• Title/Summary/Keyword: 열감지기

Search Result 26, Processing Time 0.025 seconds

Study on the Operation Characteristics of Heat Detectors through Fire and Wind Tunnel Experiment (풍동실험과 화재실험을 통한 열감지기의 동작특성에 관한 연구)

  • Ryu, Hocheol;Kim, Doohyun
    • Journal of the Society of Disaster Information
    • /
    • v.11 no.2
    • /
    • pp.203-209
    • /
    • 2015
  • The heat detector detects heat in the fire and is an important core element of the automatic fire alarm system used generally for every fire prevention objects. The heat detector is distinguished in spot type and spread type and in spot type, there are differential and thermistor types. These heat detectors give a great influence on the loss of people and property according to the sensitivity of response such as operation time and operation temperature in actual fire and in overseas people apply it for the development of products that can be operated in the early stage of fire including certification, quality management, and comparison standard by introducing response time index through the theory of heat balance that considers the heat loss and ventilation tests. In Korea, the response time index is introduced and used in the head of sprinkler products, but it is not applied to the heat detector at present. It is necessary to introduce the response time index that shows the sensitivity of response of the heat detector the installation standard for the heat detector that the response time index is applied should be different according to the fire weight, danger degree of fire, and shape of buildings. Through this study, it tries to help reduce lives and property of people through the swift warning by installing detectors suitable for the building structure.

Analysis on Activation Characteristic of Heat Detectors in a Compartment Fire (실내화재에서의 열감지기 동작특성 분석)

  • Ryu, Hocheol
    • Journal of the Society of Disaster Information
    • /
    • v.10 no.4
    • /
    • pp.598-608
    • /
    • 2014
  • The first operation of alarm system starts at a detector. And the largest effect is produced on the operation of detector by the fire source position and installation position. Nevertheless, the Korean standard for the installation of detector only specifies matters of fire detector installation according to area and height, without consideration of installation position and fire source position. Therefore, this study carried out a fire test in consideration of detector installation position and fire source position (5 places) in order to minimize casualties owing to the fast operation of fire detector when a fire occurred. Considering that it took the longest time for a detector close to a wall to work in the results of this test, it was possible to find that a minimum clearance to the wall was required.

An Analysis of False Alarm Threshold Value by Heat Detector Using Heat Release Rate (열방출률을 이용한 열감지기의 오동작 경계값 분석)

  • 홍성호;김두현
    • Fire Science and Engineering
    • /
    • v.17 no.3
    • /
    • pp.26-30
    • /
    • 2003
  • This paper presents a study on the analysis for false alarm of heat detector using HRR(Heat Release Rate). And it is represented to threshold value and domain of false alarm. The HRR threshold value of false alarm is calculated to use parameters obtained by small scale fire-experiment. The experiment is conducted to measure detector activation time and flame spread of wood cribs fire, etc. The results show that HRR threshold value of Fixed type detector is 20.24 kW and rate of rise type detector is 13.59 kW, respectively.

Response Time Index and Operation Time of Fixed Temperature Heat Detector (정온식 열감지기의 응답시간지수 및 작동시간)

  • 류호철;태순호;이병곤
    • Fire Science and Engineering
    • /
    • v.7 no.1
    • /
    • pp.11-16
    • /
    • 1993
  • Fixed temperature heat detectors that respond to the heat generated in fire plume and alarm when the temperature reaches a specified point, give a great influences to the loss of life and property according to their reaction sensitivity. In this study, hot wind tunnel tests and compartment fire experiments were performed to investigate the response time and temperature of fixed temperature heat detector. As a result, simple equations were derived which can be predicted the response time and temperature of the fixed temperature heat detector for the ramp type fire. Also other useful data, such as the effective temperature, time constant, response time index(RTI) were obtained.

