• Title/Summary/Keyword: 3rd Harmonics Current

Search Result 24, Processing Time 0.039 seconds

Influence of Harmonics in Power System Voltage on Arrester Deterioration Diagnostics by Leakage Current Measurement (누설전류측정에 의한 피뢰기 열화진단에 있어 전원고조파의 영향)

  • 길경석;한주섭;주문노
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.52 no.1
    • /
    • pp.42-46
    • /
    • 2003
  • Arresters are deteriorated by overvoltages or impulse currents, and the resistive leakage current of arresters increases as the deterioration of the arrester progresses, showing an increase in the 3$^{rd}$ harmonic component of the leakage current. In this reason, arrester diagnostic techniques based on the 3$^{rd}$ harmonic leakage current as a reference parameter of deterioration are widely used. The technique, however, includes an error due to the harmonics of power system voltage. Therefore, the influence of the harmonics on arrester diagnostics should be considered. In this paper, we designed a PSpice ZnO arrester model to simulate the influence of the voltage harmonics described above. A pure sinusoidal voltage and its the 3r harmonic voltage were applied to the model, and the leakage current components were analyzed. From the simulation results, it is confirmed that the peak value of resistive leakage current depends not only on the phase of the 3$^{rd}$ harmonic voltage but also on the magnitude of it. Consequently, the errors caused 1)y the harmonic voltage could be minimized by correcting the magnitude of leakage current upon analyzing the harmonics.cs.

A Technique of Deterioration Diagnosis for ZnO Element by Analyzing the 3rd order Harmonics- of Leakage Current (누설전류의 제3고조파 분석에 의한 ZnO소자의 열화진단기술)

  • Lee, Bok-Hee;Kang, Sung-Man
    • Proceedings of the KIEE Conference
    • /
    • 1998.07e
    • /
    • pp.1740-1742
    • /
    • 1998
  • This paper describes the technique of deterioration diagnosis for ZnO element. Due to the non-linear resistance of ZnO block, the total leakage current contains harmonics when arrester deteriorated. The most significant harmonics is the 3rd order component. So, it can be used as an indicator of the arrester condition. An iron core, which has a very high relative permeability, is used for increasing detection sensitivity and the 3th order harmonics of leakage current was detected by band-pass circuit. And we have verified the reliability and performance of the sensing device through several laboratory tests.

  • PDF

Harmonics Analysis of Leakage Current due to Artificial Contamination of Distribution Arresters (배전용 피뢰기의 인공오손에 의한 누설전류의 고조파 분석)

  • Park, Jae-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.9
    • /
    • pp.1306-1313
    • /
    • 2012
  • This paper reports the contamination performance of two distribution arresters (new and used ones) tested under three different contaminant conditions - clean fog, ESDD (equivalent salt deposit density) level (A, B, C, and D), and kaolin contamination conditions, and their leakage current, total leakage current, and component of the resistive leakage current were measured in order to diagnose arrester deterioration. The 3rd harmonics was larger than 5th and 7th ones for the arrester under the clean fog, and as the ESDD contamination level was applied, 5th one became relatively larger than 3rd one. Therefore, these results indicated that the resistive leakage current could be used for the diagnosis of the arresters.

A Vector Control System for Five-Phase Squirrel-Cage Induction Motor Considering Effects of 3rd Current Harmonics Component (제3 고조파 전류성분의 영향을 고려한 5상 농형 유도전동기의 벡터제어 시스템)

  • Kim, Min-Huei;Kim, Nam-Hun
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.61 no.4
    • /
    • pp.206-213
    • /
    • 2012
  • This paper propose a improved speed control system for five-phase squirrel-cage induction motor(IM) considering effects of 3rd. harmonic current components with field oriented control(FOC) A five-phase IM drives present unique characteristics due to the additional degrees of freedom and also drives possess many others advantage compared with the traditional three-phase motor drive system, such as reducing a amplitude of torque pulsation at low frequency and increasing the reliability. In order to maximize the torque per ampere, the proposed motor has concentrated windings. The produced back-electromotive force is almost trapezoidal, and the motor is supplied with the combined sinusoidal plus third harmonic of currents. There is necessary to controlled 3rd harmonic current. For presenting the superior performance of the proposed the speed control system, experimental results are presented using a 32-bit fixed point TMS320F2812 DSP with 1.5[KW] induction motor.

A Study on the Influence of Harmonics in Power System Voltage on Arrester Diagnostics and its Compensation (피뢰기 열화진단에 있어 전원 고조파의 영향과 보정에 관한 연구)

  • Kim, Il-Kwon;Song, Jae-Yong;Han, Ju-Seop;Kil, Gyung-Suk;Rhyu, Keel-Soo;Cho, Han-Goo
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.11
    • /
    • pp.493-497
    • /
    • 2005
  • This paper dealt with the influence of harmonic voltages on arrester diagnostics and its compensation method by using a designed Pspice arrester model. A pure sinusoidal voltage and its 3$^{rd}$ harmonic voltage were applied to the model, and the leakage current components were analyzed. The simulation results have shown that the peak value of resistive leakage current depends not only on the phase of the 3$^{rd}$ harmonic voltage but also on the magnitude of it. In this paper, an approximated 5$^{th}$ order polynomial formula by the Least-Square-Technique was derived, and correction factors which compensate the error caused by the 3$^{rd}$ harmonic voltage were calculated.

