• Title/Summary/Keyword: short circuit fault

Search Result 332, Processing Time 0.029 seconds

An Improved Short Circuit Protection Scheme for IGBT Inverters (IGBT 인버터를 위한 향상된 단락회로 보호기법)

  • 서범석;현동석
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.3 no.4
    • /
    • pp.426-436
    • /
    • 1998
  • Identification of fault current during the operation of a power semiconductor switch and activation of suitable remedial actions are important for reliable operation of power converters. A short circuit is a basic and severe fault situation in a circuit structure such as voltage source converters. This paper presents a new active protection circuit for fast and precise clamping and safe shutdown of fault currents of the IGBTs. This circuit allows operation of the IGBTs with a higher on-state gate voltage, which can thereby reduce the conduction loss in the device without compromising the short circuit protection characteristics. The operation of the circuit is studied under various conditions, considering variation of temperature, rising rate of fault current, gate voltage value, and protection circuit parameters. An evaluation of the operation of the circuit is made using IGBTs from different to confirm the effectiveness of the protection circuit.

  • PDF

Three-phase Fault Calculation by IEC 60909 (IEC 60909에 의한 삼상 고장계산)

  • Son, Seok-Geum
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.63 no.1
    • /
    • pp.12-18
    • /
    • 2014
  • This paper analyzes how to calculate the three phase short circuit current calculation procedures used in the IEC 60909 short circuit. It presented the new procedure of the fault current for the interrupting capacity of the circuit breaker. This procedure is applied to the future power system and calculates the fault current. Power demands are increased because of the growth of the economy for this reason, the fault current of the power system is largely increased and the fault current procedure for the proper interrupting capacity calculation of the existing or the new circuit breaker is essential. How to calculate the three phase short circuit current for ac electrical system and select the high voltage and low voltage circuit breaker based on IEC 60909 standards.

Detection of Stator Winding Inter-Turn Short Circuit Faults in Permanent Magnet Synchronous Motors and Automatic Classification of Fault Severity via a Pattern Recognition System

  • CIRA, Ferhat;ARKAN, Muslum;GUMUS, Bilal
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.2
    • /
    • pp.416-424
    • /
    • 2016
  • In this study, automatic detection of stator winding inter-turn short circuit fault (SWISCFs) in surface-mounted permanent magnet synchronous motors (SPMSMs) and automatic classification of fault severity via a pattern recognition system (PRS) are presented. In the case of a stator short circuit fault, performance losses become an important issue for SPMSMs. To detect stator winding short circuit faults automatically and to estimate the severity of the fault, an artificial neural network (ANN)-based PRS was used. It was found that the amplitude of the third harmonic of the current was the most distinctive characteristic for detecting the short circuit fault ratio of the SPMSM. To validate the proposed method, both simulation results and experimental results are presented.

Study on Application of Superconducting Fault Current Limiter Considering Risk of Circuit Breaker Short-Circuit Capacity in a Loop Network System

  • Kim, Jin-Seok;Lim, Sung-Hun;Kim, Jae-Chul
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.6
    • /
    • pp.1789-1794
    • /
    • 2014
  • This paper suggests an application method for a superconducting fault current limiter (SFCL) using an evaluation index to estimate the risk regarding the short-circuit capacity of the circuit breaker (CB). Recently, power distribution systems have become more complex to ensure that supply continuously keeps pace with the growth of demand. However, the mesh or loop network power systems suffer from a problem in which the fault current exceeds the short-circuit capacity of the CBs when a fault occurs. Most case studies on the application of the SFCL have focused on its development and performance in limiting fault current. In this study, an analysis of the application method of an SFCL considering the risk of the CB's short-circuit capacitor was carried out in situations when a fault occurs in a loop network power system, where each line connected with the fault point carries a different current that is above or below the short-circuit capacitor of the CB. A loop network power system using PSCAD/EMTDC was modeled to investigate the risk ratio of the CB and the effect of the SFCL on the reduction of fault current through various case studies. Through the risk evaluations of the simulation results, the estimation of the risk ratio is adequate to apply the SFCL and demonstrate the fault current limiting effect.

Design of Gate Driver Chip for Ionizer Modules with Fault Detection Function (Fault Detection 기능을 갖는 이오나이저 모듈용 게이트 구동 칩 설계)

  • Jin, Hongzhou;Ha, PanBong;Kim, YoungHee
    • Journal of IKEEE
    • /
    • v.24 no.1
    • /
    • pp.132-139
    • /
    • 2020
  • The ionizer module used in this air cleaner supplies high voltages of 3.5KV / -4KV to the discharge electrode HV+ / HV- using a winding transformer to generate positive and negative ions by electric field radiation of carbon fiber brush. The ionizer module circuit using the existing MCU has the disadvantage of large PCB size and expensive price, and the gate driver chip using the existing ring oscillator has oscillation period sensitive to PVT (Process-Voltage-Temperature) fluctuation and there is risk of fire or electric shock because there is no fault detection function by short circuit of HV+ and GND as well as HV- and GND. Therefore, in this paper, even though PVT fluctuates, by using 7-bit binary up counter, HV+ voltage reaches the target voltage by adjusting oscillation period. And an HV+ short fault detection circuit for detecting a short circuit between HV+ and GND, an HV- short fault detection circuit for detecting a short circuit between HV- and GND, and an OVP (Over-Voltage Protection) for detecting that HV+ rises above an overvoltage are newly proposed.

