Browse > Article
http://dx.doi.org/10.7731/KIFSE.2012.26.2.053

A Study on the Effect of Inflammable Materials on the Control Characteristics of Thermal and Smoke Fluid of Water Curtain System  

You, Woo-Jun (중앙대학교)
Nam, Jun-Seok (한국소방산업기술원)
Kim, Dong-Joon ((주)파라다이스산업)
Lee, Jeong-Kyoon ((주)파라다이스산업)
Ryou, Hong-Sun (중앙대학교)
Publication Information
Fire Science and Engineering / v.26, no.2, 2012 , pp. 53-58 More about this Journal
Abstract
In this study fire control characteristics for inflammable materials of water curtain system are experimentally analyzed. Heat release rate for pinewood and gasoline was calculated using Room Corner Tester (RCT) and fire test apparatus for water curtain system is manufactured. Nozzles (180 degree of injection angle, 8.2 mm of orifice diameter) are installed at the nearby ceiling of place at 5 m distance from fire originate and temperature profile as well as transmission are obtained from the fire experiment of pinewood and gasoline in the water curtain system. Based on the results, parameters of engineering importance for fire control characteristics of water curtain system such as generation of high temperature smoke and thermal phenomena of fluid flow by injection nozzle are identified.
Keywords
Inflammable materials; Water curtain system; Room corner tester; Heat release rate; Nozzle;
Citations & Related Records
Times Cited By KSCI : 4  (Citation Analysis)
연도 인용수 순위
1 W.J. You, J.S. Nam, J.J. Choi, and D.J. Kim, "An Analysis of the Smoke Control Characteristics of Water Curtain System for Underground Space", Korea Institute of Fire Science and Engineering Conference, pp.298-301(2011).
2 G.H. Ko, S.C. Kim, A. Hamins, and H.S. Ryou, "FDS Simulation and Validation on the Under- Ventilated Compartment Fires", J. of Korean Institute of Fire Sci. & Eng., Vol.23, No.5, pp.103-109 (2009).   과학기술학회마을
3 C.S. Ahn, H.S. Chae, and H.Y. Kim, "A Study on the performance Criteria of Smoke Control System for Underground Spaces Through Numerical Analysis", KIFSE, Proceedings of 2008 Autumn Annual Conference, pp.356-362(2008).   과학기술학회마을
4 Reiko Amano, "Water Screen Fire Disater Prevention System", Seisan-Keneyu, Vol.57, No.4, pp.177-181 (2005)
5 The SFPE Handbook 4th, Chapter 3(2008).
6 Standards of Model Approval and Inspection Technology for Manual Extinguisher, National Emergency Management Agency Notice No.2010- 13.
7 V. Babrauskas and S.J. Grayson, "Heat Release in Fires", Fire Science and Technology Inc.
8 W.K. Chow and S.S.Han, "Heat Release Rate Calculation in Oxygen Consumption Calorimetry", Applied Thermal Engineering, Vol.31, pp.304-310 (2011).   DOI   ScienceOn
9 Robert H. White and Mark A. Dietenberge, "Wood Handbook - Wood as an Engineering Material", Forest Products Laboratory, U.S.D.A Forest Service.
10 Y.J. Chung and M. Spearpoint, "Combustion Oroperties of Native Korean Wood Species", International Journal on Engineering Performance- Based Fire Codes, Vol.9, No.3, pp.118-125(2007).
11 S.K. Roh and J.H. Hur, "A Study on the Risk Assessment of the Underground Space - The Estimation of Smoke Reservoir Screen for Smoke Control in Subway Station Platform", T. of Korean Institute of Fire Sci. & Eng., Vol.18, No.4, pp.103- 109(2004).   과학기술학회마을
12 J.S. Kim, J.K. Park, and S.K. Roh, "A Study on the Development of Evacuation Safety Assessment System on Underground Space", T. of Korean Institute of Fire Sci. & Eng., Vol.17, No.4, pp.57- 63(2003).   과학기술학회마을