• Title/Summary/Keyword: Conductor Temperature

Search Result 492, Processing Time 0.027 seconds

장력과 풍속이 ACSR 가공송전선의 온도에 미치는 영향 (Effect of Tension and Wind Velocity on Temperature of ACSR Overhead Conductor)

  • 김상수;김병걸;이동일;민병욱
    • 한국전기전자재료학회논문지
    • /
    • 제19권5호
    • /
    • pp.480-485
    • /
    • 2006
  • A research was undertaken on the thermal properties and behavior of the conductors in a controlled chamber, which was designed to implement the outdoor air temperature, heat and wind conditions With ACSR $410mm^2$ overhead conductors, we measured the maximum temperature of the conductors and the temperature gradient from the core to the surface regions as a function of current, tension, wind velocity and outdoor air temperature. This test also provided a comparative analysis between the measured temperature values of conductors in the controlled chamber and the theoretical calculations of ANSI/IEEE at normal condition. There was not much influence of tension on the conductor temperature. However, the compactness of conductor wires increased with an increase in tension, which eventually increased the coefficient of effective thermal conductivity and, accordingly the conductor temperature was reduced more or less.

산불이 가공송전선의 온도에 미치는 영향 (The Effect of Forest Fire on Temperature of Overhead Conductor)

  • 김병걸;김상수;전완기;한세원
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 하계학술대회 논문집 Vol.8
    • /
    • pp.523-524
    • /
    • 2007
  • Forest fire can give a serious damage to overhead conductors. Therefore, the definite understanding about aging behavior of burned conductor is very important in maintaining the transmission line safely. It is sure that the temperature of conductor itself will be affected by the distance apart from flame. From this point of a view, we monitored the conductor's temperature with distance from flame. As a result, the conductor's temperature decreased as the flame goes away from the conductor gradually. The temperature of conductor was reached up to 55~65% level of its atmospheric temperature. The detailed results will be presented in the text.

  • PDF

STACIR/AW 410SQmm 가공송전선의 경년열화와 이도거동(III) (Sag Behavior of STACIR/AW 410SQmm Overhead Conductor in accordance with the Aging)

  • 김상수;김병걸;신구용;이동일;민병욱
    • 한국전기전자재료학회논문지
    • /
    • 제19권3호
    • /
    • pp.280-286
    • /
    • 2006
  • As a way to expand electric capacity in conductor with electric power demand, STACIR/AW (Super Thermal-resistant Aluminum-alloy Conductors Aluminum-clad Invar-Reinforced) conductor which has high electric current and heat resistance characteristics have been developed. STACIR/AW power line is mechanical composite wire composed of steel cores for dip control and aluminum conductors for sending electric current. Recently, to ensure stable operation and prediction of wire life span of STACIR/AW conductor, a heat property of STACIR/AW conductor have been investigated. In the present work, a change of essential property with long term-heat exposure of STACIR/AW conductor and its structure material, INVAR wire and Al conductor, have been investigated. INVAR/AW is approximately $3.2\;{\mu}m/m^{\circ}C$. thermal expansion coefficient of INVAR/AW wire increases with time of heat exposure. the thermal expansion coefficient of INVAR/AW is markedly influenced by heat and mechanical treatment. creep rate(0.242) of STACIR/AW $410\;mm^2$ conductor at room temperature is much higher than that(0.022) at $210\;^{\circ}C$ STACIR/AW $410\;mm^2$ conductor has minimum creep rate at operating temperature. To lower creep rate with increase temperature is more unique characteristics in STACIR/AW. It is expected that STACIR/AW turned its tension to INVAR/AW at the transition temperature. at room temperature, the tension apportionment of INVAR/AW in STACIR/AW is about $50\;\%$. but whole tension of STACIR/AW is placed on the INVAR/AW alone of core metal above transition temperature.

온도특성을 고려한 공항 저압간선의 경제적인 설계기법에 관한 연구 (A Study on the Economical Design of Airport Low-Voltage Feeder Which is considering the Temperature Character)

  • 최홍규;조계술;송영주
    • 조명전기설비학회논문지
    • /
    • 제17권3호
    • /
    • pp.119-126
    • /
    • 2003
  • 공항과 같이 간선이 길게 포설될 수 있는 장소의 저압간선 굵기는 해당 케이블의 허용전류와 전력계통의 전압강하를 고려하며 결정된다. 비록 도체의 허용전류 값이 부하의 허용전류 값에 비하여 여유가 있을지라도 계통의 허용전압강하를 고려할 경우 도체의 굵기는 비교적 크게 산정될 수 있다. 이러한 경우에, 도체의 허용전류 값은 부하의 최대전류 값보다 훨씬 크게 산정될 수 있으며 상대적으로 도체에서 발생되는 열은 감소하게 된다. 도체의 최대 허용온도에 보정된 도체의 교류저항 값이 저압간선의 굵기 산정을 위한 전압강하 계산공식에 적용되어 왔으며, 도체의 저항 값은 도체의 실제 온도상승 값이 적용된 저항 값에 비하여 크다 본 연구는 도체의 실제 온도상승 값이 보정된 도체의 저항 값을 적용하여 저압간선 굵기 선정 설계 실무에 적용할 수 있도록 일반적인 계산 방식에 비하여 오차가 적은 경제적인 설계 방식을 연구하였다.

