Browse > Article
http://dx.doi.org/10.7731/KIFSE.2013.27.6.032

The Real Fire Test in Bedroom for the Performance Based Fire Design  

Kim, Hyung-Jun (Department of Architectural Engineering, University of Seoul)
Kwon, In-Kyu (Department of Fire Protection Engineering, Kangwon National University)
Kweon, Oh-Sang (Fire Safety Research Center, KICT)
Kim, Heung-Youl (Fire Safety Research Center, KICT)
Chae, Seung-Un (Fire Safety Research Center, KICT)
Publication Information
Fire Science and Engineering / v.27, no.6, 2013 , pp. 32-37 More about this Journal
Abstract
For The performance based fire design of the buildings, the fire characteristic such as proceeding and scale of the fire should be figured out but, there is lack of relevant information because of different conditions and difficulties of mock-up test like type of division space, ventilation condition, etc, in buildings. Therefore, in the study, a heal release rate etc, the engineering characteristic data value on the fire is proposed by mock-up fire test for division space in buildings. The mock-up fire test is carried out in a bedroom with 2.4 (L) ${\times}$ 3.6 (W) ${\times}$ 2.4 (H) m model. Initial ignition was started from trash box and the test was carried out for 30 min. As a result of the fire test, flame was broken to outside within 7 min and 50 s after starting the test and the maximum heat release rate was measured as 3,810.6 kW at 9 min and 34 s.
Keywords
Performance based design; Fire test; Compartment fire; Fire size; Fire Growth;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Y. H. Yoo, E. K. Hwang, D. H. Kim, O. S. Kweon, H. S. Chae and S. B. Jang, "Development of Fire Spread Prevention and Escape Safety Design Technique According to Standard Fire Model", KICT 2008-116, Korea Institute of Construction Technology, pp. 1-2 (2008).
2 K. H. Kim, S. H. Lee, H Y. Kim, T. H. Song and B. K. Jin, "Establishment of Building Fire Safety System-Improvement of Building Fire Safety Regulations", KICT 2000-082, Korea Institute of Construction Technology, pp. 31-37 (2000).
3 Y. H. Yoo, H. J. Park, K. S. Cho, O. S. Kweon and H. Y. Kim, "A Case Study on Evaluation Criteria for Performance Based Design", Proceedings of 2011 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 384-387 (2011).
4 A. H. Buchanan, "Fire Engineering Design Guide", University of Canterbury, pp. 29-36 (2001).
5 J. D. Shin, S. H. Jeong, M. S. Kim and H. J. Kim, "Analysis of Fire Risk with Building Use Type Using Statistical Data", Journal of Korean Society of Hazard Mitigation, Vol. 12, No. 4, pp. 107-114 (2012).   과학기술학회마을   DOI   ScienceOn
6 Korean Agency for Technology and Standards, "Fire Tests-full-scale Room Test for Surface Products", KS F ISO 9705 (2009).
7 Korean Agency for Technology and Standards, "Fire safety-Vocabulary", KS F ISO 13493 (2002).
8 D. H. kim, "A Study on the Establishment of the Fire Load by Building Occupancy", Konkuk University, pp. 108-118 (2003).
9 E. J. Lee, "Design of Large Cone Calorimeter for the Fire Study", Journal of Korean Institute of Fire Science & Engineering, Vol. 20, No. 4, pp. 65-71 (2006).   과학기술학회마을
10 O. S. Kweon, Y. H. Yoo, H. Y. Kim and S. H. Min, "An Experiment Study on Fire Safety Performance of Glass Wool Sandwich Panel", Fire Science and Engineering, Vol. 26, No. 5, pp. 21-27 (2012).
11 Boverket, "Boverkets allmanna rad 2011:xx Vagledning I analytisk dimensionering av byggnaders brandskydd-Remiss", Kalskrona:Boverket (2010).
12 British Standard Institution, "PD 7974-1:2003, Application of fire safety engineering principles to the design of building-part1:Initiation and development of fire within the enclosure of origin", London:BSI (2003).
13 B. Karlsson and J.G. Quintiere, "Enclosure Fire Dynamics", Boca Raton, Florida: CRC Press (2000).