Browse > Article
http://dx.doi.org/10.6109/jkiice.2013.17.1.127

Anti-islanding using Active Frequency Shake Method for Grid-connected PV Generation System  

Ock, Seungkyu (청주대학교 전자공학과)
Kang, Moonsung (청주대학교 전자공학과)
Yang, Oh (청주대학교 반도체설계공학과)
Abstract
The islanding detection and prevention function in the important performance of the grid-connected inverter is the essential details which should be considered for worker's safety to maintain the system. This paper tries to suggest the active frequency shake islanding detection technique in the grid-connected PV generation system using sunlight. The existing active frequency drift method algorithm is described to suggest active frequency shake method algorithm. And, the algorithm which can reduce the non-detection zone, improve THD, and improve the detection speed in comparison with the existing algorithm is suggested. And we applied the proposed algorithm to the 3kW grid-connected photovoltaic inverter generation and verified the feasibility of the technique through the simulation and experiments.
Keywords
Anti-islanding; AFS(Active Frequency Shake); AFD(Active Frequency Drift); THD(Total Harmonic Distortion); PV(photovoltaic) generation system;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Tada Ishikawa, "Grid-connected photovoltaic power systems: surveys of inverter and related protection equipments," IEA-PVPS Report, IEA-PVPS T5-05, 2002.
2 Moon-Ju Ko, Ick Choy, Ju-Yeop Choi, Seung-Ho Song, Ki-Ok Lee, "Novel AFD method of islanding detection with a periodic zero current for improving on islanding detection for grid-connected photovoltaic inverters", Journal of the Korean Solar Energy Society, Vol.26, Aprill 2006, pp. 17-22.   과학기술학회마을
3 Jin-Ung An, Gwon-Jong Yu, Ich Choy, Ju-Yeop Choi, Ki-Ok Lee, "Modeling and Analysis of Modified Active Frequney Drift Method", Power electronics annual conference, Vol.16, No.2, 2011, pp. 145-151.
4 KEPCO, "분산형전원 배전계통 연계 기술기준", 2010
5 IEEE Recommended Practice for Utility Interface of Photovoltaic(PV) Systems, IEEE Standard 929-2000, April 2000.
6 RoppM.E., BegovicM. and Rohatgi A., "Analysis and performance assessment of the active frequency drift method of islanding prevention", IEEE Transactions on Energy Conversion, vol. 14, pp.810-816, Sept. 1999.   DOI   ScienceOn
7 J. Yin, L. Chang, and C. Diduch, "Recent developments in islanding detection for distributed power generation," in Proc. 2004 Large Engineering Systems Conferenceon Power Engineering, pp. 124-128, 2004.
8 Jung Y., Choi J., Yu B., So J. and Yu G., "A Novel Active Frequency Drift Method of Islanding Prevention for the grid-connected Photovoltaic Inverter", in Proc. 2005 Power Electronics Specialists Conference, pp. 1915-1921.
9 Y. S. Jung, J. H. Choi, and G. J. Yoo, "A novel active anti-islanding method for grid-connected photovoltaic inverters," J. Power Electron., vol. 7, no. 1, pp. 64-71, Jan. 2007.
10 JANG S.-I., KIM K.-H.: 'An islanding detection method for distributed generations using voltage unbalance and total harmonic distortion of current', IEEE Trans. Power Deliv., 2004, 19, (2), pp. 745-752
11 IEEE recommended practices and requirements for harmonic control in electrical power systems, IEEE Std 519-1992, 1992.
12 이기옥, "주파수변이 단독운전 검출기법의 모델링 및 분석", 박사학위논문, 광운대학교, 2010.
13 S.A.M. Verhoeven, "Utility aspects of grid-connected photovoltaic power systems," IEA-PVPS Report, IEA-PVPS T5-01, 1998.