Browse > Article
http://dx.doi.org/10.5207/JIEIE.2003.17.3.119

A Study on the Economical Design of Airport Low-Voltage Feeder Which is considering the Temperature Character  

최홍규 (홍익대학교 전기공학과)
조계술 (홍익대학교 전기공학과)
송영주 (홍익대학교 전기공학과)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.17, no.3, 2003 , pp. 119-126 More about this Journal
Abstract
The size of low voltage level conductor cables can be installed with a long length just like a aviation field, shall be determined for considering the ampacity of cable and the drop of voltage for the power system. Therefore, The size of the conductor cables may be larger one for considering the tolerable voltage drop comparatively, although the allowable ampacity of the conductor cables may have a margin in comparison with the rated full load current In this case, the conductor cables' allowable ampacity will be very larger than the rated full load current and the generated heat of the conductor will be relatively downed. The conductor cables' alternating current resistance corrected with the maximum allowable temperature of the conductors, has been applied on the general formula for the calculating the voltage drop in determinating the size of low voltage level conductor cables, and the resistance is larger than the resistance corrected with the actual temperature of the conductor cables. This paper was studied for the purpose of the conductor resistance corrected with the actual temperature rise of the conductor and address the economic design formula so that this studies shall minimize the errors which can be occurred in comparison with the general formula and which can be applied in design work for determining the size of low voltage level conductor cables.
Keywords
Aviation field; Voltage drop; Economic design formula; Low voltage feeder;
Citations & Related Records
연도 인용수 순위
  • Reference
1 IEC 949 - 1988 [Calculation of Thermally Permissible Short-Circuit Currents, taking into account Non-Adiabatic Heating Effects].
2 IEEE S-135-1 - 1962 (ICEA P-46-426) [Power Cable Ampacities Volume 1-Copper Conductors].
3 "전기 설비 기술계산 핸드북", 기다리, pp.115 - 170.
4 KS C 3611-1933 [600V 폴리 에틸렌 케이블].
5 조계술, "저압 간선의 설계기법에 관한 연구", 한국조명 전기설비 학회 2001년 학술대회, 2001.
6 NEMA WC-52-1986 (ICEA P-54-440) [Ampacities of Cables in open-top Cable Trays].
7 KS C 4202-1977 [일반용 저압 3상 유도 케이블].
8 新版 . 電力 ケ-ブル技術 ハンドブツク, 電氣書院, 1989.
9 NEC HANDBOOK - 1999 Article 310 [Conductors for General Wiring].
10 JCS 161E - 1995 [전력 케이블 허용전류 - 1].
11 최홍규외, "전력 사용시설물 설비 및 설계", 성안당, pp245 - 398, 1999.
12 IEEE 835-1994 [IEEE Standard Power Cable Ampacity Tables].