• 제목/요약/키워드: Arc Interruption

검색결과 69건 처리시간 0.024초

가스차단기의 아크현상 해석프로그램에 대한 연구 (A Study on the Program Analyzing the Arc Phenomena in Gas Circuit Breaker)

  • 최영길;최상태;이광식
    • 조명전기설비학회논문지
    • /
    • 제25권12호
    • /
    • pp.74-81
    • /
    • 2011
  • A computational approach was developed to understand about the arc quenching process in a gas circuit breaker(GCB). This approach is a program to analyze the gas flow in the breaker. The arc is processed at the same time. The program was used the so-called FLIC method for gas analysis techniques. It was referenced that the arc is interpreted the 'a Simplified Enthalpy Flow Arc Model'. In order to validate about the results of the program, a Auto Puffer GCB was chosen as the test subject. Because, the breaker is the one that arc current is interrupted by using the arc heating. And also, the current interrupting capability can be obtained only owing to the positive utilization(auto puffer) of the clogging phenomenon, without other puffer actions. In this paper, it has been realized that the entire arc quenching process is computerized, which is based on the self-flow current interruption by the auto puffer action. This program, which was verified through experiments, produced good results.

수용가 저압 전기설비의 원격 감시시스템 및 아크차단 장치 활성화 방안에 관한 연구 (A study Improvement Direction for Arc Interruption Equipment and On-line Monitoring System of Consumer Low Voltage Facilities)

  • 김기현;박치현;임용배;최명일;배석명
    • 조명전기설비학회논문지
    • /
    • 제22권1호
    • /
    • pp.79-86
    • /
    • 2008
  • 국내 및 국외에서도 마찬가지로 전기설비 안전점검에 대한 부분이 발전된 정보통신 기술(IT: Information Technology)에 접목 시켜 실시간으로 서비스를 제공하는 추세에 있다. 전기설비와 관련된 전기안전 부가서비스의 활성화를 위한 방향과 새로운 고부가 비즈니스 사업 창출을 위해서 어떤 부분에서 개선 및 추가되어야 할 부분인지에 대하여 본 논문에서 조사하였다. 따라서 전력 부가 서비스의 활성화 방향에 대하여 실시간 원격 감시 시스템의 활성화 부분과 아크 차단기 도입의 필요성 및 관련 법 부분에 대해 조사 분석하였다.

자계내에서 직류 차단시 아크소호 특성에 관한 연구 (A Study on the Characteristics of Arc Quenching of DC Interruption in the Magnetic Field)

  • 이동원;송현직;박원주;이광식;이동인
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제10권5호
    • /
    • pp.66-74
    • /
    • 1996
  • 본 연구는 자계내에서 직류 차단설비의 아크소호 현상을 규명하기 위하여 침대 평판 전극에 부극성 직류 고전압 인가시 아크전압 및 전류 그리고 이들 파형특성을 자계세기의 변화에 따라 연구 검토하였다. 본 연구에서 얻은 중요한 결론은 다음과 같다. 자계가 인가되지 않았을 때는 아크동특성이 나타나지 않고 아크전압의 감소와 아트전류의 증가가 순간적으로 이루어진 후, 일정하게 유지되었을 뿐만아니라 전류 파형으로부터 아크방전이 연속적으로 발생됨을 알수 있었다. 자계가 인가되면 아크동특성이 나타난후, 서서히 아크전압이 감소되고 증가되고 아크전류는 감소되었다. 그리고 전류파형으로부터 아크방전은 단속적으로 됨에 따라 전류영점이 나타남을 알 수 있었고, 전류영점이 나타나는 주기와 아크방전의 단속 주기가 일치하였으며 자계가 증가될수록 주기도 증가되었다.

  • PDF

아크 플라즈마에 의한 PTFE 노즐 용삭현상 (ABLATION OF PTFE NOZZLE DRIVEN BY ARC PLASMA)

  • 이종철;김윤제
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2005년도 추계 학술대회논문집
    • /
    • pp.311-317
    • /
    • 2005
  • It has been the most progressive interruption technique to use the ablation gas from the surface of PTFE nozzle driven by arc plasma during switching process in $SF_6$ gas circuit breakers. This advanced interruption technique can reduce the required mechanical energy to compress and blow the gas for extinguishing the arc plasma between the electrodes due to using the ablation effect instead. In order to consider the phenomena during calculation of switching process, it is required to confirm the principles of ablation from PTFE nozzle as well as of arc plasma during switching process. In this study, we have calculated the switching process considered the ablation of PTFE nozzle driven by arc plasma using multidisciplinary simulation technique and compared the results with the data without the ablation effect. More $50\%$ difference of pressure rise inside expansion chamber has been found from the results and it should be indispensable for this type of computational work to consider and include the ablation effect of PTFE nozzle. Further study on turbulence and radiation will be followed.

  • PDF

진공차단기에서 아크-후 전류의 측정 (Measurement of the Post-Arc Current in a Vacuum Circuit Breaker)

  • 송기동;정진교;오연호;이우영
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제55권10호
    • /
    • pp.521-527
    • /
    • 2006
  • After various measuring methods and system were investigated, Rogowski colis for the measurement of parameters in current zero region were designed and manufactured. Using the Rogowski coils and a 38kV 40kA VCB (vacuum circuit breaker), at last the post-arc current has been successfully measured firstly. It was found that the Rogowski coils used in this study have good characteristics and propriety to measure the parameters of current zero. We realized that the data processing for evaluating the post-arc current from the experimental results needs much more careful attention than that for building the measuring technique and system. The magnitude of post-arc current and the falling time of it to zero are proportioned to the rate of current di/dt. The magnitude of post-arc currents were around $1{\sim}3A$ to the interruption current of $20{\sim}30kA$ in the model VCB.

