• 제목/요약/키워드: synthetic breaking test

검색결과 10건 처리시간 0.025초

Re-ignition System using Vacuum Triggered Gap-switch for Synthetic Breaking Test

  • Park Seung-Jae;Suh Yoon-Taek;Kim Dae-Won;Kim Maeng-Hyun;Song Won-Pyo;Koh Hee-Seog
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제5C권4호
    • /
    • pp.145-151
    • /
    • 2005
  • The synthetic breaking test method was developed to evaluate the breaking performance of ultra high-voltage circuit breaker and made up of two independent circuits; current source circuit and voltage source circuit. In application of this test method, it is necessary to extend the arc of the test breaker. So, the new re-ignition system using VTGS (Vacuum Triggered Gap-Switch) was constructed to improve the efficiency and reliability of this test. In this re-ignition system, VTGS operates in high vacuum state of $5{\time}10^{17}$torr and control system consists of the triggering device and the air M-G (Motor-Generator). This re-ignition system showed the operating characteristics, such as delay time ($t_d$) and jitter time ($t_j$ not exceeding 5us and 1us respectively, and had the operating voltage of $25\~150kVdc$ at the gap distance of 24mm.

진공인터럽터용 신규 접점소재에 대한 차단 성능 평가 (Evaluation of Breaking Performance of New Contact Material for the Vacuum Interrupter)

  • 차영광;이일회;주흥진;신태용;박경태
    • 한국전기전자재료학회논문지
    • /
    • 제34권1호
    • /
    • pp.50-55
    • /
    • 2021
  • Copper-chromium alloys have been used as contact materials of vacuum interrupters in circuit breakers, but new materials with highly stable performance are required to break the high voltage and high current barrier due to the recent increase in breaking capacity. In this paper, a new contact material was fabricated from a ternary alloy instead of existing Cu-Cr alloys. Its breaking performance and endurance were verified from a synthetic test and compared with that of various contact materials. The test results verified that the breaking performance of the new contact material was excellent.

Simplified Synthetic Testing Facility with Modified TRV Circuit

  • Chong, Jin-Kyo;Lee, Kyung Seob;Lee, Chang-Hoon;Kim, Gyu-Tak
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권2호
    • /
    • pp.881-885
    • /
    • 2018
  • In order to develop a gas circuit breaker (GCB), the breaking performance of the short line fault (SLF) should be prioritized over that of the breaker terminal fault (BTF). In brief, it is necessary to evaluate the thermal characteristics of the insulating gas that is filled in a GCB. In the process of developing a GCB, many companies use the simplified synthetic testing facility (SSTF).In order to evaluate the SLF breaking performance of a GCB with a long minimum arcing time, a modifications to the conventional SSTF was proposed. In this study, we developed the SSTF with a modified transient recovery voltage circuit. The performance of the newly developed SSTF was verified by an $L_{90}$ breaking performance test on a rating combination of 170 kV, 50 kA, and 60 Hz.

전류영점 영역에서 파퍼식 SF6 가스차단기의 아크 컨덕턴스에 관한 연구 (A Study on Arc Conductance of Puffer Type SF6 GCB at Current Zero Period)

  • 정진교;송기동;이우영;김규탁
    • 전기학회논문지
    • /
    • 제59권2호
    • /
    • pp.328-332
    • /
    • 2010
  • The SLF(Short Line Fault) breaking capability test for high voltage class $SF_6$ GCB(Gas Circuit Breaker) was conducted. Simplified LC resonant circuit test facility was used for SLF breaking test. During test, Test current was measured by Rogwski coil and arc voltage was measured by voltage divider. Arc conductance was calculated by using these test results before 200ns at current zero. Critical arc conductance value at rated voltage 145kV class is about 2.3mS regardless of breaking current magnitude and arc conductance value at rated voltage 170kV class is about 2.6mS.

$SF_6$ 가스차단기의 아크저항에 관한 연구 (A Study On The Arc Resistance of $SF_6$ Gas Circuit Breaker)

  • 정진교;이우영;김규탁
    • 전기학회논문지
    • /
    • 제56권9호
    • /
    • pp.1566-1570
    • /
    • 2007
  • [ $SF_6$ ] gas circuit breakers are widely used for short circuit current interruption in EHV(Extra High Voltage) or UHV(Ultra High Voltage) power systems. To develop $SF_6$ gas circuit breakers, the arc resistance value is necessary to compare experimental results to numerical ones. The arc resistance value can be obtained from a breaking test with a $SF_6$ gas circuit breaker. The direct testing or synthetic testing facility is widely used to verify the breaking ability for $SF_6$ gas circuit breakers. We employed the simplified synthetic testing facility to test a $SF_6$ gas circuit breaker prototype. The arc resistance characteristic was measured and calculated under the various experimental conditions. This arc resistance value can be used for verifying the numerical results from arc simulation in a circuit breakers.

