• Title/Summary/Keyword: 구획실

Search Result 67, Processing Time 0.022 seconds

A Study of the Suitability of Combustion Chemistry in the EDC Model for the LES of Backdraft (백드래프트 현상의 LES를 위한 EDC 모델의 연소 화학반응기구 적합성 연구)

  • Myilsamy, Dinesh;Oh, Chang Bo;Han, Yong Shik;Do, Kyu Hyung
    • Fire Science and Engineering
    • /
    • v.31 no.4
    • /
    • pp.35-42
    • /
    • 2017
  • Large Eddy Simulation (LES) was peformed for the backdraft occurred in a compartment filled with high-temperature methane fuel using the Fire Dynamics Simulator (FDS) of version 6. The prediction performance of FDS, adopted the Eddy Dissipation Concept (EDC) combustion model with five different chemical reaction mechanisms, was evaluated. The temporal distributions of temperature, fuel mass fraction, velocity and pressure were discussed with numerical results and the pressure variation in time was compared with that of previous experiment. The FDS adopted the EDC model showed the possibility of LES for the backdraft phenomena. However, the prediction performance of the LES with EDC model strongly depended on the chemical reaction mechanism considered. It is necessary that the suitability of the chemical reaction mechanism should be validated in advance for LES with the FDS v6 to be applied to the simulation of backdraft.

A Study on Fire Features of Double-Skin Facade Structure by Using Fire Simulation (FDS) (화재 시뮬레이션(FDS)을 이용한 이중외피 구조의 화재 특성에 관한 연구)

  • Gu, Seon-Hwan;Kim, Hyun-Ho;Song, Young-Joo
    • Fire Science and Engineering
    • /
    • v.28 no.1
    • /
    • pp.1-11
    • /
    • 2014
  • This study aims to address the fire characteristics of Double-skin facade using the Fire Dynamics Simulator (FDS). To end this, Double-skin facade was classified into the four structures, that is Box, Shaft-box, Corridor, Multistory, through PyroSim program which was based on FDS, and further each structure of fire characteristics were analyzed numerically as well as comparatively in the current study. This study also examined smoke movement, smoke density, smoke detectors, and visibility in order to closely identify the each structure of fire characteristics. The results of the study discovered that the Box structure did not significantly affect smoke which was rising in the other rooms, except for the fire room whereas the Corridor structure had positive effects on Double-skin facade horizontally. In addition, the Shaft-box structure showed the fastest vertical movement by means of the shaft, on the other hand, rising smoke influenced the other rooms as well. The Multistory structure along with rising smoke had a great impact on the other divided rooms in a vertical way.

Effects of Ventilation Condition on the Fire Characteristics in Compartment Fires (Part II: Multi-dimensional Fire Dynamics) (구획화재에서 환기조건의 변화가 화재특성에 미치는 영향 (Part II: 다차원 화재거동))

  • Kim, Jong-Hyun;Ko, Gwon-Hyun;Park, Chung-Hwa;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.24 no.5
    • /
    • pp.32-38
    • /
    • 2010
  • Multi-dimensional fire dynamics were studied numerically with the change in ventilation conditions in a full-scale ISO 9705 room. Fire Dynamic Simulator (FDS) was used for the identical conditions conducted in previous experiments. Flow rate and doorway width were changed to create over-ventilated fire (OVF) and under-ventilated fire (UVF). From the numerical simulation, it was found that the internal flow pattern rotated in the opposite direction for the UVF relative to the OVF so that a portion of products recirculated to the inside of compartment. Significant change in flow pattern with ventilation conditions may affect changes in the complex process of CO and soot formation inside the compartment due to increase in the residence time of high-temperature products. The fire behavior in the UVF created complex 3D characteristics of species distribution as well as thermal and flow structures. In particular, additional burning near the side wall inside the compartment significantly affected the flow pattern and CO production. The distribution of CO inside the compartment was explained with 3D $O_2$ distribution and flow patterns. It was observed that gas sampling at local positions in the upper layer were insufficient to completely characterize the internal structure of the compartment fire.

