유효전력변동방식을 이용한 새로운 단독운전 검출기법 연구 (A Novel Active Anti-islanding Method using Effective Power Variation)

  • 유병규;정영석;미키히코 마츠이;유권종
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2006년도 전력전자학술대회 논문집
    • /
    • pp.213-215
    • /
    • 2006
  • Islanding phenomenon is undesirable because it lead to a safety hazard to utility service personnel and may cause damage to power generation and power supply facilities as a result of unsynchronized reclosure. In order to prevent the phenomenon, various anti-islanding methods have been studied. This paper proposes the variation method of inverter output current magnitude to prevent the islanding phenomenon as a novel method, which causes the large frequency variation of inverter output voltage after islanding. Unlike most active anti-islanding method deteriorating power quality, this novel method will have high performance of islanding detection and good power quality. For the verification of the proposed method, the simulated result and analyses are presented.

  • PDF

역상분 전류 주입을 적용한 3상 인버터 기반 BESS의 단독 운전 검출 방법 (Anti-islanding Detection Method for BESS Based on 3 Phase Inverter Using Negative-Sequence Current Injection)

  • 신은석;김현준;한병문
    • 전기학회논문지
    • /
    • 제64권9호
    • /
    • pp.1315-1322
    • /
    • 2015
  • This paper proposes an active islanding detection method for the BESS (Battery Energy Storage System) with 3-phase inverter which is connected to the AC grid. The proposed method adopts the DDSRF (Decoupled Double Synchronous Reference Frame) PLL (Phase Locked-Loop) so that the independent control of positive-sequence and negative-sequence current is successfully carried out using the detected phase angle information. The islanding state can be detected by sensing the variation of negative-sequence voltage at the PCC (Point of Common Connection) due to the injection of 2-3% negative-sequence current from the BESS. The proposed method provides a secure and rapid detection under the variation of negative-sequence voltage due to the sag and swell. The feasibility of proposed method was verified by computer simulations with PSCAD/EMTDC and experimental analyses with 5kW hardware prototype for the benchmark circuit of islanding detection suggested by IEEE 1547 and UL1741. The proposed method would be applicable for the secure detection of islanding state in the grid-tied Microgrid.

계통연계형 태양광발전시스템의 AFS 기법을 이용한 단독운전 방지 (Anti-islanding using Active Frequency Shake Method for Grid-connected PV Generation System)

  • 옥승규;강문성;양오
    • 한국정보통신학회논문지
    • /
    • 제17권1호
    • /
    • pp.127-136
    • /
    • 2013
  • 계통연계형 인버터의 중요 성능 중 단독운전 검출기능 및 방지기능은 계통을 유지보수하기 위한 작업자의 안전을 위하여 고려되어야 할 필수 사항이다. 본 논문에서는 태양광을 이용한 계통연계형 태양광발전시스템에서의 AFS(Active Frequency Shake) 단독운전 검출기법을 제안하고자 한다. 먼저 AFS 단독운전 검출 알고리즘을 제안하기 위하여 기존의 능동 주파수 변이기법 알고리즘에 대해 기술한다. 그리고 단독운전 불검출영역을 줄이고, THD(Total Harmonic Distortion)를 개선하며, 기존 알고리즘 보다 검출 속도 또한 향상 시킬 수 있는 알고리즘을 제시하였다. 아울러 제안된 단독운전방지 기법을 3kW 계통연계형 태양광 인버터에 적용하고 시뮬레이션 및 실험을 통하여 제안하는 알고리즘의 타당성을 검증하였다.

역상분 전압 주입을 이용한 태양광 인버터의 단독 운전 검출 (Anti-islanding Detection of Photovoltaic Inverter Based on Negative Sequence Voltage Injection to Grid)

  • 김병헌;박용순;설승기;김우철;이현영
    • 전력전자학회논문지
    • /
    • 제17권6호
    • /
    • pp.546-552
    • /
    • 2012
  • This paper presents an active anti-islanding detection method using negative sequence voltage injection to the grid through a three-phase photovoltaic inverters. Because islanding operation mode can cause a variety of problems, the islanding detection of grid-connected photovoltaic inverter is the mandatory feature. The islanding mode is detected by measuring the magnitude of negative sequence impedance calculated by the negative sequence voltage and current at the point of common coupling. Simulation and experimental test are performed to verify the effectiveness of the proposed method which can detect the islanding mode in the specified time. The test has been done in accordance with the condition on IEEE Std 929-2000.

Active Frequency Drift Method for Islanding Detection Applied to Micro-inverter with Uncontrollable Reactive Power

  • Kwak, Raeho;Lee, June-Hee;Lee, Kyo-Beum
    • Journal of Power Electronics
    • /
    • 제16권5호
    • /
    • pp.1918-1927
    • /
    • 2016
  • This paper proposes active frequency drift (AFD) as an anti-islanding method applied to micro-inverters with uncontrollable reactive power. When using ordinary inverter topologies, such as full bridge inverters in photovoltaic systems, the islanding phenomenon can be detected with reactive power-based methods, such as reactive power variation. However, when the inverter topology cannot control the reactive power, conventional anti-islanding methods with reactive power cannot be utilized. In this work, the topology used in this paper cannot control the reactive power. Thus, an anti-islanding method that can be used in topologies that cannot control the reactive power is proposed. The conventional anti-islanding method of the topology that cannot control reactive power is introduced and analyzed. Unlike the conventional AFD method, the proposed method extends a zero current interval every predetermined cycle. The proposed method offers certain advantages over conventional AFD methods, such as total harmonic distortion. The proposed method is validated through simulation and experiment.