Weil-Dobke 합성단락시험로의 최적화 연구 (A Study on Optimization of the Weil-Dobkes Synthetic Short-Circuit Tests)

  • 김맹현;고희석
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제50권6호
    • /
    • pp.287-292
    • /
    • 2001
  • This paper deals with the configuration, operating principles, systematic calculation method of parameter and optimization method of test circuit for parallel current injection method, series voltage injection method and hybrid synthetic test method as the method for performance test of circuit breaker with extra high interrupting capacity. The test method depicted above is applied to short-circuit making and breaking test (operating sequence :Os CdOs, Od-CdOs) and out-of-phase tests(operating sequence :Os, CdOs) for performance test of the newly-developed 420kV, 50kA and 800kV 50kV puffer-type gas circuit-breaker according to IEC 60056 and IEC 60427. The testing results, evaluation of equivalence for test and analyzed results are also presented in this paper.

  • PDF

362kV, 63kA 초고압차단기 투입차단시험 (Short-circuit making and breaking test for 362kV, 63kA circuit breaker)

  • 박승재;서윤택;윤학동;김맹현;고희석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.554-556
    • /
    • 2004
  • Testing capacity of KERI synthetic short-circuit testing facilities has been upgraded to fulfill the requirements up to 550kV 63kA, 1-break circuit breaker ratings. Specially the current capacity was increased 50kA to 63kA and the full type test of 362kV 63kA circuit breaker(1-break) was firstly completed in domestic. UP to now, domestic manufacturers have depended on the foreign testing laboratory for performance verification of newly designed products. This paper introduces the summary of the increased short-circuit testing facilities, the testing techniques and its results for the making and breaking performance of 362kV, 63kA circuit breaker which was Performed according to IEEE C37.06(1999) used in North America.

  • PDF

800kV, 50kA 차단기의 전절연 검증을 위한 시험방법 검토 (Review about test method for the full-insulation verification of circuit breaker rated on 800kV, 50kA)

  • 박승재;서윤택;윤학동;김용식;김맹현;고희석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.569-571
    • /
    • 2005
  • In case of dead-tank circuit breaker with the earthed enclosure, the dielectric performance for phase to ground should be verified under the hot-gas condition produced by the current interruption. This test condition is required in breaking test duties with the rated short-circuit current and rated voltage. And, KERI has completed the reinforcement of the synthetic testing facilities and these facilities have the testing capacity which enables the full-pole testing for 800kV circuit breaker by adopting the series voltage injection method. So, this paper introduced the test circuit and procedures about the full-pole and the multi-part testing method which was devised to estimate the full -insulation of phase-to-ground for the multi-pole and dead-tank circuit breaker.

  • PDF

아크전압을 고려한 비대칭전류차단 합성시험 해석 (An Analysis Of Asymmetrical Breaking Synthetic Test Considering Arc Voltages of Circuit Breakers)

  • 이용한
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.635-637
    • /
    • 2005
  • 차단기 합성시험은 직접시험과의 등가성을 유지하는 것이 가장 중요한데, 합성시험에서의 전류일 전압은 직접시험에 비해 매우 낮기 때문에 보조차단기 및 피시험 차단기의 아크전압에 의해 마지막 전류루프가 심하게 왜곡될 수 있다. 특히, 비대칭전류차단시험(T100a)에서는 마지막 전류루프의 특성이 차단기 성능평가에 매우 중요한데, 아크전압에 의한 마지막 전류루프의 왜곡이 심하면 합성시험의 등가성이 결여되어 적절치 못한 시험결과를 초래할 수 있다. 따라서 본 논문에서는 아크전압을 고려한 비대칭전류차단 합성시험 특성을 해석함으로써, 적절한 방법에 의해 아크전압에 의한 왜곡을 보상하여 합성시험의 등가성을 유지할 수 있는 기반을 마련하였다.

  • PDF

산업부산물을 활용한 제철·제강용 합성 칼슘 페라이트 특성 - (2) (The Properties of Synthetic Calcium Ferrite for Ironmaking and Steelmaking using Industrial By-products - (2))

  • 박수현;추용식;서성관;박재완
    • 자원리싸이클링
    • /
    • 제23권5호
    • /
    • pp.12-20
    • /
    • 2014
  • 칼슘 페라이트는 소결광 제조 시 생성되는 자용성 소결 광물의 일종으로, 제철 공정의 소결광용 결합제 및 제강용 융제로 사용된다. 기존 소결광용 결합제 및 제강용 융제보다 용융온도가 낮아 결합제 및 융제로서의 효과가 우수하다. 본 연구에서는 제철공정에서 발생하는 다양한 산업부산물을 시작원료로 사용하여 칼슘 페라이트를 제조하였다. 칼슘 페라이트 물성을 분석 평가하기 위해, 시멘트 제조공정 시험법을 준용하였다. 더불어 칼슘 페라이트의 물성을 평가하기 위해 결정분석, 파괴하중, 열분석 등을 시행하였다.