• Title/Summary/Keyword: Autoignition Temperature (AIT)

Search Result 73, Processing Time 0.028 seconds

Measurement and Prediction of Autoignition Temperature of n-Butanol and sec-Butanol System (노말부탄올과 2차부탄올 계의 최소자연발화온도의 측정 및 예측)

  • Ha, Dong-Myeong
    • Fire Science and Engineering
    • /
    • v.26 no.5
    • /
    • pp.48-53
    • /
    • 2012
  • The autoignition temperature (AIT) is important index for the safe handling of flammable liquids which constitute the solvent mixtures. This study measured the AITs and ignition delay time for n-Butanol+sec-Butanol system by using ASTM E659 apparatus. The AITs of n-Butanol and sec-Butanol which constituted binary system were $340^{\circ}C$ and $447^{\circ}C$, respectively. The experimental AITs of n-Butanol+sec-Butanol system were a good agreement with the calculated AITs by the proposed equations with a few A.A.D. (average absolute deviation).

A Study of Minimum Autoignition Temperature Behavior (MAITB) of Benzene and n-Hexane Mixture (벤젠과 노말헥산 혼합물의 최소자연발화온도 거동에 관한 연구)

  • Ha, Dong-Myeong;Kim, Kyu-Hyun
    • Fire Science and Engineering
    • /
    • v.27 no.1
    • /
    • pp.8-13
    • /
    • 2013
  • The autoignition temperature (AIT) is important index for the safe handling of flammable liquids which constitute the solvent mixtures. This study measured the AITs and ignition delay time for Benzene and n-Hexane system by using ASTM E659 apparatus. The AITs of Benzene and n-Hexane which constituted binary system were $583^{\circ}C$ and $240^{\circ}C$, respectively. The experimental AITs of Benzene and n-Hexane system were a good agreement with the calculated AITs by the proposed equations with a few A.A.D. (average absolute deviation).

Investigation of Reliability of Flash Points and Autoignition Temperatures of Acids (산류(Acids)의 인화점과 최소자연발화온도의 신뢰성 고찰)

  • Ha, Dong-Myeong
    • Journal of the Korean Society of Safety
    • /
    • v.24 no.2
    • /
    • pp.42-47
    • /
    • 2009
  • The flash point and the AIT(auto-ignition temperature) are the most important combustible properties used to determine the potential for the fire and explosion hazards of flammable material. In order to know the accuracy of data in MSDS(Material Safety Data Sheet), the flash point of n-acids were measured by using Pensky-Martens closed cup tester(ASTM D93), Setaflash closed cup tester(ASTM D3278), Tag open cup tester(ASTM D1310) and Cleveland open cup tester(ASTM D92). Also, the AIT of n-acids were measured by using ASTM E659-78 tester. The measured the flash points and the AIT were compared with literatures and MSDS in KOSHA. The measured the flash points and the AIT were different from those in literatures and MSDS. Therefore, This paper shows that it is needed to investigate the MSDS compatibility of n-acids for the fire safety objectives.

The Investigation of Combustible Hazard by Measurement of Flash Point and Autoignition Temperature of n-Dodecane (노말도데칸의 인화점과 최소발화온도 측정에 의한 연소위험성 고찰)

  • Ha, Dong-Myeong
    • Fire Science and Engineering
    • /
    • v.25 no.2
    • /
    • pp.120-125
    • /
    • 2011
  • For the safe handling of n-dodecane, the explosion limits were investigated and the lower flash points and AITs (autoignition temperatures) by ignition delay time were experimented. By using the literatures data, the lower and upper explosion limits of n-dodecanee recommended 0.6 Vol.% and 4.7 Vol.%, respectively. The lower flash points of n-dodecane by using closed-cup tester were experimented $77^{\circ}$ and $80^{\circ}C$. The lower flash points of n-dodecane by using open cup tester were experimented $84^{\circ}C$ and $87^{\circ}C$. This study measured relationship between the AITs and the ignition delay times by using ASTM E659-78 apparatus for n-dodecane. The experimental AIT of n-dodecane was $222^{\circ}C$.

The Measurement and Prediction of Fire and Explosion Properties of n-Nonane (노말노난의 화재 및 폭발 특성치의 측정 및 예측)

  • Ha, Dong-Myeong
    • Journal of the Korean Society of Safety
    • /
    • v.31 no.5
    • /
    • pp.42-48
    • /
    • 2016
  • The usage of the correct combustion properties of the treated substance for the safety of the process is critical. For the safe handling of n-nonane being used in various ways in the chemical industry, the flash point and the autoignition temperature(AIT) of n-nonane was experimented. And, the explosion limit of n-nonane was calculated by using the flash point obtained in the experiment. The flash points of n-nonane by using the Setaflash and Pensky-Martens closed-cup testers measured $31^{\circ}C$ and $34^{\circ}C$, respectively. The flash points of n-nonane by using the Tag and Cleveland open cup testers are measured $37^{\circ}C$ and $42^{\circ}C$. The AIT of n-nonane by ASTM 659E tester was measured as $210^{\circ}C$. The lower explosion limit by the measured flash point $31^{\circ}C$ was calculated as 0.87 vol%. And the upper explosion limit by the measured upper flash point $53^{\circ}C$ was calculated as 2.78 vol%. It was possible to predict lower explosion limit by using the experimental flash point or flash point in the literature.

