• 제목/요약/키워드: 열 화원

검색결과 46건 처리시간 0.018초

대심도 지하역사에서의 화재시 플랫폼 스크린 도어에 의한 열, 연기 거동 영향 분석 (The Analysis of the effects of the platform screen door on the fire driven flow in The Deeply Underground Subway Station)

  • 장용준;김학범;이창현;정우성
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2008년도 추계학술대회B
    • /
    • pp.1984-1989
    • /
    • 2008
  • In this study, fire simulations were performed to analyze the characteristics of the fire driven flow and the effects of the platform screen door on the smoke flow in the station, when the fire occurred in the center of the platform. Soongsil Univ. station (line number 7, 47m in depth underground) was chosen which was the one of the deepest underground subway stations in the Seoul metro, SMRT. The parallel computational method was employed to compute the heat and mass transfer eqn's with 6 CPUs of the linux clustering machine. The fire driven flow was simulated with using FDS code in which LES method was applied. The Heat release rate was 10MW and The Ultrafast model was applied for the growing model of the fire source. The 10,000,000 structured grids were used.

  • PDF

터널 화재시 종횡비에 따른 연기 거동에 관한 수치해석적 연구 (A Numerical Study of an Effect of the Aspect Ratio on Smoke Movement in funnel Fires)

  • 이성룡;김충익;유홍선
    • 한국화재소방학회논문지
    • /
    • 제18권2호
    • /
    • pp.1-6
    • /
    • 2004
  • 본 연구에서는 터널 화재 시 종횡비에 따른 연기의 거동 특성을 파악하기 위하여 화재 전용 해석 코드인 FDS 3.0을 이용하여 수치해석 하였다. 수치해석 결과를 실험 결과와 비교하여 FDS의 터널 화재 적용 가능성을 검증하였으며, 실험 값과 비교한 결과 1$0^{\circ}C$이내의 범위에서 비교적 잘 일치하였다. 속도 분포를 이용한 연층의 경계높이의 예측 값이 실험과 약 3%의 오차를 보였으며 온도장과 속도장의 해석을 통해 터널내 연기의 거동을 확인하였다. 종횡비의 변화에 따른 결과도 잘 일치하였으며, 종횡비가 증가할수록 화원 부근에서는 온도가 낮지만 연기가 퍼져나가면서 폭방향으로의 열손실 감소로 인해 온도 감소율은 줄어들었다.

어린이집 화재 시 연기 거동에 관한 실험적 연구 (An Experimental Study of Smoke Movement in a Kindergarten Fire)

  • 이성룡;한동훈
    • 한국화재소방학회논문지
    • /
    • 제27권2호
    • /
    • pp.62-69
    • /
    • 2013
  • 본 연구에서는 어린이집 화재 시 열 및 연기의 거동 특성을 파악하기 위하여 재개발 예정지의 어린이집에서 실험이 실시되었다. 실험대상 어린이집은 2층 구조로 되어있으며, 각 층의 연면적은 252 $m^2$이다. 가연물로는 헵탄 36리터를 사용하였다. 한 변의 길이가 0.8 m인 정사각형 화원을 사용하였으며, 정상상태에서 최대 열방출율은 약 1.7MW이다. 실험동안 연기의 이동 및 온도 변화를 측정하였다. 1층 복도에서, 화재 발생 1분 후 연기가 1.4 m 높이까지 하강하였으며, 화재 발생 약 4분 후 복도 전체가 연기로 가득 찼다. 2층 대부분의 영역에서 온도가 $70^{\circ}C$ 이하로 유지되었으나 실내가 연기로 가득 찼다.

가연성 물질에 따른 워터커튼 시스템의 열 및 연기유동 제어특성에 관한 연구 (A Study on the Effect of Inflammable Materials on the Control Characteristics of Thermal and Smoke Fluid of Water Curtain System)

  • 유우준;남준석;김동준;이정균;유홍선
    • 한국화재소방학회논문지
    • /
    • 제26권2호
    • /
    • pp.53-58
    • /
    • 2012
  • 본 연구에서는 가연성 물질을 고려한 워터커튼 시스템(Water Curtain System)의 열 및 연기유동 제어 특성을 실험적으로 분석하였다. 이를 위해서 Room Corner Tester(RCT)를 사용하여 연료의 종류가 소나무(PineWood)와 가솔린(Gasoline)인 경우 각각의 발열량(Heat Release Rate)을 구하였으며, 워터커튼용 화재실험 장치를 제작하여 화원근방에서 5m 떨어진 지점의 천장 부근에 분사각도 $180^{\circ}$, 오리피스 직경 8.2 mm의 노즐(Nozzle)을 설치한 후 목재와 가솔린 각각에 대해서 화재실험을 실시하여 워터커튼 전후의 온도분포와 가시도를 측정하였다. 그결과 워터커튼 시스템의열및연기유동 제어는 가연성 물질의 연소특성에 따른 고온의 연기발생량과 분사 노즐에 의한 유동현상이 중요한 상관관계를 갖고 있음을 확인하였다.

