• 제목/요약/키워드: 소화 노즐

검색결과 74건 처리시간 0.021초

노즐 위치 및 분사각이 공기유동 및 $CO_2$ 소화제 전달특성에 미치는 영향 (The Effect of Nozzle's Location & Injection Angle on the Characteristics of Air Flow and $CO_2$ Extinguishant Transfer)

  • 박찬수
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제26권4호
    • /
    • pp.472-484
    • /
    • 2002
  • To analyze the characteristics of air flow and $CO_2$ extinguishant transfer when extinguishant is injected into a closed space similar to marine engine room, a numerical simulation on a space was performed. Flow fields and $CO_2$ concentration fields are calculated according with the variation of the location & injection angle of nozzles. The results of simulation showed that the pattern of recirculation flow was affected greatly with the location & injection angle of nozzles and such a recirculation flow accelerated mass transfer of $CO_2$ and greatly affected the diffusion process of $CO_2$ extinguishant. It is considered that this result of this study can be useful to designing the arrangement of nozzles for the $CO_2$ fire fighting equipments in a marine engine room.

2유체 미세 물분무 소화노즐의 분무유동 특성 (Spray Flow Characteristics of Twin-fluid Water Mist Nozzle for Fire Suppression)

  • 김봉환;최효성;김동건
    • 한국기계가공학회지
    • /
    • 제10권3호
    • /
    • pp.60-66
    • /
    • 2011
  • In the present investigation, experimental studies were conducted on the fire suppression performance of twin-fluid water mist spray which is subjected to thermal radiation in a closed space. Downward-directed water-mist sprays, interacting with an under kerosene pool fire, were investigated in a test facility. The mass mean diameter of water-mist droplets were measured by PMAS under various flow conditions. The developed twin-fluid water mit spray nozzle satisfied the criteria of NFPA 750, Class 1. The mechanism of fire suppression by fine water mist was concluded to be the cooling of the fire surface which leads to the suppression of fuel evaporation. It was proved that the automatic twin-fluid water mist spray system under lower pressures could be applied to an industrial facilities.

소화노즐의 분무특성에 대한 설계 변수 영향의 수치해석적 연구 (Numerical Study on the Effects of Design Parameters on the Spray Characteristics of Fire Suppression Nozzles)

  • 이창효;최병일;한용식;김창;정희택
    • 한국분무공학회지
    • /
    • 제11권4호
    • /
    • pp.199-204
    • /
    • 2006
  • Numerical investigation has been performed to simulate the spray characteristics in mist-spray fire suppression nozzles in sense of design parameters. Two key shape factors in nozzle orifices. i.e. diameter and length are chosen as simulation parameters. Commercial softwares, FLUENT and FDS with the proper modelings were applied as numerical tools. Main performances of nozzles, i.e., K-factors, spray angles, droplet size, jet velocities and fire suppression time are analyzed for each parameter to find optimal design conditions.

  • PDF

미분무수 소화 노즐의 분무 특성 예측을 위한 CFD기법의 적용 (APPLICATION OF CFD TECHNIQUE TO PERFORMANCE PREDICTION OF SPRAY CHARACTERISTICS OF WATER-MIST FIRE SUPPRESSION NOZZLES)

  • 정희택;이창효;최병일;한용식;옥영욱
    • 한국전산유체공학회지
    • /
    • 제11권4호
    • /
    • pp.56-61
    • /
    • 2006
  • Numerical simulation has been performed to investigate the characteristics of the mist flow through the fire suppression nozzles. The commercial CFD software, FLUENT with the proper modeling was applied for analyzing both the internal and external flow of the spray nozzles. Computations were made for the full cone nozzle in the operation range of the low pressure and high flow-rate. To validate the present computational procedure, numerical results are compared with measurements in terms of K-factor, SMD, axial spray velocity and spray angles. Numerical results suggested that the present numerical model can be used as an adequate tool for a design purpose of mist-spray nozzles.

소화 노즐의 분무 특성 예측을 위한 CFD 기법의 적용 (Application of CFD Technique to Performance Prediction of Spray Characteristics of Fire Suppression Nozzles)

  • 정희택;이창효;정향남;최병일;한용식;옥영욱
    • 유체기계공업학회:학술대회논문집
    • /
    • 유체기계공업학회 2005년도 연구개발 발표회 논문집
    • /
    • pp.233-239
    • /
    • 2005
  • In the present study, numerical simulation has been performed to investigate the characteristics of the mist flow through the fire suppression nozzles. The commercial CFD software, FLUENT with the proper modeling was applied in both the internal and external flow region of the spray nozzles. Applications were done to the full cone nozzle for the operation range of the low pressure and high flow-rate. Numerical validation was proved by the comparison of the experimental data. Parametric study of the key design factors was tried to improve the performance.

