• 제목/요약/키워드: 복사냉방 시스템

검색결과 20건 처리시간 0.02초

바닥복사냉방의 결로방지를 위한 제습제어에 관한 연구 (A Study on the Dehumidification Control to Prevent Condensation for Radiant Floor Cooling)

  • 김용이;김광우
    • 설비공학논문집
    • /
    • 제15권2호
    • /
    • pp.137-143
    • /
    • 2003
  • In the forming of an integrated system of radiant floor cooling and dehumidifying, chilled coil can be used for cooling and dehumidification. Therefore, it is necessary to find the efficient control method which can eliminates latent load efficiently. This study has been conducted to find this method by dividing the dehumidification system into 3 types according to the control variables and analyzing characteristics of each system. To prevent the floor surface condensation, the amount of condensation can be manipulated by water temperatures, water flow rates in chilled coil, and air flow rates passing by it. So dehumidification system control can be divided into constant air flow control and variable air flow control. Regarding dehumidification control, variable air flow control, which eliminates latent load rather than sensible load, is preferable to constant flow control.

온돌을 이용한 바닥복사냉방의 제어성능에 관한 실험적 연구 (An Experimental Study on Control Performance of Radiant Floor Cooling Using Ondol)

  • 김용이;임재한;한여명;김광우
    • 설비공학논문집
    • /
    • 제13권11호
    • /
    • pp.1165-1173
    • /
    • 2001
  • The objectives of this study are to analyze the application of radiant floor cooling and to evaluate the control methods through experiments when the radiant heating system is used for cooling. Through the experiment analysis the control methods such as on/off control, variable flow control and outdoor reset with indoor temperature feedback control are evaluated and compared. The cooling curve (reset ratio) is found for radiant cooling, which shows tole relation between outside air temperature and supply water temperature. Comparison of cooling methods shows that outdoor reset with indoor temperature feedback control is more appropriate than on/off control and variable flow control with regard to prevention of the condensation and thermal comfort.

  • PDF

주거 건물의 복사냉방시스템 적용에 관한 연구 (A Study on the Application of the Radiant Floor Cooling System in Residential Building)

  • 임재한;여명석;김광우
    • 한국주거학회논문집
    • /
    • 제15권3호
    • /
    • pp.73-82
    • /
    • 2004
  • The objective of this study is to demonstrate the potential of radiant cooling systems using Ondol as an alternative cooling system in residential buildings. For this purpose, computer simulation and model experiments have been performed for the system performance analysis regarding comfort, floor surface condensation, and supply water temperature. The results of this study is the following: In radiant floor cooling system, room air temperatures were maintained within the set temperature range of $\pm$1$^{\circ}C$ without any discomfort condition. And taking into account only the condensation occurrence, it was possible to achieve radiant floor cooling for a period of about 77% of the total cooling period in weather condition of Seoul. The minimum supply water temperature is about 15$^{\circ}C$, so renewable energy system such as ground heat exchange system can be used as an alternative in cooling source. Also, floor surface condensation can be prevented by integrating with the dehumidification system.

사무소건물의 에너지절약형 냉방시스템 성능분석에 관한 연구 (A Study on the Perfomance Analysis of Low Energy Cooling Systems in Office building)

  • 박창봉;이언구
    • 한국태양에너지학회 논문집
    • /
    • 제30권6호
    • /
    • pp.89-94
    • /
    • 2010
  • A large portion of the energy cost of a building is cooling and heating to maintain a comfortable indoor environment. Air conditioning is now one of the important parts in the building design, as increase in energy consumption and pollutant emission in energy conversion process. In this study, elements that affects the energy consumption of model building are identified and the perfomance analysis of the alternative a Low Energy Cooling Systems considering characteristics of model building and energy saving performance is analyzed. In this study, elements that affect the energy consumption of office building are identified and energy saving performance of the alternative air conditioning system is analyzed. As a result, applied to earn and suggest basic data for energy saving measures. In this study, EnergyPlus simulation program was used to evaluate the energy load when alternative Low Energy Cooling Systems are applied to the model building. The reliability of simulation program is verified by comparing actual energy load from operation data of building management office and predicted energy load using simulation program. For Low Energy Cooling System application which considers the purpose and characteristics of the building, reasonable and energy-saving air conditioning method obtained by analyzing energy consumption elements for each expected air conditioning methods is used to deduct result of this study.