진공차단기 3상 동시 차단시의 서지 특성 분석 (Surge Characteristics Analysis of Three-phase Virtual Chopping at Vacuum Circuit Breaker)

  • 김종겸
    • 전기학회논문지
    • /
    • 제67권9호
    • /
    • pp.1159-1164
    • /
    • 2018
  • Vacuum circuit breakers(VCB) are widely used for current interruption of high-voltage inductive loads such as induction motors. This VCB can be chopped off before the current zero due to its high arc-extinguishing capability. One of the outstanding features of VCB is that it can cut off high frequency re-ignition current more than other circuit breakers. If the transient recovery voltage generated in the arc extinguishing is higher than the dielectric strength of the circuit breaker, a re-ignition phenomenon occurs. The surge voltage of the re-ignition is very high in magnitude and the steepness of the waveform is so severe that it can act as a high electrical stress on the winding. If the high frequency current of one phase affects the other two phases when the re-ignition occurs, it may cause a high surge voltage due to the virtual current chopping. If the magnitude of the voltage allowed in the motor winding is high or the waveform level is too severe, it may lead to insulation breakdown. Therefore, it is necessary to reduce the voltage to within a certain range. In this study, we briefly explain the various phenomena at the time of interruption, analyzed the magnitude of the dielectric strength and the transient recovery voltage at the simultaneous three-phase interruption that can give the greatest influence to the inductive load, proposed a method to reduce the impact.

센서없는 아크고장전류 제어 알고리즘 설계 (Design of Control a Algorithm for Arc Fault Current without Current Sensor)

  • 반기종;김낙교
    • 대한전기학회논문지:시스템및제어부문D
    • /
    • 제55권6호
    • /
    • pp.255-260
    • /
    • 2006
  • Arc Fault Current is an which occurrs in two opposite electrode. In this paper, arc current control algorithm is designed for the interruption of arc fault current which is occurred in the low voltage network. This arc is one of the main causes of electric fire. General arc current sensor has troubles for detecting arc currents, thus we would like to propose the arc current detection method without current sensor. In this parer, arc discharge currents within power lines are being detected through the arc current control algorithm.

50kW 태양광 설비의 아크 검출 알고리즘 개발 (Development of Arc Detection Algorithm for 50 kW Photovoltaic System)

  • 김상규;이창성;지평식
    • 전기학회논문지P
    • /
    • 제67권1호
    • /
    • pp.27-32
    • /
    • 2018
  • In this paper, we developed an algorithm to detect arc of PV power plant through frequency analysis. For arc detection based on frequency analysis, the filter should be designed to emphasize the difference between the arc state and the normal state. Therefore, in this paper, we analyzed the arc detection performance according to various filter structures. The arc detection algorithm developed in this paper extracts the filtering signal on current by using various filters and then calculates the frequency components and total energy using the FFT. In the final step, the arc is detected using the calculated energy magnitude. In order to verify the performance of the proposed arc detection algorithm, experiments were conducted on 51 kW solar inverters connected to power line. Through various experiments, it was confirmed that the proposed method effectively detects the arc.

저압 배선용차단기 절연회복특성 파악을 위한 절연회복전압 측정기법 연구 (Study on Measurement Method of Dielectric Recovery Voltage to analysis Dielectric Recovery Characteristic of Molded Case Circuit Breaker)

  • 송태헌;조영만;고광철
    • 조명전기설비학회논문지
    • /
    • 제29권8호
    • /
    • pp.49-54
    • /
    • 2015
  • Molded Circucit Breaker(MCCB) is a most widely used device to protect loads from the over-current in low power level distribution system. When the MCCB interrupts the over-current, the arc discharge occurred between fixed contact and moving contact to create hot gas. By the Lorentz force due to arc current, the occurred arc is bent to the grids. The grids extend and cool and divide it for arc extinguish. In the majority cases, the MCCB protects loads by interrupting the over-current successfully but in some cases the re-ignition is occurred by hot-gas created during process of interruption. The re-ignition arises when the recovery voltage(RV) is more higher than the recovery strength between contacts and it leads to interruption fault. Therefore to find out the dielectric recovery characteristics of protecting device has a great importance for preventing interruption fault. In this paper, we studies measurement method of the dielectric recovery characteristics considering inherent attribute of the MCCB. To measure the dielectric recovery characteristic of MCCB, we makes an experiment circuit for applying the over-current and the randomly recovery voltage. The measurement methode to find out the dielectric recovery voltage of the MCCB was established and the result was based on experiment results.

센서없는 AFCI 알고리즘 설계 (AFCI algorithm design without sensor)

  • 반기종;최성대;윤광호;김상훈;남문현;김낙교
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 심포지엄 논문집 정보 및 제어부문
    • /
    • pp.231-233
    • /
    • 2006
  • Arc Fault Current is an electric discharge which is occurred in two opposite electrode. In this paper, arc current control algorithm is designed for the interruption of arc fault current which is occurred in the low voltage network. This arc is one of the main causes of electric fire. General arc current sensor has troubles for detecting arc currents, thus we would like to propose the arc current detection method without current sensor. In this paper, arc discharge currents within power lines are being detected through the arc current control algorithm.

  • PDF