  • PDF

CFD를 이용한 소화시스템 노즐의 분무 특성에 대한 연구 (The Study of a Atomizing Characteristics of a Nozzle in a Fire Extinguishing System for using CFD)

  • 최관수;정영권;김영수;김인관
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.1184-1189
    • /
    • 2008
  • This paper is a study about characteristics of the SSC-1 nozzle, which is used in a fire extinguishing system in a ship. Through this paper, we can find that the traces and elements’ distributions obtained from experiments are as the same as the simulation analysis results of CFD program. At the point of 100mm, the $\alpha$ is 34.9 in the CFD analysis, and it is 32.5 in the experiment. This shows that there is no big different between the CFD analysis and the experiment result. And the average elements velocity is similar to the SMD.

  • PDF

ESS 화재전용 소화약제 및 소화시스템 개발에 관한 연구 (A Study on the Development of Fire Extinguishing Agent and Extinguishing System for ESS Fire)

  • 이연호;이주형;김수진;전성호;최병철;오승주;김시국
    • 한국화재소방학회논문지
    • /
    • 제34권2호
    • /
    • pp.147-155
    • /
    • 2020
  • 본 논문은 ESS 화재전용 소화약제 및 소화시스템 개발에 관한 연구이다. ESS 화재를 진압하기 위해 제작된 소화약제는 침윤제 타입으로 주된 소화효과인 냉각작용과 더불어 질식작용과 함께 표면장력 및 점도를 낮춘 침투성이 높은 소화약제로 ESS 모듈 내부의 배터리 셀까지 소화약제가 침투 가능한 특징이 있다. 소화시스템의 경우 랙 단위로 화재를 진압하는 국소방출방식으로 설계하였고, 소화효과를 극대화하기 위해 랙에 장착되는 일반형 노즐과 ESS 모듈 후면 홀에 삽입하는 360° 회전형 노즐을 제작하고, 가스방출압력에 의해 소화약제가 강하게 방사되도록 하였다. ESS 모듈 1단위 및 모듈 3단위 화재진압성능 실험결과 소화약제 방사 후 각각 8 s 및 9 s 만에 눈에 보이는 화염이 모두 소멸되었다. 또한, 소화약제 방사종료 후 600 s 동안 재발화 여부를 확인한 결과 모든 화재진압성능 실험에서 재발화가 일어나지 않고 ESS 화재가 완벽히 진압되는 것을 확인할 수 있었다.

공동구내 분무분포에 관한 연구 (A Study on the Water Spray Distribution in Underground Culvert)

  • 김엽래
    • 한국방재학회 논문집
    • /
    • 제4권3호
    • /
    • pp.83-87
    • /
    • 2004
  • 지하공동구내에는 전력, 통신, 가스 냉 난방배관 등 생활에 필요한 공작물이 수용되어 있다. 미래에 지하 공동구의 사용은 확대되며, 화재의 위험이 증가될 것이므로 미연에 화재에 대비해야 하며, 지하공동구내 최대한의 연소방지효과를 가져오게 할 수 있는 소화시스템의 연구가 필요하다. 본 논문은 지하공동구내 화재를 진압하기 위한 노즐의 분무분포를 해석하고, 이에 따라 지하공동구의 화재안전성능을 확보하고자 한다. 앞으로 화재 및 재해예방을 위해 국내기술로서 국내 환경에 맞은 소화시스템 연구가 지속적으로 이루어져야 할 것이다.

자율형 소화모니터 노즐의 분사 성능에 대한 실험 연구 (Experimental Study on Spray Performance of Nozzles for Autonomous Fire Fighting Monitor)

  • 유성선;김형태;서정화
    • 대한조선학회논문집
    • /
    • 제59권2호
    • /
    • pp.80-88
    • /
    • 2022
  • A systematic experimental study is carried out for the fire fighting monitor nozzle of 65A diameter to design and manufacture a new nozzle with better water spray performance than available domestic nozzles. The nozzle inlet pressure, flow rate and reach for the discharged water from the nozzle are measured by utilizing the experimental facility consisting of two pumps and piping system with a flow meter and pressure gauges. It was found that the baffle position and baffle head chamfering were the most sensitive design factors to be remarkably changed in the flow rate of the discharged water. Also, It was confirmed that the baffle position and the water exit area had the significant effect on the change in reach distance. The results obtained from this study are expected to be used effectively to design new nozzles with excellent spray performances and also to validate numerical analysis results for evaluating the water spray performance of fire fighting monitor nozzles.