센서를 이용한 자동 실내 온도 제어시스템 설계 및 구현 (Design and Implementation of Automatic Control System in Room using Sensor)

  • 정규태;이은진;김흥수
    • 한국정보통신학회:학술대회논문집
    • /
    • 한국정보통신학회 2015년도 춘계학술대회
    • /
    • pp.326-328
    • /
    • 2015
  • 건물에서 창문의 기능은 태양 복사열의 유입을 통해 실내의 환경을 조성하고 동절기에는 난방비의 절감을 유도할 수 있으나, 다른 구조체에 비해 단열 성능이 크게 떨어져 5배 이상의 에너지가 손실되어 에너지 취약 부위이다. 또한 하절기에는 태양 복사열 과다로 냉방비가 가중된다. 이에 본 논문에서는 일반 가정에서 온도, 습도, 조도, 일사량 등의 실내 환경 정보를 이용하여 창문 자동 제어시스템을 개발하고자 한다. 이 시스템은 다양한 센서를 이용하여 실내 환경 정보를 수집하고 수집된 정보를 이용하여 모터를 제어하여 창문을 제어 할 수 있는 시스템이다. 가정 내 에너지 절감을 위하여 창호와 블라인드에 환경 자동화 서비스를 제공하여 사용자의 만족도를 높이고 스마트폰을 이용하여 시스템 제어를 통해 생활 속에 편리함을 제공하고자 한다.

  • PDF

Mock-up실험에 의한 바닥복사 냉방시스템의 온도특성에 관한 연구 (A Study on the Temperature Characteristics of the Floor Cooling System of Mock-up Experimentent)

  • 유호천;이영아
    • 한국태양에너지학회 논문집
    • /
    • 제28권6호
    • /
    • pp.48-57
    • /
    • 2008
  • The research analyzed the distribution of the indoor temperatures of a radiant floor cooling system through mock-up experiments. It investigated the temperature difference of feed water, the vertical temperature difference of indoor air, the temperature difference of floor surface, and so on. The following is the results of the research. First, the research shows that the difference between indoor temperature and outside temperature was the smallest when the temperature of feed water was set at 16$^{\circ}C$. In addition, the temperature changes according to indoor positions (wall, room, floor, and ceiling) were the most uniform. Thus, the research found that the cold water temperature of 16$^{\circ}C$ is the most proper. In addition, it confirmed that the feed water temperature of 18$^{\circ}C$ is effective because the temperature can lower the temperature of a room to 13.55$^{\circ}C$, which is lower than the temperature of a non-cooling mode. Second, an investigation on the temperature distribution of vertical air in indoor space shows that the temperature distribution had a difference of 0.2 to 1.9$^{\circ}C$ on the average, which satisfies the range of 3.0$^{\circ}C$ in the standard of ISO.

온실의 환기 및 냉방 설계를 위한 열평형 모델의 작용 (Application of Heat Balance Model Design of Ventilating and Cooling Greenhouse)

  • 남상운
    • 생물환경조절학회지
    • /
    • 제9권4호
    • /
    • pp.201-206
    • /
    • 2000
  • 여름철 고온기에 시설 이용율을 높이고 안정적인 생산을 하기 위해서는 고온 극복 시스템의 도입이 필요하며, 이러한 시스템을 도입하기 위하여는 적정 설비용량의 중요하다. 온실의 고온극복방법을 차광환기시스템, 차광환기 패드시스템, 차광환기 포그시스템으로 설정하고, 각 방법별로 시스템의 설계제원 결정을 위한 열평형식을 구성하였으며 현장 실험을 통하여 적용성을 검토하였다. 환기창 단면 풍속을 1분 간격으로 측정하여 유량으로 환산한 값을 환기량의 실측치로 하고 열평형식을 이용하여 계산한 환기량과 비교한 결과 비교적 잘 일치하는 것으로 나타났다. 열평형 모델의 입력변소중 피복재의 열관류이 1% 증가하면 필요환기량은 0.3% 감소하였고, 태양복사에 대한 증발산비(E)의 값이 1% 증가하면 필요환기량은 1.3%나 감소하는 것으로 나타났다. 따라서, E 값의 선택이 매우 중요하며 온실의 환기 및 냉방 설계기준을 설정하기 위해서는 여러 가지 작물의 상태에 따른 E값의 변화를 실측한 자료의 축적을 통해 가이드라인이 제시되어야 할 것으로 판단된다. 온실의 환기 및 냉방 설비 용량 결정을 위한 열평형 모델의 적용성을 검토하기 위하여 6가지의 동일한 조건에 대하여 시뮬레이션한 결과, 필요 공기교환율은 5.1∼7.7%정도, 증발수량은 6.8∼9.3%정도 fan and pad 시스템이 포그시스템에 비하여 큰 것으로 나타났다.