짧은 터널 내의 연기거동에 관한 연구 (A Study of Smoke Movement in a Short Tunnel)

  • Kim, Sung-Chan;Ryou, Hong-Sun;Kim, Chung-Ik;Hong, Ki-Bae
    • 터널과지하공간
    • /
    • 제12권1호
    • /
    • pp.31-36
    • /
    • 2002
  • 터널화재시 화원의 크기에 따른 연기기동을 파악하기 위하여 모현실험 및 수치해석이 수행되었다. 모형실험의 결과를 실제 터널에 대해 적용하기 위하여 Frode상사법을 이용하였다. 터널공간내의 화재 해석에 대한 수치해석의 타간성을 입증하기 위하여 모형실험과 수치해석에서 얻어진 연층의 온도분포를 비교하였다. 터널내 온도분포를 해석함으로써 배기장치가 없는 짧은 터널에 대하여 연층은 전체 터널 높이의 절반 이하로 하강하지 않는다는 사실을 파악하였다. 또한 실험에서 얻어진 연층선단의 전파속도는 화재 발생부의 1/3 풍에 비례한다는 사실을 파악하였으며 이는 기존의 경험식 및 수치해석결과와도 잘 일치하였다. 따라서 짧은 터널에서 화재시 피난대책을 수립하는데 있어서 연층의 수평전파가 수직전파에 비해 중요한 설계변수임을 본 연구를 통하여 제시하였다.

지지체의 변화에 따른 Ni-페라이트의 2단계 열화학 사이클 반응 특성에 관한 연구 (Two-Step Thermochemical Cycle with Supported $NiFe_2O_4$ for Hydrogen Production)

  • 김우진;강경수;김창희;조원철;강용;박주식
    • 한국수소및신에너지학회논문집
    • /
    • 제19권6호
    • /
    • pp.505-513
    • /
    • 2008
  • The two-step thermochemical cycle was examined on the $CeO_2$, YSZ, and $ZrO_2$-supported $NiFe_2O_4$ to investigate the effects of support material addition. The supported $NiFe_2O_4$ was prepared by the aerial oxidation method. Thermal reduction was conducted at 1573K and 1523K while water-splitting was carried out at 1073K. Supporting $NiFe_2O_4$ on $CeO_2$, YSZ and $ZrO_2$ alleviated the high-temperature sintering of iron-oxide. As a result, the supported $NiFe_2O_4$ exhibited greater reactivity and repeatability in the water-splitting cycle as compared to the unsupported $NiFe_2O_4$. Especially, $ZrO_2$-supported $NiFe_2O_4$ showed better sintering inhibition effect than other supporting materials, but hydrogen production amount was decreased as cycle repeated. In case of $CeO_2$-supported $NiFe_2O_4$, improvement of hydrogen production was found when the thermal reduction was conducted at 1573K. It was deduced that redox reaction of $CeO_2$ activated above 1573K.

화염 전파모델을 이용한 소파화재 설계화원구성의 적용성 연구 (Feasibility Study on the Fire Scenario Design of a Couch Burning through a Fire Spread Model)

  • 김성찬
    • 한국화재소방학회논문지
    • /
    • 제30권6호
    • /
    • pp.37-42
    • /
    • 2016
  • 본 연구는 화재전파해석 모델을 이용하여 화재 위험성 평가에 적용되는 설계화재 구성의 적용가능성을 파악하고자 한다. 화재전파해석을 위해 열중량분석과 시편연소실험이 수행되었으며 실험에서 얻어진 물성을 FDS 열해리 모델에 적용하여 격자크기에 따른 화재해석을 수행하였다. 해석 결과 전체적인 화재성장특성은 실화재 실험결과와 큰 차이를 보였으나 초기 피크 발열량과 전체 방출 열에너지는 약 30% 이내에서 유사한 예측결과를 보였다. 본 연구의 해석모델은 화재성장율이나 최대발열량 도달시간 등과 같은 화재성장특성을 예측하는데 한계를 보였다. 그러나 지속적인 모델의 개선 및 재료 물성의 상세연구를 통해 설계화재시나리오 구성에 있어서 화재모델의 적용성이 있음을 보여준다.