초고층건물에서 발생되는 굴뚝효과 방지대책

  • 권용일;박명식
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.33 no.12
    • /
    • pp.32-38
    • /
    • 2004
  • 초고층건물의 건설이 증가되고 있지만 건물외파와 출입문의 기밀도가 낮게 유지될 때, 이러한 누설면적과 층별로 구획할 수없는 수직샤프트(계단실 등)와 직렬로 배치될 경우, 필연적으로 발생하게 되는 굴뚝 현상(stack effect)의 발생원인과 차압크기 산정하는 방법 및 예방대책을 소개하고자 한다.

  • PDF

The Real Fire Test in Bedroom for the Performance Based Fire Design (성능기반 화재안전설계를 위한 침실 공간에서의 실화재 실험)

  • Kim, Hyung-Jun;Kwon, In-Kyu;Kweon, Oh-Sang;Kim, Heung-Youl;Chae, Seung-Un
    • Fire Science and Engineering
    • /
    • v.27 no.6
    • /
    • pp.32-37
    • /
    • 2013
  • For The performance based fire design of the buildings, the fire characteristic such as proceeding and scale of the fire should be figured out but, there is lack of relevant information because of different conditions and difficulties of mock-up test like type of division space, ventilation condition, etc, in buildings. Therefore, in the study, a heal release rate etc, the engineering characteristic data value on the fire is proposed by mock-up fire test for division space in buildings. The mock-up fire test is carried out in a bedroom with 2.4 (L) ${\times}$ 3.6 (W) ${\times}$ 2.4 (H) m model. Initial ignition was started from trash box and the test was carried out for 30 min. As a result of the fire test, flame was broken to outside within 7 min and 50 s after starting the test and the maximum heat release rate was measured as 3,810.6 kW at 9 min and 34 s.

Performance Evaluation of FDS for Predicting the Unsteady Fire Characteristics in a Semi-Closed ISO 9705 Room (반밀폐된 ISO 9705 화재실에서 비정상 화재특성 예측을 위한 FDS의 성능평가)

  • Mun, Sun-Yeo;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.26 no.3
    • /
    • pp.21-28
    • /
    • 2012
  • The objective of this study is to evaluate the prediction accuracy of FDS(Fire Dynamic Simulator) for the thermal and chemical characteristics of under-ventilated fire with unsteady fire growth in a semi-closed compartment. To this end, a standard doorway width of the full-scale ISO 9705 room was modified to 0.1 m and the flow rate of heptane fuel was increased linearly with time (until maximum 2.0 MW based on ideal heat release rate) using a spray nozzle located at the center of enclosure. To verify the capability of FDS, the predicted results were compared with a previous experimental data under the identical fire conditions. It was observed that with an appropriate grid system, the numerically predicted temperature and heat flux inside the compartment showed reasonable agreement with the experimental data. On the other hand, there were considerable limitations to predict accurately the unsteady behaviors of CO and $CO_2$ concentration under the condition of continuous fire growth. These results leaded to a discrepancy between the present evaluation of FDS and the previous evaluation conducted for steady-state under-ventilated fires. It was important to note that the prediction of transient CO production characteristics using FDS was approached carefully for the under-ventilated fire in a semi-closed compartment.

A Study on Fire Risk Assessment of a EPS room using Fire Simulation (시뮬레이션 분석을 통한 EPS실 화재위험성 평가에 관한 연구)

  • Ham, Eungu;Kim, Dongcheol;Lee, Changwoo
    • Journal of the Society of Disaster Information
    • /
    • v.11 no.4
    • /
    • pp.581-588
    • /
    • 2015
  • This study was conducted by utilizing simulation (FDS6) the fire characteristics of the flammable substances such as cable compartment of a small space in the EPS room type. In the partitioned space of a room EPS supply of oxygen does not facilitate the combustion of the upward-sloping curve, as in a standard fire curve is not observed. Simulation results in a situation where ventilation is limited to the heat release rate and smoke emission characteristics of the fire showed a complex and unstable form a repeating rise and fall. Fire time was longer than the fire load. Change in the smoke emission than the heat release rate is slow, but changes of the overall surface was found to exhibit affinity.