A Study on the Possibility of Electrical Fires due to the Short Circuit and Ground Fault of Power Cable Supported by an Iron Fence (철제펜스로 지지된 동력배선의 단락.지락에 의한 전기화재 발생 개연성 연구)

  • Kim, Jeong-Hun;Park, Byoung-Ki;Song, Jong-Hyeok;Jung, Ki-Chang
    • Journal of the Korean Society of Safety
    • /
    • v.22 no.6
    • /
    • pp.41-45
    • /
    • 2007
  • Short circuit and ground fault account for the primary causes of electrical fires. In this research, real-scale experiments were conducted to assess the possibility of electrical fires due to these causes. The experiment conditions were identical with an actual fire accident, in which the power cable was supported by an iron fence. The purposes of this research are to investigate the short circuit caused by wire cutting, the conductivity of the iron fence depending on its coating conditions, and the ground fault of one wire or two wires in an effort to reconstruct the fire accident. The test results show that, owing to the instant operation of circuit breaker in the moment of short circuit or ground fault, the generated ignition energy is far less than necessary to start an ignition. Therefore it is concluded that electrical fire is highly unlikely if the electric system is protected by a circuit breaker with normal functions.

Load Flow Calculation and Short Circuit Faults Transients in Dispersed Generation Systems

  • Hosseini, Seyed Hossein;Shahnia, Farhad;Tizghadam, Saeed
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2005.06a
    • /
    • pp.800-804
    • /
    • 2005
  • Load flow and short circuit fault transients of a power distribution system with wind turbines as dispersed generation units is presented. Usage of renewable energies such as wind is already a small part of total installed power system in medium and low voltage networks. In this paper, a radial power distribution system with wind turbines is simulated using DIgSILENT PowerFactory software for their influence on load flow and short circuit fault transients. Short fault occurring in dispersed generation systems causes some problems for the system and costumers such as fault level increase or the problems of sudden fluctuations in the current, voltage, power and torque of the double fed induction machine utilized in the wind turbines which have been studied and investigated.

  • PDF

Short-circuit Analysis by the Application of Control Signal of Power Converter to the Inductive Fault Current Limiter

  • Ahn, Min-Cheol;Hyoungku Kang;Bae, Duck-Kweon;Minseok Joo;Park, Dong-Keun;Lee, Sang-Jin;Ko, Tae-Kuk
    • Progress in Superconductivity and Cryogenics
    • /
    • v.6 no.2
    • /
    • pp.25-28
    • /
    • 2004
  • Three-phase inductive superconducting fault current limiter (SFCL) with DC reactor rated on 6.6 $KV_{rms}/200 A_{rms}$ has been developed in Korea. This system consists of one DC reactor, AC/DC power converter, and a three-phase transformer, which is called magnetic core reactor (MCR). This paper deals with the short-circuit analysis of the SFCL. The DC reactor was the HTS solenoid coil whose inductance was 84mH. The power converter was performed as the dual-mode operation for dividing voltage between the rectifying devices. The short-term normal operation (1 see) and short-circuit tests (2∼3 cycles) of this SFCL were performed successfully. In regular short-circuit test, the fault current was limited as 30% of rated short-circuit current at 2 cycles after the fault. The experimental results have a very similar tendency to the simulation results. Using the technique for the fault detection and SCR firing control, the fault current limiting rate of the SFCL was improved. From this research, the parameters for design and manufacture of large-scale SFCL were obtained.

Short-term Run and Short-circuit Test of 6.6㎸/200A DC reactor Type Superconducting Fault Current Limiter (6.6㎸/200A급 DC 리액터헝 초전도한류기의 단시간운전 및 단락시험)

  • 안민철;이승제;강형구;배덕권;윤용수;고태국
    • Proceedings of the Korea Institute of Applied Superconductivity and Cryogenics Conference
    • /
    • 2003.10a
    • /
    • pp.10-13
    • /
    • 2003
  • 6.6㎸rms/200Arms DC reactor type superconducting fault current limiter (SFCL) has been developed. This paper deals with the manufacture and short-circuit test of the SFCL. DC reactor was the HTS solenoid coil whose inductance was 84mH. AC/DC power converter was performed as the dual-mode operation. The short-term run(1 sec) and short-circuit test of this SFCL was performed successfully. The experimental results have a similar tendency to the simulation results. In short-circuit test, at 2 cycles after the fault, fault current limitation rate was about 30%.

  • PDF

A Study on Advanced Fault Locating for Short Fault of a Double Circuit Transmission Line (병행 2회선 송전선로의 선간단락시 고장점 표정의 개선에 관한 연구)

  • Park, Yu-Yeong;Park, Chul-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.30 no.1
    • /
    • pp.28-37
    • /
    • 2016
  • Fault locating is an important element to minimize the damage of power system. The computation error of fault locator may occur by the influence of the DC offset component during phasor extraction. In order to minimize the bad effects of DC offset component, this paper presents an improved fault location algorithm based on a DC offset removal filter for short fault in a double circuit transmission line. We have modeled a 154kV double circuit transmission line by the ATP software to demonstrate the effectiveness of the proposed fault locating algorithm. The line to line short faults were simulated and then collected simulation data was used. It can be seen that the error rate of fault locating estimation by the proposed algorithm decreases than the error rate of fault locating estimation by conventional algorithm.