Safely Improving Method to Zero-Harmonics Current with 4-Pole Low Voltage Circuit Breaker Equipped N-phase Trip Device

4극 저압차단기 N상 Trip장치를 사용한 영상고조파 안전성 개선방안

  • 기채옥 (서울산업대학교 대학원 전기공학과) ;
  • 김주철 (서울산업대학교 대학원 전기공학과) ;
  • 최창규 (서울산업대학교 대학원 전기공학과)
  • Published : 2009.05.07

Abstract

In 3-phase 4 wire system, appearance of the $3^{rd}$ harmonic current by increasing non-liner load is the one of causes overheating neutral wire of power line, and apparatus. So it is necessary to protect power-factor decreasing by the $3^{rd}$ harmonic, and electric power apparatus, and line safely, in this study, power system accidents caused by the $3^{rd}$ harmonic were investigated, then harmonic components analysis and unbalanced load analysis got accomplished. As result, we proposed the method to protect the power line and apparatus from over-current of neutral line by using the most economic 4-pole low voltage circuit breaker.

3상 4선식 배전방식에서 비선형 부하증가로 인한 제 3고조파 전류발생은 선로의 중성선 및 기기를 과열시키는 원인으로 작용하고 있다. 따라서 고조파에 의한 역률저하 및 기기, 선로 등을 안전하게 보호할 필요가 있다. 본 논문에서는 제 3고조파 전류로 인한 사고사례를 조사하고 고조파 분석 및 부하 불평형 등을 분석하였다. 이를 통해 가장 경제적인 4극 저압차단기를 사용하여 중성선의 과전류로부터 선로 및 기기를 보호하는 방법을 제시하였다.