초록
With the intention of investigating the breakdown properties of oil-immersed transformer oils in temperature range of 20∼100[$^{\circ}C$], we are made researches AC breakdown in the gap of 500∼2,500[$\mu\textrm{m}$]. The classification for the physical properties of oil for oil-immersed transformer by FTH and $^1$H-NMR experiments was confirmed to type of mineral oils. As the dependance of breakdown properties due to electrode gap length variation, breakdown voltage was found increasing according to the increase of gap, while dielectric strength was decreasing. As a result the characteristics for AC breakdown, It goes to prove that the breakdown voltage was increased to 90[$^{\circ}C$] but decreased over 90[$^{\circ}C$] in the temperature range. Also, breakdown voltage was found increasing in the increase of gap and the rising of temperature according to Weibull distribution.