Proceedings of the Korean Society for Noise and Vibration Engineering Conference (한국소음진동공학회:학술대회논문집)
- 2007.11a
- /
- Pages.6-11
- /
- 2007
- /
- 1598-2548(pISSN)
Environmental Noise Prediction and Countermeasures for Packaged Power Station
육상용 디젤엔진 발전플랜트의 환경소음 영향 평가 및 저감 대책
Abstract
Packaged power station (PPS) is a stationary diesel engine generator set and developed for the supply of electric power to small villages, islands and factories etc. Therefore, the PPS is closely installed to residence area and sometimes cause the environmental noise problems. In this paper, environmental noise analysis was performed for the power plant with 28 sets of PPS. The initial analysis results showed the some difference between the measurement and analysis because of the inaccurate noise source data. To improve the accuracy of analysis, main noise sources were inversely estimated using the in-situ measurement data in the vicinity of PPS and steam boiler. As the results of re-analysis, the good agreement was obtained and it was concluded that the noise levels exceed the specified noise limit in residence area. In order to reduce the noise, the several methods such as geometry alteration of inlet duct, application of hybrid-type silencer and noise protection barrier were suggested and verified with the confirmed analysis model.
Keywords