가공송전선의 열적거동과 전류 및 외기온도의 영향 (Effect of Ambient Temperature and Current on Overhead Conductor)

  • 김상수;김병걸;현석규;이동일;민병욱
    • 한국전기전자재료학회논문지
    • /
    • 제19권5호
    • /
    • pp.486-491
    • /
    • 2006
  • A research was undertaken on the thermal properties and behavior of the conductors in a controlled chamber, which was designed to implement the outdoor air temperature, heat and wind conditions. With ACSR $410mm^2$ overhead conductors, we measured the maximum temperature of the conductors and the temperature gradient from the core to the surface regions as a function of current, tension, wind velocity and outdoor air temperature. This test also provided a comparative analysis between the measured temperature values of conductors in the controlled chamber and the theoretical calculations of ANSI/IEEE at normal condition.

통전 중 산불에 노출된 가공송전선의 온도 및 장력 변화 거동 (Temperature and Load Change behavior of Overhead Conductor under loading current due to Forest Fire)

  • 김병걸;장용호;김상수;한세원
    • 한국전기전자재료학회논문지
    • /
    • 제22권4호
    • /
    • pp.366-371
    • /
    • 2009
  • The authors have published several technical reports on the deterioration of conductor due to forest fire in series so far. This is because even we have been experiencing hundreds of forest fires every year, no systematic research on conductor which is very vulnerable to fire have been fulfilled. This paper describes the sag-tension behavior of conductor under loading current normally when only partial area of a long conductor is exposed to fire. Temperatures of Overhead Conductor were different with measurement position. When the partial area of conductor was heated up to $500^{\circ}C$, 20 % of permanent tension loss was observed. This results in the increase of sag of 1.5 m when span is 300 m. The other results will be presented in the text.

지중관로에서의 실제 허용전류 산출을 위한 도체온도 계산 알고리즘 개선에 관한 연구 (Improvement of the Conductor Temperature Calculation Algorithm for Calculating the Allowable Current in the Underground Channel)

  • 이향범;이병철;김정훈;남용현;강지원
    • 전기학회논문지
    • /
    • 제67권3호
    • /
    • pp.352-357
    • /
    • 2018
  • In this paper, the improvement of the conductor temperature calculation algorithm is studied. The allowable current of the underground transmission line is determined by the conductor temperature limit. Usually to calculate the allowable current limit, the conductor temperature is assumed in the most worst environment condition. It is possible to increase the transmission capacity if the actual burial environment is considered. Therefore, in this paper an algorithm is proposed to calculate the conductor temperature by distinguishing two area of a underground transmission line condition - the manhole where the temperature sensor can be installed and the underground transmission line in which the temperature sensor can not be installed easily. When calculating the conductor temperature by the underground line in the pipeline, the existing standard describes each environment as a single soil heat resistance and one ambient temperature. In order to compensate this situation, thermal resistance model that can take into consideration the ground surface temperature and under ground temperature is proposed. It is shown that the accuracy of the proposed model is increased compared with the existing standard calculation result.

ITER TF 초전도 도체 개발과 특성 (Development of ITER TF Cable-in-Conduit Conductors and Their Characteristics)

  • 김형찬;오동근;박수현;김기만
    • Progress in Superconductivity
    • /
    • 제10권2호
    • /
    • pp.108-115
    • /
    • 2009
  • As a participant taking part in the ITER TF conductor R&D program, we developed two toroidal field conductors with variations of conduit thickness resulting in the different void fraction of the conductors. The estimated void fractions of the conductors are 31% and 33%. In this paper we present the details of the TF conductor development and performance test results of them carried out by the measurement of current sharing temperature under cyclic loading. Regarding the conductor development, the internal-Sn-processed $Nb_3Sn$ strand characteristics, strand cabling, twist pitch and characteristics of the conduit materials are presented. For the understanding of the conductor design and performance, the conductor test results are presented and the effect of the conductor design parameters such as void fraction and twist pitch is discussed based on the results.

  • PDF

The Finite Element Analysis and the Optimum Geometric Design of Linear Motor

  • Lee Tae-Won
    • International Journal of Precision Engineering and Manufacturing
    • /
    • 제6권4호
    • /
    • pp.73-77
    • /
    • 2005
  • Linear motor has been considered to be the most suitable electric machine for linear control with high speed and high precision. Thrust of linear motor is one of the important factors to specify motor performance. Maximum thrust can be obtained by increasing the magnitude of current in conductor and is relative to the sizes of conductor and magnet. However, the magnitude of current and the size of conductor have an effect on temperature of linear motor. Therefore, it is practically important to find optimum design that can effectively maximize thrust of linear motor within limited range of temperature. Finite element analysis was applied to calculate thrust and numerical solutions were compared with experiments. The temperature of the conductor was calculated from the experimentally determined thermal resistance. The ADPL of ANSYS was used for the optimum design process, which is commercial finite element analysis software. Design variables and constraints were chosen based on manufacturing feasibility and existing products. As a result, it is shown that temperature of linear motor plays an important role in determining optimum design.

송전선로의 설비특성을 고려한 운영그룹 분류 및 최고허용온도 (An Operation Grouping and Its Maximum Allowable Conductor Temperature Considering Facility-conditions of Transmission Lines)

  • 손홍관;김병걸;박인표;안상현;장태인;최종기
    • 전기학회논문지
    • /
    • 제57권11호
    • /
    • pp.1922-1928
    • /
    • 2008
  • The thermal rating of a conductor are maximum continuous current capacity and short time emergency current capacity. The overload operation for a faults have an effect on a conductor lifetime. Its time duration and overload level are limited to facility conditions of transmission lines. The short time emergency current capacity in KOREA observe the KEPCO's DESIGN RULE 1210, but its rules are not included to concept of an allowable short time duration. This papers are described to the calculation concept of short time emergency current capacity considering a time duration and an overload level. And we suggested a operation grouping and its maximum conductor temperature considering facility conditions - conductor lifetime, stability of connection points, conductor height above ground and clearance, in the operating and new T/L.