Browse > Article
http://dx.doi.org/10.5370/JEET.2014.9.6.1789

Study on Application of Superconducting Fault Current Limiter Considering Risk of Circuit Breaker Short-Circuit Capacity in a Loop Network System  

Kim, Jin-Seok (Dept. of Electrical Engineering, Soongsil University)
Lim, Sung-Hun (Dept. of Electrical Engineering, Soongsil University)
Kim, Jae-Chul (Dept. of Electrical Engineering, Soongsil University)
Publication Information
Journal of Electrical Engineering and Technology / v.9, no.6, 2014 , pp. 1789-1794 More about this Journal
Abstract
This paper suggests an application method for a superconducting fault current limiter (SFCL) using an evaluation index to estimate the risk regarding the short-circuit capacity of the circuit breaker (CB). Recently, power distribution systems have become more complex to ensure that supply continuously keeps pace with the growth of demand. However, the mesh or loop network power systems suffer from a problem in which the fault current exceeds the short-circuit capacity of the CBs when a fault occurs. Most case studies on the application of the SFCL have focused on its development and performance in limiting fault current. In this study, an analysis of the application method of an SFCL considering the risk of the CB's short-circuit capacitor was carried out in situations when a fault occurs in a loop network power system, where each line connected with the fault point carries a different current that is above or below the short-circuit capacitor of the CB. A loop network power system using PSCAD/EMTDC was modeled to investigate the risk ratio of the CB and the effect of the SFCL on the reduction of fault current through various case studies. Through the risk evaluations of the simulation results, the estimation of the risk ratio is adequate to apply the SFCL and demonstrate the fault current limiting effect.
Keywords
Superconducting Fault Current Limiter (SFCL); Protective coordination; Protective devices;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 O.-B. Hyun, K.-B. Park, J.-W. Sim, H.-R. Kim, S.-W. Yim, and I.-S. Oh, "Introduction of a Hybrid SFCL in KEPCO grid and local points at issue," IEEE Trans. Appl. Supercond., vol. 19, no. 3, pp. 1946-1949, 2009.   DOI   ScienceOn
2 Y. Jiang, S. Dongyuan, D. Xianzhong, T. Yuejin, and C. Shijie, "Comparison of superconducting fault current limiter in power system," IEEE Power Engineering Society Summer Meeting, vol. 1, pp. 43-47, July 2001.
3 B. Gromoll, G. Ries, W. Schmidt, H.-P. Kramer, P. Kummeth, and H.-W. Neumuller, "Resistive current limiters with YBCO films," IEEE Trans Appl. Supercond., vol. 7, no. 2, pp. 828-831, June 1997.   DOI   ScienceOn
4 W. Paul and M. Chen, "Superconducting control for surge currents," IEEE Spectrum, vol. 35, no. 5, pp. 49-54, May 1998.
5 S.-R. Lee, J. Y. Yoon, and B.-J. Lee, "A study on 154 kV protective relaying systems for HTS power devices application in Korea," Journal of the Korea Institute of Appl. Supercond. And Cryog. vol. 9, no. 4, pp. 28-31, 2007.
6 O. B. Hyun, H. R. Kim, Y. S. Yim, J. Sim, K. B. Park, and I. S. Oh, "Domestic Efforts for SFCL Application and Hybrid SFCL," Progress, Superconductivity, vol. 10, no. 1, pp. 60-67, Oct. 2008.
7 S.-H. Lim, "Fault current limiting characteristics of separated and integrated three-phase flux-lock type SFCLs," J. Electr. Eng. Technol., vol. 2, no. 3, pp. 289-293, September 2007.   과학기술학회마을   DOI   ScienceOn
8 G. -H. Lee, K. B. Park, J. W. Sim, Y. G. Kim, I. S. Oh, O. B. Hyun, and B. W. Lee, "Hybrid superconducting fault current limiter of the first half cycle nonlimiting type," IEEE Trans. Appl. Supercond., vol. 19, no. 3, pp. 1888-1891, June 2009.   DOI   ScienceOn
9 H. -R. Kim, S. W. Yim, S. Y. Oh, and O. B. Hyun, "Recovery in superconducting fault current limiters at low applied voltages," IEEE Trans. Appl. Supercond., vol. 18, no. 2, pp. 656-659, June 2008.   DOI   ScienceOn
10 J.-Y. Park, S.-R. Lee, and J.-Y. Yoon, "Application of Bus-tie HTS-FCL on 154kV buses in the Korean Power System," IEEE T&D Conference and Exhibition, pp. 1-4, 2009.
11 S.-R. Lee, J.-Y. Kim, and J.-Y. Yoon, "A study on the bus-tie application of 154kV HTC-FCL in Korean power system," Trans. Of Korean Institute of Electrical Engineers, vol. 54A, no. 5, pp. 226-223, 2005.   과학기술학회마을
12 J.-S. Kim, S.-H. Lim, and J.-C. Kim, "Comparative analysis on current limiting characteristics of hybrid superconducting fault current limiters (SFCLs) with first half cycle limiting and non-limiting operations," Journal of Electrical Engineering & Technology vol. 7, no. 5, pp. 659-663, 2012.   과학기술학회마을   DOI   ScienceOn
13 J.-S. Kim, J.-F. Moon, S.-H. Lim, and J.-C. Kim, "Study on selection of SFCL's impedance for protective coordination with overcurrent relay in a distribution system," IEEE T&D Conference and Exhibition, pp. 1-4, 2009.
14 J.-S. Kim, S.-H. Lim, and J.-C. Kim, "Study on application method of superconducting fault current limiter for protection coordination of protective devices in a power distribution system," IEEE Trans. Appl. Supercond., vol. 22, no. 3, pp. 5601504, June 2012.   DOI   ScienceOn
15 M. R. Haghifam, A. Ghaderi, and M. Abapour, "Enhancement Circuit Breaker Reliability by Using Fault Current Limiter", Power & Energy Society General Meeting, pp. 1-5, IEEE PES 2009.
16 M. H. Kim, J. F. Moon, S. H. Lim, and J. C. Kim, "Method of recloser-fuse coordination in a power distribution system with superconducting fault current limiter," IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1164-1167, June 2010.   DOI   ScienceOn