A Study on the Temperature Characteristics of the Floor Cooling System of Mock-up Experimentent  

Yoo, Ho-Chun (School of Architecture, University of Ulsan)
Lee, Young-A (School of Architecture, Graduate School, University of Ulsan)
Publication Information
Journal of the Korean Solar Energy Society / v.28, no.6, 2008 , pp. 48-57 More about this Journal
Abstract
The research analyzed the distribution of the indoor temperatures of a radiant floor cooling system through mock-up experiments. It investigated the temperature difference of feed water, the vertical temperature difference of indoor air, the temperature difference of floor surface, and so on. The following is the results of the research. First, the research shows that the difference between indoor temperature and outside temperature was the smallest when the temperature of feed water was set at 16$^{\circ}C$. In addition, the temperature changes according to indoor positions (wall, room, floor, and ceiling) were the most uniform. Thus, the research found that the cold water temperature of 16$^{\circ}C$ is the most proper. In addition, it confirmed that the feed water temperature of 18$^{\circ}C$ is effective because the temperature can lower the temperature of a room to 13.55$^{\circ}C$, which is lower than the temperature of a non-cooling mode. Second, an investigation on the temperature distribution of vertical air in indoor space shows that the temperature distribution had a difference of 0.2 to 1.9$^{\circ}C$ on the average, which satisfies the range of 3.0$^{\circ}C$ in the standard of ISO.
Keywords
Floor cooling system; Thermal Performance; Artificial Wood; Insulation Materials;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 유호천 외 건축환경계획 태림문화사, 2006
2 조영흠, 공동주택에서 바닥복사냉방의 적정 운영방안에 관한 연구, 설비공학논문집 제16권 제6호, 2004. 6, pp.574-583
3 이승언, 강재식, 정영선, 최현중, 환경 및 시간경과에 따른 건축용 단열재의 열전도율 변화에 관한 실험적 연구, 대한건축학회논문집 제19권 제2호, 2003. 12.
4 J. Miriel et. al., Radiant ceiling panel heating-cooling system; experimental and simulated study of the performances, thermal comfort and energy consumptions, Applied Thermal Engineering 22, pp1861-1875, 2002.   DOI   ScienceOn
5 이승복, 원종서, 바닥복사 냉.난방시스템의 유형별 에너지성능 평가, 대한건축학회논문집 제21권 제3호, 2006. 06
6 이상엽, 제습기능이 통합된 바닥복사 냉방시스템의 적용 가능성에 관한 실험적 연구, 설비공학논문집 제14권 제2호, 2002. 2.
7 김난행, 손장열, 건식이중바닥온돌시스템 개발을 위한 실험적 연구, 한국주거학회논문집 제17권 제3호, 2006. 06   과학기술학회마을
8 특허청, 출원번호. 2006-0034425 인조목재의 제조방법.
9 조영흠, 임재한, 석호태, 여명석, 김광우, 공동주택 현장 실험을 통한 바닥복사냉방의 성능평가, 대한건축학회논문집 제20권 11권, 2004. 11.
10 K, Nagano et, al., Experiments on thermal environmental design of ceiling radiant cooling for supine human subjects, Building and Environments 39, pp487-495, 2004
11 유호천 외 건축설비계획 태림문화사, 2005
12 임재한, 주거건물에서 제습시스템이 통합된 바닥 복사냉방이 운영방안 평가, 대한건축학회논문집 제23권 제10호, 2007. 10.