Things To Be Considered for a New Conservation Laboratory (보존처리실 신설시 고려 사항)

  • Ahn, Byongchan
    • Journal of Conservation Science
    • /
    • v.11 no.1 s.14
    • /
    • pp.52-57
    • /
    • 2002
  • Although a conservation laboratory is a kind of hospital for cultural assets, it is often planned on the standard of ordinary offices. In this study, things and conditions to be considered for a new conservation laboratory were discussed and suggested briefly, for the sections of architecture, electricity and lightning, air condition, fire protection, machinery and tools. As methods of creating a workspace adequate to conservation work, the method of dividing workspace on the basis of workstand and the method of placing machinery and tools on the basis of water supply and sewage systems were explained., Because a conservation laboratory varies in its duties and functions, it seems difficult that all the standards and conditions suggested in this study be fulfilled in every case. But understanding general standards and conditions and choosing ones adequate to special functions of each laboratory will be helpful to planning a new conservation laboratory.

  • PDF

Effect of the Characteristic Length Scale on the Grid Dependency of FDS model (특성길이에 따른 FDS 모델의 격자 의존성)

  • Kim, Sung-Chan
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2012.04a
    • /
    • pp.66-69
    • /
    • 2012
  • Field Model에 의한 화재해석방법은 화재현상을 지배하는 망정식윤 직접 해석하기 때문에 Zone model에 비해 공간내의 상세 정보를 제공함과 동시에 다양한 화재형태에 내해 보편적인 적용이 가능하다. Field model은 해석영역을 구성하는 격자점에 대해 이산화된 지배 방정식을 해석하는 과정에서 차분방법이나 격자의 크기에 따라 수치오류가 발생할 수 있다. 특히 격자수는 계산시간에 영향을 미치는 가장 중요한 인자이기 때문에 효율적인 계산을 위해서는 격자크기의 최적화가 이루어져야 한다. 본 연구에서는 구획공간 화재의 최적 격자크기 선정을 위해 격자해상도(Grid Resolution)에 따른 해석결과의 독립성을 비교분석하고 이를 통해 구획공간화재에 대한 격자 최적화 방법에 대해 논의하고자 한다. 화재크기 및 특성 길이에 따른 격자의존성을 파악하기 위해 ISO-9705 표준화재실에 내해 적용된 격자크기는 최소 3 cm에서 최대 30 cm까지 총 7 종류의 격자크기에 대해 FDS 해석이 수행되었다. 해석결과, 환기량이 충분한 화재에 대해서도 격자해상도가 16보다 작은 경우 출입구의 유동은 격자에 따른 독립성을 확보하지 못하는 것으로 나타났으며 화재발열량이 증가함에 따라 독립적인 해석해를 얻기 위해서는 더 큰 격자해상도를 요구하는 것으로 나타났다. 따라서 현재 실무에서 격자최적화를 위해 사용되고 있는 격자선정법에 대한 재검토가 필요하며 화재특성 및 구획공간 조건에 따른 최적격자 조건을 도출하기 위한 추가적인 연구가 필요하다.

  • PDF

Characteristics of Heat Flux in a Compartment Fire - Reduced Scale Test (구획공간 화재의 열유속 특성 - 축소 실험)

  • Kim, Sung-Chan;Ko, Gwon-Hyun
    • Fire Science and Engineering
    • /
    • v.25 no.5
    • /
    • pp.128-133
    • /
    • 2011
  • The present study performs a series of 40 % reduced scale of ISO-9705 fire test to investigate the characteristics of heat flux on the floor level in terms of fire characteristics and location in the compartment. The heat flux was measured with Schmidt-Boelter type heat flux gauge at two locations on the floor level of inside and doorway side of the compartment. Different types of fuel - methane, heptane, toluene, ethanol, polystyrene - were burned in this test series. The measured heat flux inside of the compartment was relatively higher than that of front side as the heat release rate of fire and upper layer temperature increased. The difference of measured heat flux at inside and doorway side increased for high sooty fire. The present study shows that the heat flux distribution at lower layer greatly depend on the thermal radiation from fire and upper layer, not only the upper layer temperature but also various fire characteristics such as composition of combustion gases, soot concentration, ventilation condition and so on.