구획 화재에서 스프링클러 열 손실계수 변화에 따른 작동 시간 분석 (Analysis on the Effects of the Heat Loss Coefficient on the Operation Time of Sprinkler in Compartment Fire)

  • 유우준
    • 한국화재소방학회논문지
    • /
    • 제32권5호
    • /
    • pp.34-39
    • /
    • 2018
  • 본 연구에서는 구획 공간 화재 시 발열량이 급격히 변하는 조건에서 스프링클러헤드의 손실인자 변화에 따른 작동시간을 분석하였다. 이를 위해서 내화보드로 구성된 구획 공간의 크기가 폭 0.3 m, 세로 0.5 m, 길이 3.0 m인 구조물을 제작하고 헵탄(n-Heptane) 풀 화재 실험을 수행하여 구획 공간 내부의 온도 분포, 헵탄의 질량감소율 그리고 발열량을 산출하였다. 또한, Fire Dynamics Simulator (FDS) Version 6.5를 사용하여 실험 조건과 동일한 발열량을 가정하고 스프링클러헤드의 설치위치 및 손실인자(C-factor) 변화에 따른 작동 시간을 분석하였다. 그 결과 반응시간지수(Response Time Index, RTI)가 $100(m{\cdot}s)^{0.5}$이고 작동온도가 $72^{\circ}C$인 스프링클러는 화원 상층부의 기류 온도가 $100^{\circ}C$에서 $300^{\circ}C$로 상승하고, 기류의 속도가 약 0.7 m/s인 경우 C-factor = 0과 1일 때 스프링클러의 작동시간은 최소 30 s~60 s, C-factor = 3일 때 62 s에서 최대 92 s, C-factor = 5일 때 120 s 이상으로 나타났다.

화재모델링을 이용한 목표 대상물의 열적 손상에 대한 정량적 위험성 평가방법의 고찰 (An Investigation of Quantitative Risk Assessment Methods for the Thermal Failure in Targets using Fire Modeling)

  • 양호동;한호식;황철홍;김성찬
    • 한국화재소방학회논문지
    • /
    • 제30권5호
    • /
    • pp.116-123
    • /
    • 2016
  • 화재모델링을 이용한 목표 대상물의 열적 손상에 대한 정량적 위험성 평가방법이 검토되었다. 이를 위해 대표적인 화재모델로서 FDS가 사용되었으며, 특정 구획 내에서 화원 면적 변화에 따른 전기 케이블의 열적 손상과 관련된 확률이 평가되었다. 보수적 관점에서 적용되고 있는 '최대 손상임계 초과확률'과 손상시간의 정보가 포함된 '손상확률'이 체계적으로 비교되었다. 목표 대상물이 표면온도 및 열유속에 대한 최소 손상기준에 도달하는 순간에 열적 손상이 발생된다는 가정이 적용된 최대 손상임계 초과확률에 비해 본 연구에서 제안된 손상확률은 정량적 화재 위험성을 보다 현실적으로 평가할 수 있음을 확인하였다.

화재성장시나리오에 따른 스프링클러 헤드의 작동조건 (Activation Conditions of Sprinkler Head Considering Fire Growth Scenario)

  • 김성찬
    • 한국화재소방학회논문지
    • /
    • 제34권4호
    • /
    • pp.45-51
    • /
    • 2020
  • 본 연구에서는 스프링클러 헤드의 해석모델을 통해 화재성장모드별 스프링클러 작동시 연층기류의 열유동조건을 파악하고자 한다. 화원은 최대발열량 3 MW의 시간제곱의 화재성장을 가정하였다. 시험대상 스프링클러헤드는 작동온도 65~105 ℃, RTI 25~171 m1/2s1/2 범위의 표준형과 조기반응형 8종을 대상으로 한다. 연층기류의 온도와 감열부의 온도차는 화재성장이 느리고 스프링클러 헤드의 RTI값이 작을수록 감소하는 경향을 보였다. 스프링클러 헤드 작동 순간의 연층 기류 온도와 속도조건은 전체적으로 시험기준의 범위와 비교적 잘 일치하고 있으나 저성장 화재에서는 최저시험기준 이하의 온도와 속도조건에서 작동이 이루어질 수 있음을 파악하였다. 본 연구는 스프링클러 헤드의 작동에 대한 기초연구로서 시험기준의 신뢰성을 향상시키는데 기여할 수 있다.