristics in this paper. We selected pure LLDPE, pure EVA and LLDPE films mixed with EVA as specimens, which were mixed with the weight percentages of 50, 60, 70 and 80[wt%] to be thin film. DC applying voltage speed was 500[V/sec]. The relation between dielectric breakdown characteristics and the variations of super structure due to mixing was investigated, and especially trap level at amorphous region, threshold energy increment of conductive electron at free volume were considered.

  • PDF

Dielectric Characteristics of HTS Cable (고온초전도 케이블의 유전 특성)

  • Kwag, Dong-Soon;Kim, Hae-Jong;Cho, Jeon-Wook;Seong, Ki-Chul;Kim, Sang-Hyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.08a
    • /
    • pp.64-68
    • /
    • 2002
  • According to the increasing power demand for the future construction of many underground cables will be required. However, construction of new ducts for power cables will be more difficult. Therefore, research work for realizing the high temperature superconducting(HTS) cable has advanced, where the development of electrical insulating system at cryogenic temperature is one of the major researches. For an electrical insulation design of HTS cable, it is important to understand not only breakdown but also partial discharge and dielectric loss($tan{\delta}$) in liquid nitrogen/paper composite insulation system. In this paper, we investigated breakdown characteristics in liquid nitrogen/paper composite insulation system for the application to HTS cable. And, we studied the breakdown characteristics of the multi-layer and butt gap of the insulation papers in liquid nitrogen. Also, we measured dielectric loss($tan{\delta}$) of the mini-model Cable made of TERLAM IPP.

  • PDF

Dielectric Breakdown Analysis of Bone-Like Materials with Conductive Channels (전도채널을 갖는 뼈와 유사한 재료의 절연파괴 해석)

  • Lee, Bo-Hyun;Lin, Song;Beom, Hyeon-Gyu
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.35 no.6
    • /
    • pp.583-589
    • /
    • 2011
  • The dielectric breakdown of bone-like materials subject to purely electric fields is investigated. In general, these materials consist of some layers with stronger dielectric strength and others with weaker dielectric strength in a parallel staggered pattern. The growth of the conductive channel is impeded during penetration of the weaker layer in the bone-like material because the electric-field concentration is relieved. The electric-field distribution around the head of the tubular channel is obtained from finite element analysis. The dielectric strength of the bone-like material is evaluated using the J integral, and some parameters affecting the dielectric strength are determined. It is shown that the J-integral values are reduced with an increase in the breakdown area in the weaker layer. It is also found that the ratio of the permittivity of the weaker layer to that of the stronger layer can strongly affect the dielectric breakdown.

Electrical Breakdown Properties of Insulating Oils for oil-immersed transformer (유입변압기용 절연유의 절연파괴특성)

  • 이인성;신현택;이종필;이수원;홍진웅
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.11a
    • /
    • pp.605-608
    • /
    • 2001
  • With the intention of investigating the breakdown properties of oil-immersed transformer oils in temperature range of 20∼100[$^{\circ}C$], we are made researches AC breakdown in the gap of 500∼2,500[$\mu\textrm{m}$]. The classification for the physical properties of oil for oil-immersed transformer by FTH and $^1$H-NMR experiments was confirmed to type of mineral oils. As the dependance of breakdown properties due to electrode gap length variation, breakdown voltage was found increasing according to the increase of gap, while dielectric strength was decreasing. As a result the characteristics for AC breakdown, It goes to prove that the breakdown voltage was increased to 90[$^{\circ}C$] but decreased over 90[$^{\circ}C$] in the temperature range. Also, breakdown voltage was found increasing in the increase of gap and the rising of temperature according to Weibull distribution.

  • PDF

Dielectric Breakdown Characteristics of PPLP and GFRP for HTS DC Cable System (고온초전도 DC 케이블 시스템용 PPLP 및 GFRP의 절연 특성)

  • Kim, S.H.;Choi, J.H.;Kim, W.J.;Jang, H.M.;Lee, S.K.
    • Progress in Superconductivity and Cryogenics
    • /
    • v.13 no.3
    • /
    • pp.5-9
    • /
    • 2011
  • DC high-temperature superconducting(HTS) cable system has attracted a great deal of interest from the view point of low loss, dense structure and large capacity. A HTS cable system is made of cable and termination. The insulating materials and insulation technology must be solved for the long life, reliability and compact of cable system. In this paper, we will report on the dielectric breakdown characteristics of insulating materials for HTS cable and termination. The AC, DC and lightning impulse breakdown strength of laminated polypropylene paper(PPLP) and glass fiber reinforced plastic(GFRP) have been measured under nitrogen pressures in the range of 0.l-0.4MPa. PPLP and GFRP are found to have a significantly higher DC breakdown strength. Also, DC surface flashover voltage of negative polarity is slightly higher than that of positive polarity in GFRP.

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

  • Kim, Hee-Dong
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.1
    • /
    • pp.280-285
    • /
    • 2014
  • In order to evaluate the insulation deterioration in the stator windings of five gas turbine generators(137 MVA, 13.8 kV) which has been operated for more than 13 years, diagnostic test and AC dielectric breakdown test were performed at phases A, B and C. These tests included measurements of AC current, dissipation factor, partial discharge (PD) magnitude and capacitance. ${\Delta}I$ and ${\Delta}tan{\delta}$ in all three phases (A, B and C) of No. 1 generator stator windings showed that they were in good condition but PD magnitude indicated marginally serviceable and bad level to the insulation condition. Overall analysis of the results suggested that the generator stator windings were indicated serious insulation deterioration and patterns of the PD in all three phases were analyzed to be internal, slot and spark discharges. After the diagnostic test, an AC overvoltage test was performed by gradually increasing the voltage applied to the generator stator windings until electrical insulation failure occurred, in order to determine the breakdown voltage. The breakdown voltage at phases A, B and C of No. 1 generator stator windings failed at 28.0 kV, 17.9 kV, and 21.3 kV, respectively. The breakdown voltage was lower than that expected for good-quality windings (28.6 kV) in a 13.8kV class generator. In the AC dielectric breakdown and diagnostic tests, there was a strong correlation between the breakdown voltage and the voltage at which charging current increases abruptly ($P_{i1}$, $P_{i2}$).