Proceedings of the Korean Society for Noise and Vibration Engineering Conference (한국소음진동공학회:학술대회논문집)
- 2006.11a
- /
- Pages.258-261
- /
- 2006
- /
- 1598-2548(pISSN)
An Experimental Study on the Control of Duration time of Impulse Noise from a High Voltage COS Fuse
고전압 COS 퓨즈로부터 방사된 충격성 소음의 지속시간 제어에 관한 실험적 연구
Abstract
This study introduces the control of duration time of impulse noises emitted from a high voltage COS fuse of a transformer. When a high voltage COS fuse becomes a short circuit by the over current, the peak sound pressure level over 150 dB(A) is generated at the distance of 2m from a COS Fuse. For the purpose of the reduction of impulse noise, in this study, the reactive type silencer has been utilized. And also electrical interrupting test was experimented. From the experimental results, the reactive type silencer has been shown to have the noise reduction of about 13 dB(A). It has been found that the electrical interception performance of the COS fuse was related to the control of the duration time of impulse noise.
Keywords