Abstract
This study reviewed the capturing performance of a canopy hood used in some melting processes of a casting manufacturing factory through a site survey. In addition, this study compared and evaluated the flow field and pressure field for the plans to enhance the hazardous air pollutants collection capacity by using CFD model. The case-2(flange attached + double hood) can be improved in terms of collection performance, but is expected to increase in hood static pressure by about 70% more than the existing structure, so it was shown that its site applicability is not good. It is judged that the shape of case-3(flange attached + double cone attached) is most suitable to improve the suction efficiency. This is because a double cone is installed at the center of the opening to concentrate the flow rate on the edge of the hood and control the hume rising to the center of the hood without a static pressure rise via the slope of the cone.
본 연구에서는 현장조사를 통해 주물 제조 사업장의 일부 용해공정에 적용되고 있는 캐노피 후드(canopy hood)의 흡인 성능을 검토하였다. 또한, CFD model을 이용하여 유해대기오염물질 포집 능력을 향상시킬 수 있는 방안들을 대한 유동장 및 압력장을 비교 및 평가하였다. Case-2(플랜지 부착+이중 후드)의 경우 포집 성능 측면에서는 개선이 가능하지만 후드 정압이 기존 구조보다 약 70% 이상 증가할 것으로 예측되어 현장 적용성이 좋지 않을 것으로 나타났다. 흡인효율을 개선하기 위해서는 case-3(플랜지 부착+이중 콘 부착)의 형상이 가장 적합할 것으로 판단된다. 이는 개구부 중앙에 이중 콘(cone)이 설치되어 후드 가장자리로 유량을 집중시킬 수 있으며, 또한 후드 중앙으로 상승되는 흄(hume)은 콘의 기울기에 의해 정압 상승의 요인 없이 제어할 수 있기 때문이다.