• Title/Summary/Keyword: Cable fault

Search Result 273, Processing Time 0.022 seconds

A Study on the Fault Location Using Multiscale Correlation in Underground Power Cable Systems (Multiscale Correlation을 이용한 지중송전계통 고장점 추정에 관한 연구)

  • Jung Chae Kyun;Lee Jong Beom;Kang Ji Won
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.557-559
    • /
    • 2004
  • The study of applying wavelet transform in power cable system fault location has been recognized by many researchers and investigated. For performance of fault location, the fault generated transients can be captured at one end of the cable or both ends. Between two approaches, single-ended approach is less expensive and more reliable as it doesn't need communication link between the ends of the cable. So, we performs the approach based on the one. In this paper, we are going to introduce a new algorithm to discriminate the transient and the reflected signal using wavelet coefficient. For wavelet transform, the stationary wavelet transform(SWT) is applied instead of conventional DWT because SWT has redundancy properties which is more useful in noisy signal processing.

  • PDF

Investigation of On-line Monitoring Method on 1500 V Direct Current Cable of Subway

  • Shen, Xiaojun;Jiang, Xiuchen;Yi, Zeng
    • Transactions on Electrical and Electronic Materials
    • /
    • v.7 no.5
    • /
    • pp.247-251
    • /
    • 2006
  • The traction DC feeder cable is one of the key devices for the safety operation of subway system, but for low voltage DC feeder cable (<3000 V) for subway, little attention has been paid by investigators on its online monitoring technology. With an introduction of cable laying and operation environment for the cable, this paper investigated the on-line monitoring technology of 1500 V DC feeder cable of subway. Firstly, in the text, the fault model of 1500 V DC cable was proposed based on the analysis of the fault type of the DC feeder cable, and then put forward synthetically on-line monitoring discharge signal and DC leakage current signal to assess DC feeder cable insulating state. The results of laboratory experiment prove that the proposed methods are feasible and can be implemented on-line monitor on DC feeder cable of subway.

Detection and Location of Cable Fault Using Improved SSTDR (개선된 SSTDR을 이용한 케이블 고장 검출과 위치 계산)

  • Jeon, Jeong-Chay;Kim, Jae-Jin;Choi, Myeong-Il
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.9
    • /
    • pp.1583-1589
    • /
    • 2016
  • This paper proposes an improved spread spectrum time domain reflectometry (ISSTDR) using time-frequency correlation and reference signal elimination method in order to have more accurate fault determination and location detection than conventional (SSTDR) despite increased signal attenuation due to the long distance to cable fault location. The proposed method has a two-step process: the first step is to detect a peak location of the reference signal using time-frequency correlation analysis, and the second step is to detect a peak location of the correlation coefficient of the reflected signal by removing the reference signal. The proposed method was validated through comparison with existing SSTDR methods in open-and short-circuit fault detection experiments of low voltage power cables. The experimental results showed that the proposed method can detect correlation coefficients at fault locations accurately despite reflected signal attenuation so that cable faults can be detected more accurately and clearly in comparison to existing methods.

Modeling and Transient Analysis of Cable in Combined Transmission Line with HIF and Analysis of Transient Characterstic in CCPU of Uderground Cable (혼합송전선로에서 고저항 지락사고시 케이블 과도현상 해석 및 전력케이블 시스 접지저항에 따른 CCPU 과도특성 모의)

  • Jung, Che-Kyun;Lee, Jong-Beom
    • Proceedings of the KIEE Conference
    • /
    • 2000.07a
    • /
    • pp.446-448
    • /
    • 2000
  • This paper discribes the modeling and transient analysis of cable in combined transmission line under high impedance fault(HIF). And also, transient characterstic analyzed on cable covering protection unit(CCPU) is presented. Modeling of the combined transmission line is established in PSCAD/EMTDC V3. The required data to analyze the transient phenomena is given from the actual system. The results show the HIF modeling in cable, fault current according to the value of fault resistance. And also when the value and method of grounding resistance is changed in CCPU, simulation results are presented.

  • PDF

Transient State Analysis of HTS Cable Using EMTP-RV (EMTP-RV를 이용한 초전도 케이블 과도상태 해석)

  • Ha, Chul-Jong;Yang, Byeong-Mo;Lee, Hyun-Chul;Lee, Geun-Joon;Baek, Young-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.7
    • /
    • pp.1194-1198
    • /
    • 2010
  • A high temperature superconducting power cable (HTS power cable) was applied large current capacity by no resistance in normal state. Fault state was risen out of over-current but, it was limited to resistance. this study was modeling equivalence, and unbalanced state analyzed operating charateristics of HTS power cable. The equivalence model was composed superconductor, shield, and former part. This model simulation was appeared conductor and shield current in normal state, but fault state was appeared former current as rise current by resistance. so it need to sufficiently influenced the quench characteristic when the former design.