Investigation of Combustion Properties for Using Safe Hydrogen (안전한 수소 이용을 위한 연소특성치 고찰)

  • Ha, Dong-Myeong
    • Journal of the Korean Institute of Gas
    • /
    • v.12 no.2
    • /
    • pp.1-6
    • /
    • 2008
  • For the safety design and operation of many gas process, it is necessary to know certain explosion limit, flash point, autoignition temperature (AIT) and minimum oxygen concentration of handling substances. Also it is necessary to know explosion limit at high temperature and pressure. In this study for the safe handling of hydrogen, explosion limit and AIT of combustion properties for hydrogen were investigated. By using the literatures data, the lower and upper explosion limits of hydrogen recommended 4.0 vol% and 77.0 vol%. Also the AIT of hydrogen with ignition sources recommended $400^{\circ}C$ at the electrically heated crucible furnace (the whole surface heating) and recommended $640^{\circ}C$ at the local hot surface. The new equations for predicting the temperature and the pressure dependence of the explosion limits of hydrogen are proposed. The values calculated by the proposed equations were a good agreement with the literature data.

  • PDF

Measurements of Autoigniton Temperature(AIT) and Time Lag of BTX(Benzene, Toluene, Xylenes) (BTX(Benzene, Toluene, Xylenes)의 자연발화온도와 발화지연시간의 측정)

  • Ha, Dong-Myeong
    • Journal of the Korean Society of Safety
    • /
    • v.21 no.3 s.75
    • /
    • pp.45-52
    • /
    • 2006
  • The AITs(autoignition temperatures) describe the minimum temperature to which a substance must be heated, without the application of a flame or spark, which will cause that substance to ignite. The AITs are often used as a factor in determining the upper temperature limit for processing operations and conditions for handling, storage and transportation, and in determining potential fire hazard from accidental contact with hot surfaces. The measurement AITs are dependent upon many factors, namely initial temperature, pressure, volume, fuel/air stoichiometry, catalyst material, concentration of vapor, time lag. Therefore, the AITs reported by different ignition conditions are sometimes significantly different. This study measured the AITs of benzene, toluene and xylene isomers from time lag using AS1M E659-78 apparatus. The experimental ignition delay times were a good agreement with the calculated ignition delay times by the proposed equations wtih a few A.A.D.(average absolute deviation). Also The experimental AITs of benzene, toluene, o-xylene, m-xylene and p-xylene were $583^{\circ}C,\;547^{\circ}C,\;480^{\circ}C,\;587^{\circ}C,\;and\;557^{\circ}C$, respectively.

Measurement and Investigation of Combustible Characteristics for Risk Assessment of Toluene (톨루엔의 위험성 평가를 위한 연소특성치 측정 및 고찰)

  • Ha, Dong-Myeong;Jeong, Kee-Sin
    • Fire Science and Engineering
    • /
    • v.24 no.2
    • /
    • pp.76-81
    • /
    • 2010
  • For the safe handling of toluene, explosion limit at $25^{\circ}C$ and the temperature dependence of the explosion limits were investigated. And flash point and AIT (Autoignition Temperature) for toluene were experimented. By using the literature data, the lower and upper explosion limits of toluene recommended 1.13 vol% and 7.9 vol%, respectively. In this study, measured the lower and upper flash points of toluene by air-blowing tester were $5^{\circ}C$ and $40^{\circ}C$, respectively. And measured the upper flash points of toluene by Setaflash tester was $41.5^{\circ}C$. This study measured relationship between the AITs and the ignition delay times by using ASTM E659-78 apparatus for toluene, and the experimental AIT of toluene was $547^{\circ}C$. The new equations for predicting the temperature dependence of the explosion limits of toluene is proposed. The values calculated by the proposed equations were a good agreement with the literature data.

Investigation of Combustible Characteristics for Risk Assessment of Benzene (벤젠의 위험성 평가를 위한 연소 특성치 고찰)

  • Ha, Dong-Myeong
    • Journal of the Korean Society of Safety
    • /
    • v.24 no.5
    • /
    • pp.28-33
    • /
    • 2009
  • The thermochemical parameters for safe handling, storage, transport, operation and process design of flammable substances are explosion limit, flash point, autoignition temperatures(AITs), minimum oxygen concentration(MOC), heat of combustion etc.. Also it is necessary to know explosion limit at high temperature and pressure. For the safe handling of benzene, lower explosion limit(LEL) at $25^{\circ}C$, the temperature dependence of the explosion limits and flash point were investigated. And the AITs for benzene were experimented. By using the literatures data, the lower and upper explosion limits of benzene recommended 1.3 vol% and 8.0 vol%, respectively. This study measured relationship between the AITs and the ignition delay times by using ASTM E659-78 apparatus for benzene, and the experimental AIT of benzene was $583^{\circ}C$. The new equations for predicting the temperature dependence of the explosion limits of benzene is proposed. The values calculated by the proposed equations were a good agreement with the literature data.

Measurement of Autoignition Temperature of n-Propanol and Formic acid System (n-Propanol과 Formic acid계의 최소자연발화온도의 측정)

  • Cho, Young-Se;Ha, Dong-Myeong
    • Fire Science and Engineering
    • /
    • v.27 no.5
    • /
    • pp.64-69
    • /
    • 2013
  • The autoignition temperatures (AITs) of solvent mixture was important index for the safe handling of flammable liquids which constitute the solvent mixtures. This study measured the AITs and ignition delay time for n-propanol and formic acid system by using ASTM E659 apparatus. The AITs of n-Propanol and Formic acid which constituted binary system were $435^{\circ}C$ and $498^{\circ}C$, respectively. The experimental AITs of n-propanol and formic acid system were a good agreement with the calculated AITs by the proposed equations with a few A.A.D. (average absolute deviation). And n- Propanol and formic acid system was shown the minimum autoignition temperature behavior (MAITB).