  • PDF

Thermo-Diode식 태양열 이용 모듈(Smart Module)개발 (Development of Energy Efficient Smart Module with Variable Direction of Heat Flow, Heat Capacity and Surface Absorptivity)

  • 이경진;천원기
    • 태양에너지
    • /
    • 제18권3호
    • /
    • pp.119-128
    • /
    • 1998
  • 본 연구에서는 열흐름의 방향, 태양 복사열의 집열 그리고 축열부의 열용량 등이 조절 가능한 Thermo-Diode식 태양열 이용 모듈(Smart Module)의 개발하였으며, 이를 통하여 액체식 열다이오드에 대한 작동 메카니즘과 이를 적용한 태양열 이용 시스템의 효율적 작동과 그 가능성을 확인하였다. 기존의 태양열 시스템은 일조시간 동안만 시스템이 운용되는 반면 본 Smart Module은 낮뿐만 아니라 밤에도 단열 및 냉방부하 감소 효과를 거둘 수 있다.

  • PDF

강판 마감형 조립식 벽패널 복사냉난방시스템의 냉난방 방열 특성 평가 (Evaluation of Heating and Cooling Thermal Output Characteristics of Prefabricated Steel Wall Panel System for Radiant Heating and Cooling)

  • 임재한;구보경;김성임;송승영
    • 한국태양에너지학회 논문집
    • /
    • 제33권2호
    • /
    • pp.70-77
    • /
    • 2013
  • Recently the radiant panel heating and cooling system has been regarded as an alternative of low temperature heating and high temperature cooling by applying the renewable energy sources to the heating and cooling of buildings. Especially this system can be used as HVAC system alternatives in super high-rise buildings for energy saving and thermal comfort. Also it can be possible to reduce the plenum space because the minimum ventilation air will be supplied into the space. This study focused on the evaluation the basic characteristics of thermal output in prefabricated steel wall panel system for radiant heating and cooling. In order to evaluate the thermal output according to both various supply water temperatures and supply water flow rates, three-dimensional dynamic heat transfer analysis was performed. As results, for the heating mode, thermal output increased by 26% with the supply temperature increasing by $5^{\circ}C$. The surface temperature of panels range within $1{\sim}3^{\circ}C$. For the cooling mode, thermal output decreased by 18.2% with the supply temperature increasing by $2^{\circ}C$. The surface temperature of panels range within $0.5{\sim}1^{\circ}C$ and it was shown the even temperature distribution.

태양열 이용 냉난방 공조시스템중 평판형 집열기의 동계 상부 열손실 해석 (Analysis of the Top Loss Coefficient for Flat Plate Collector in a Solar Air-Conditioning System during Winter)

  • 김보철;최광환;금종수;김종렬
    • 태양에너지
    • /
    • 제18권3호
    • /
    • pp.15-24
    • /
    • 1998
  • 태양열 집열기의 열손실은 크게 3가지 즉 상부 열손실, 하부 열손실, 측부 열손실로 대별되나 단열이 양호한 집열기에서는 일반적으로 측면으로의 열손실은 무시한다. 측부 열손실을 제외한 두 열손실 중에서도 상부 열손실은 집열기의 대부분의 열손실을 차지하는 지배적인 요소이다. 따라서 태양열 집열기의 집열 성능을 정확하게 파악하기 위해서는 상부 열손실 계수를 정확하게 계산할 필요가 있다. 본 연구에서 사용한 평판형 태양열 집열기(재생기)는 하계에는 제습 및 냉방을 행하고 동계에는 난방을 행하는 전천후 집열판으로 제작되었다. 따라서 장치의 전환없이 겨울에 난방용으로 사용하였을 경우의 집열 성능을 파악하기 위하여 옥외에서 실험을 하였다. 동계 기간 실험을 통하여 본 집열기의 상부 열손실 계수는 약 $3{\sim}4.5W/m^2^{\circ}C$임을 알 수 있었다. 그리고 집열표면에 선택흡수막을 입혀서 난방용으로 사용하면 주위와의 복사 열손실을 크게 줄일 수 있기 때문에 본 집열기의 집열 성능을 향상시킬 수 있을 것으로 사료된다.

  • PDF