시간영역에서의 유효/무효전력을 이용한 마이크로그리드의 단독운전의 판단 알고리즘 (Islanding detection algorithm for a micro-grid based on the active and reactive power in the time domain)

  • 이영귀;이혜원;김연희;정태영;강용철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.145-146
    • /
    • 2011
  • A micro-grid (MG) is usually interconnected to the main grid through the dedicated line. Immediately after the removal of the grid supply, the MG should be disconnected and remain disconnected until the main grid is re-energized. It should detect islanding condition as soon as it happens to adjust the setting of the protection relays in the MG. This paper proposes an islanding detection algorithm for the MG based on the active and reactive power delivered to the dedicated line in the time domain. The performance of the proposed algorithm is verified under islanding conditions and fault conditions using the PSCAD/EMTDC simulator. The results indicate that the proposed algorithm can discriminate the islanding conditions from the various fault conditions.

  • PDF

Islanding Detection for PV System Connected to a Utility Grid

  • Han, Seok-Woo;Mok, Hyung-Soo;Choe, Gyu-Ha
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 1998년도 Proceedings ICPE 98 1998 International Conference on Power Electronics
    • /
    • pp.719-723
    • /
    • 1998
  • Prevention of the islanding phenomena is one of the most important issues because it can damage electrical equipment connected to the utility system and endanger human life. It is very difficult to detect an islanding condition of a power distribution line with conventional voltage of frequency relays, while the output power and the load power of utility interactive PV inverter units are in nearly balanced state in both active power and reactive power. This paper describes the protective equipment that prevents the PV system connected to the utility grid from starting islanding. Both predictive ocntrol method and harmonic injection method are used for a current control and islanding detection for operating safety.

  • PDF

Islanding Detection Method for Inverter-based Distributed Generation Systems using a Signal Cross-correlation Scheme

  • Bae, Byung-Yeol;Jeong, Jong-Kyou;Lee, Ji-Heon;Han, Byung-Moon
    • Journal of Power Electronics
    • /
    • 제10권6호
    • /
    • pp.762-768
    • /
    • 2010
  • This paper describes the development of a new islanding detection method for inverter-based distributed generation systems, which uses a signal cross-correlation scheme between the injected reactive current and the power frequency deviation. The proposed method injects 1% of the reactive current to the rated current which brings about a negligible degradation of the power quality. It discriminates the islanding state, when the calculated cross-correlation index is larger than 0.5. The operational feasibility was verified through computer simulations with PSCAD/EMTDC software and experimental research with a hardware prototype. The proposed method can detect the islanding state without degrading the power quality at the point of common connection. Further study is required to overcome the cancellation of the injected reactive current from multiple distributed generation units interconnected with the utility grid.

계통연계형 태양광발전시스템을 위한 단독운전 검출에 관한 연구 (A Study on the Islanding Detection for Grid Connected Photovoltaic System)

  • 이기제;김민;이진섭;유권종
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2002년도 전력전자학술대회 논문집
    • /
    • pp.555-558
    • /
    • 2002
  • The general ways of the anti-islanding can be classified into the active method and passive method. The passive method which use only the voltage information when power failure occurs has much possibility of the wrong detection. And the active method detects the change of the voltage frequency as instantaneously changing the frequency of the inverter output current. Therefore, in this paper, the method to inject arbitrary order harmonics into controlled current is proposed. In this method islanding can be detected by measuring the amount of load voltage of injected harmonics order. And as a current control method predictive control method is used, which make actual current accurately to track reference current by Instantaneously computing converter output voltage and has fast response in transient state. This parer proposed method was verified by simulation.

  • PDF

자동 위상 이동을 이용한 계통 연계형 태양광 발전 시스템의 고립운전 검출기법 (Islanding Detection Method for Grid-connected PV System using Automatic Phase-shift)

  • 윤중혁;최종우;소정훈;유권종;김흥근
    • 전력전자학회논문지
    • /
    • 제12권2호
    • /
    • pp.107-114
    • /
    • 2007
  • 계통 연계형 태양광 발전 시스템이 정전 혹은 사고 등으로 계통으로부터 분리되었을 때 태양광 발전 시스템이 배전선 부하를 떠맡아 운전을 계속하는 현상을 고립운전이라 하는데 이런 상태가 지속되면 선로 유지보수자의 안전사고를 야기할 수 있으며 전기설비에 나쁜 영향을 줄 수도 있다. 수동 검출법은 연계점(PCC:Point of Common Coupling)의 전압이나 주파수를 측정하여 한계치를 벗어나면 고립운전으로 판단하는데 RLC 부하의 유효전력과 무효전력이 각각 PV 시스템의 유효전력, 무효전력과 서로 비슷하면 검출할 수 없다. 이 경우 고립운전을 검출하기 위한 다양한 능동 검출법이 제안되었으며 가장 효과적인 방법은 미국 샌디아 연구실(Sandia National Lab)에서 제안한 SFS법(Sandia Frequency Shift method)이다. 본 논문에서는 자동 위상 이동을 이용한 새로운 능동 검출기법을 제안하고 Matlab 시뮬레이션과 실험을 통하여 타당성을 검증하였다.