A Speed Control Characteristics for Five-Phase Squirrel-Cage Induction Motor Injecting 3rd Current Harmonics Component (제3 고조파 전류성분 주입에 의한 5상 농형 유도전동기의 속도제어 특성)

  • Kim, Min-Huei;Kim, Nam-Hun
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.18 no.3
    • /
    • pp.279-288
    • /
    • 2013
  • This paper proposes a improved speed control system for five-phase squirrel-cage induction motor(IM) injecting 3rd. current harmonic components with field oriented control (FOC) A five-phase IM drives present unique characteristics due to the additional degrees of freedom and also drives possess many others advantage compared with the traditional three-phase motor drive system, such as reducing a amplitude of torque pulsation at low frequency and increasing the reliability. In order to maximize the torque per ampere, the proposed motor has concentrated windings. The produced back-electromotive force is almost trapezoidal, and the motor is supplied with the combined sinusoidal plus third harmonic of currents. There is necessary to controlled 3rd harmonic current in order to high response characteristics. For presenting the superior performance of the proposed the speed control system, experimental results are presented using a 32-bit fixed point TMS320F2812 DSP with 1.5[kW] induction motor.

Influence of System Voltage Harmonics on Arrester Deterioration Diagnostic Techniques by Leakage Current Measurement (누설전류측정에 의한 피뢰기 열화진단기술에 있어 전원고조파의 영향)

  • Kil, Gyung-Suk;Han, Joo-Sup
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.08a
    • /
    • pp.142-145
    • /
    • 2002
  • This paper describes an influence of system voltage harmonics on arrester deterioration diagnostic techniques based on leakage current measurement because the resistive current is composed of two components caused by nonlinear characteristics of arrester and by system voltage harmonics. Resistive leakage currents of arresters, which can be evaluated by the third harmonic component of total leakage currents, increase with its deterioration progress. In this paper, we developed a PSpice model for ZnO arrester to simulate the harmonics' effect described above. In simulation, pure sinusoidal voltage and the $3^{rd}$ harmonic voltage are applied to the model, and the leakage current changes are compared. The simulation results showed that the magnitudes of resistive leakage current depend not only on the phase of system voltage harmonics but also on the magnitude of it.

  • PDF

Characteristics analysis of PFC boost converter with soft switching for harmonics reduction (고조파 저감을 위한 소프트 스위칭 승압형 PFC컨버터의 특성해석)

  • 김봉규
    • Proceedings of the KIPE Conference
    • /
    • 2000.07a
    • /
    • pp.150-154
    • /
    • 2000
  • This paper proposes PFC boost converter with soft switching for harmonics decrement and analyzes characteristics of PFC boost converter. In this technique power factor correction(PFC) is usually obtained by operating the PFC stage in the discontinuous current mode(DCM) Switching devices are operated for reducing current stress and electronical noise. As a result eliminate 3rd harmonic component and high power factor(PF) of the input line are verified by characteristics analysis and experimental results.

  • PDF

Characteristics Leakage Current of Surface Discharge according to Kaolin Contamination by Deteriorated Polymer Insulators (열화된 고분자애자의 카올린 오손에따른 표면방전특성)

  • Park, Jae-Jun;Ga, Pyung-Hyun;Seo, Ui-Won;Jung, Myeong-Yeon;Song, Il-Kwen;Kim, Hee-Dong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1100-1103
    • /
    • 2004
  • The paper presents the results of using the fundamental and the low frequency harmonic components of leakage current to study aging of EPDM insulator for contaminated condition by kaolin. The largeer the leakage current during 200ms, the higher harmonic component at 60hz. The harmonic component at 60hz and the odd order harmonics is increase relation without Kaolin Conent. Arcing on the surface was always associated with distortion in the leakage current; hence the low frequency components of the leakage currnent can be used as a means to evaluate the surface degration. Both the fundamental and 3rd & 5th harmonics increase dry-band activity.

  • PDF

Safely Improving Method to Zero-Harmonics Current with 4-Pole Low Voltage Circuit Breaker Equipped N-phase Trip Device (4극 저압차단기 N상 Trip장치를 사용한 영상고조파 안전성 개선방안)

  • Ki, Che-Ouk;Kim, Ju-Chul;Choi, Chang-Kyu
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.05a
    • /
    • pp.458-461
    • /
    • 2009
  • In 3-phase 4 wire system, appearance of the $3^{rd}$ harmonic current by increasing non-liner load is the one of causes overheating neutral wire of power line, and apparatus. So it is necessary to protect power-factor decreasing by the $3^{rd}$ harmonic, and electric power apparatus, and line safely, in this study, power system accidents caused by the $3^{rd}$ harmonic were investigated, then harmonic components analysis and unbalanced load analysis got accomplished. As result, we proposed the method to protect the power line and apparatus from over-current of neutral line by using the most economic 4-pole low voltage circuit breaker.

  • PDF