Estimation Method of Cable Fault Location in Rocket Motors Using M-sequence Signals (M시퀀스 신호를 이용한 로켓 추진기관 케이블 결함 위치 추정 기법)

  • Son, Ji-Hong
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.21 no.5
    • /
    • pp.84-92
    • /
    • 2020
  • This paper describes the estimation method of cable fault location in rocket motors using M-sequence (Maximal Length Sequence). In order to estimate the location of a cable fault, three methods have been usually used: TDR (Time Domain Reflectometry), FDR (Frequency Domain Reflectometry), and TFDR (Time-Frequency Domain Reflectometry). However, these methods suffer the disadvantage of requiring users to be close to a test field, which is dangerous. The estimation method of cable fault location using M-sequence is proposed to solve this problem. The proposed method can make use of DAS (Data Acquisition System). The experiments were three cases: damaged, open, and short. The RG-58 coaxial cable was used in the experiments. As a result, the proposed method has better performance than that of conventional methods such as TDR and TFDR.

The Effects of Optical Cable Fault on Customer Complaints (광케이블 고장이 고객 불만에 미치는 영향 연구)

  • Jung, So-Ki;Cha, Kyoung Cheon
    • The Journal of Korean Institute of Communications and Information Sciences
    • /
    • v.40 no.2
    • /
    • pp.325-333
    • /
    • 2015
  • In this paper, we are aim to analysis the effects of optical cable fault on customer complaints. We considered several causes: the elapse time to allow repair from the optical cable fault, whether working day or not, seasonality and human error, external construction, optical cable cutting or core banding that is controllable causes and natural disasters, vehicle crash, fire that is uncontrollable causes. The results of analysis are as follows: First, customer complaints increase through indifferencial relationship when using the production function for the number of expected victims and elapsed time due to the optical cable fault. Second, not only the elapsed time but also controllable variables, human error, external construction, the core cut occurs, increased customer complaints due to optical cable faults.

A Study on Power Cable Fault Using PSCAD/EMTDC (PSCAD/EMTDC를 이용한 전력케이블 고장현상에 판한 연구)

  • Kim, Jeom-Sik;Lee, Jong-Beom
    • Proceedings of the KIEE Conference
    • /
    • 1996.07b
    • /
    • pp.868-870
    • /
    • 1996
  • This paper describes the faun phenomena by the simulation in power system including underground transmission power cable. Studying on fault phenomena is a very important part to decide the circuit breaker, protective relay and system configuration. Simulation was carried out in several different model system depended upon cable kinds using PSCAD/EMTDC, which is one of the transient program. The simulated results show the possibility to analyze transient phenomena for the cable system.

  • PDF

A Line to Ground Fault Location Algorithm for Underground Cable System (지중 케이블 계통의 1선지락 고장점 표정 알고리즘)

  • Lee Duck-Su;Yang Xia;Choi Myeon-Song
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.6
    • /
    • pp.267-273
    • /
    • 2005
  • This paper proposes a line-to-ground fault location algorithm for underground cable system. A feature of the proposed method is a new algorithm based on the analytic research which has not been tried until now. The proposed method firstly makes voltage and current equations using analysis of distributed parameter circuit for each of cores and sheathes respectively, and then establishes an equation of the fault distance according to the analysis of the fault conditions. Finally the solution of this equation is calculated by Newton-Raphson iteration method. The effectiveness of this proposed algorithm has been proven through PSCAD/EMTDC(Ver. 4.1) simulations.

Analysis of Diagnosis and Very Low Frequency Experiment to Detect of Fault on 22.9kV Class Cable (22.9kV급 케이블 결함 검출을 위한 초저주파 실험 및 현장 진단 분석)

  • Kim, Young-Seok;Kim, Taek-Hee;Kim, Chong-Min;Shong, Kil-Mok
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.10
    • /
    • pp.1780-1785
    • /
    • 2016
  • This paper presents few case studies of state diagnosis of XLPE cables using very low frequency techniques. The power cables of 22.9kV which have installation fault were assessed using VLF technique in addition to other techniques like insulation resistance and DC voltage withstand test. From the experimental results, The dielectric loss($tan{\delta}$) values of degradation of the cable(joint, knife, needle) at $U_0$ were 5.839, 5.526 and 6.251, respectively and all values were "further study advised". VLF PD measurement was also found defective portion. These method was effective in defect to fault in the degradation of the cable. However, the breakdown did not occur in the degradation of the cable because of properties of XLPE insulation. Few case studies of using VLF $tan{\delta}$ diagnosis for fault are measured and analyzed. The $tan{\delta}$ values at $U_0$ were "further study advised" or "action required".