  • PDF

Study on Influence of Air Flow of Ceiling Type Air Conditioner on Fire Detector Response (천장형에어컨 기류가 화재감지기 작동에 미치는 영향 분석)

  • Choi, Moon-Soo;Lee, Keun-Oh
    • Fire Science and Engineering
    • /
    • v.32 no.5
    • /
    • pp.40-45
    • /
    • 2018
  • This paper is an analysis of the influence of ceiling air conditioner airflow on fire detector response. In order to analyze the response characteristics of fire detector while forming air flow of a ceiling-type air conditioner, fire tests were carried out in accordance with ISO standard. This experiment was carried out in a fire test site of 10 m (width) ${\times}$ 7 m (length) ${\times}$ 4 m (height). As a result of the experiment, the response of fire detector shows a normal pattern that is delayed as the distance from the fire source is increased in the absence of the air conditioner, but it is confirmed that the pattern is not maintained in the strong air flow. When the air flow of air conditioner was strong, the response time was increased by 121% in the smoke detector and by 39% in the heat detector. In the case of ceiling type air conditioners, it is considered that the number of fire detectors should be increased, or a detector with high sensitivity should be installed for early detection of fire.

DB Construction of Activation Temperature and Response Time Index for Domestic Fixed-temperature Heat Detectors in Ceiling Jet Flow (천장제트기류에 대한 국내 정온식 열감지기의 작동온도 및 반응시간지수(RTI)에 관한 DB 구축)

  • Yoon, Ga-Yeong;Han, Ho-Sik;Mun, Sun-Yeo;Park, Chung-Hwa;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.34 no.3
    • /
    • pp.35-42
    • /
    • 2020
  • The accurate prediction of fire detector activation time is required to ensure the reliability of fire modeling during the safety assessment of performance-based fire safety design. The main objective of this study is to determine the activation temperature and the response time index (RTI) of a fixed heat detector, which are the main input factors of a fixed-temperature heat detector applied to the fire dynamics simulator (FDS), a typical fire model. Therefore, a fire detector evaluator, which is a fire detector experimental apparatus, was applied, and 10 types of domestic fixed-temperature heat detectors were selected through a product recognition survey. It was found that there were significant differences in the activation temperature and RTI among the detectors. Additionally, the detector activation time of the FDS with the measured DB can be predicted more accurately. Finally, the DB of the activation temperature and RTI of the fixed-temperature heat detectors with reliability was provided.

A REPORT ON THERMAL LAG OF PAINTED HEAT DETECTORS (도막상태에 따른 열감지기의 감온특성에 관한 시험, 연구(2))

  • Lee, Bok-Yeong;Yu, In-Ho
    • Fire Protection Technology
    • /
    • s.15
    • /
    • pp.11-21
    • /
    • 1993
  • This report is announced about thermal lag of painted heat detectors. Thermal lag is forecast result from painting the part of heat receiving. Test is simulated that heat detector is painted by synthetic resin emulsion paint according to the cricumstance of installation, corrosion, temperature, dust.

  • PDF

A Study of the Rate of Rise Spot Type Heat Detector on the Artificially Accelerated Aging Characteristics (차동식 스포트형 열감지기의 인공 가속열화특성에 관한 연구)

  • Kim, Chan-Young
    • Fire Science and Engineering
    • /
    • v.25 no.2
    • /
    • pp.107-113
    • /
    • 2011
  • This paper presents the results of artificially accelerated aging characteristics of the rate of rise spot type heat detectors. This experiment carried out to investigate the detector's operating characteristics when a fire was broken out or the regular tests were performed. The result showed that the delay of operating time or no-operation of heat detector which was made by company B and used in the field for 5 years may be occurred even at the $100^{\circ}C$. This result is due to the leakage of inflated air from heat chamber. However the operating display LED was not out of order, even if the temperature was increased up to $160^{\circ}C$.

A Study on the Response Characteristics of Fire Detector by Full-scale Experiment of Fire Phenomena in the Row House (주택 실물화재실험에 의한 화재감지기 응답특성에 관한 연구)

  • SaKong, Seong-Ho;Kim, Shi-Kuk;Lee, Chun-Ha;Jung, Jong-Jin
    • Fire Science and Engineering
    • /
    • v.23 no.3
    • /
    • pp.67-72
    • /
    • 2009
  • This paper is for response feature of fire detectors not only to analysis response feature of fire detector, but also to observe flame spread of inside-building and fire enlargement by using the row house which is supposed to be broken up. Many kinds of popular detectors such as heat type detector(differential type, fixed temperature type, Analogue type)and smoke type(light scattered type, Analogue type, single alarm type) were installed in the house in order to check for the change of temperature by installing of thermocouples. As a result, smoke detectors are better than heat detectors when it comes to making effective fire-detect system in the row house.