• Title/Summary/Keyword: power system protection

Search Result 1,263, Processing Time 0.035 seconds

A Study on Shortcircuit Fault Protection Method Using Rogowski Coil (Rogowski 코일을 이용한 과전류 폴트 차단 기법에 관한 연구)

  • Yoon, Hanjong;Cho, Younghoon
    • Proceedings of the KIPE Conference
    • /
    • 2018.07a
    • /
    • pp.108-110
    • /
    • 2018
  • This paper proposes shortcircuit fault protection method in a synchronous buck converter using the PCB pattern Rogowski coil. The PCB pattern Rogowski coils are embedded in the gate driver to measure the device currents of the top and bottom side. When shortcircuit occurs in the system, the gate signal is blocked by the proposed fault protection method using the device current. The simulation and experimental results show that the proposed fault protection method is verified in the shortcircuit system.

  • PDF

Basic study on the protection of Korean power system applying superconducting devices (초전도 전력기기 적용에 따른 계통보호문제 고찰)

  • Lee, Seung-Ryul;Yoon, Jae-Young;Lee, Byong-Jun
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.625-626
    • /
    • 2007
  • This study is on the protection system of Korean power system applying superconducting power devices. We investigates firstly protection systems of Korean power system and then do a basic study on the impact of relay systems in the power system with superconducting devices. For the more reliable result, we will carry out relay operation tests in the power system applying superconducting facilities using RTDS(Real Time Digital Simulator) in the future.

  • PDF

Design of A Downlink Power Control Scheme in Unequal Error Protection Multi-Code CDMA Mobile Medicine System

  • Lin, Chin-Feng;Lee, Hsin-Wang;Hung, Shih-Ii;Li, Ching-Yi
    • Proceedings of the Korea Society of Information Technology Applications Conference
    • /
    • 2005.11a
    • /
    • pp.335-338
    • /
    • 2005
  • In this paper, we propose a downlink power control scheme to apply in the unequal error protection multi-code CDMA mobile medicine system. The mobile medicine system contains (i) blood pressure and body temperature measurement value, (ii) ECG medical signals measured by the electrocardiogram device, (iii) mobile patient's history, (iv) G.729 audio signal, MPEG-4 CCD sensor video signal, and JPEG2000 medical image. By the help of the multi-code CDMA spread spectrum communication system with downlink power control scheme and unequal error protection strategy, it is possible to transmit mobile medicine media and meet the quality of service. Numerical analysis and simulation results show that the system is a well transmission platform in mobile medicine.

  • PDF

A Study on the Effective Surge Protection Method from Induced Lightning Surgeto Improve Isolate Grounding to Common Grounding (낙뢰 Surge 방호를 위한, 독립접지를 공통접지로 개선하는 효율적인 방법에 대한 연구)

  • Jeon, Hyung-Gu;Woo, Jea-Wook;Suh, Yong-Joon
    • Proceedings of the KSR Conference
    • /
    • 2011.10a
    • /
    • pp.1459-1467
    • /
    • 2011
  • This paper proposes the effective method to improve the protection from induced lightning Surge by making common grounding from individual grounding. Common grounding under equipotential principle is more effective than individual grounding for lightning Surge protection, and so common grounding is indicated as international technical standard under the AC power supply system with neutral line. So, this paper is to propose the effective way of induced lightning Surge protection method for currently installed power supply system which has no neutral grounded line and individual grounding which are weak for lightning Surge protection. This proposal can improve the power supply system as has neutral line, and improve the grounding system to common grounding system. And also this paper proposes to make effective equipotential system with voltage variable shunting devices for lightning Surge protection.

  • PDF

A Study on the Effective Surge Protection Method from Induced Lightning Surge to Improve Isolate Grounding to Common Grounding (낙뢰 Surge 방호를 위한, 독립접지를 공통접지로 개선하는 효율적인 방법에 대한 연구)

  • Woo, Jea-Wook
    • Proceedings of the Korean Institute of Navigation and Port Research Conference
    • /
    • 2013.10a
    • /
    • pp.215-218
    • /
    • 2013
  • This paper proposes the effective method to improve the protection from induced lightning surge by making common grounding from individual grounding. Common grounding under equipotential principle is more effective than individual grounding for lightning surge protection, and so common grounding is indicated as international technical standard under the AC power supply system with neutral line. So, this paper is to propose the effective way of induced lightning surge protection method for currently installed power supply system which has no neutral grounded line and individual grounding which are weak for lightning surge protection. This proposal can improve the power supply system as has neutral line, and improve the grounding system to common grounding system. And also this paper proposes to make effective equipotential system with voltage variable shunting devices for lightning surge protection.

  • PDF

Analysis on Insulation and Protection Characteristics of Grid Connected ESS in Ground/Short-Circuit Fault (지/단락실증시험에서 MW급 계통연계형 ESS 절연/보호시스템 성능 분석에 관한 연구)

  • Kim, Jin-Tae;Lee, Seung-Yong;Park, Sang-Jin;Cha, Han-Ju;Kim, Soo-Yeol
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.6 no.2
    • /
    • pp.119-122
    • /
    • 2020
  • With recent ESS (Energy Storage System) fire accident, the fault protection performance is becoming more important. However, there has never been any experiments with the protection performance on the faults in the ESS system level. In this study, the effect of AC ground fault and IGBT (Insulated Gate Bipolar mode Transistor) short-circuit failure on MW class ESS was performed experimentally for the first time in the world. First of all, the effect of the AC single line ground fault on battery was analyzed. Moreover, the transient voltage was investigated as a function of the battery capacity and the power level. Finally, the breaking capability and insulation performance of ESS were examined under PCS short-circuit fault condition. Through the tests, it was found that ESS protection system safely blocked the faulty current regardless of the faults, whereas the electronic parts such as IGBT and MC (Magnetic Contactor) were broken by the fault current. Also, the electrical breakdown in ESS resulted from the transient voltage during the protection process.

A Study of System Protection with emphasis on Power System Stability (전력계통 안정도를 고려한 계통보호 대책 연구)

  • Jang, B.T.;Lee, S.Y.;Kim, K.H.;Ahn, J.S.;Yang, J.J.;Kang, G.H.;Park, J.K.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.99-101
    • /
    • 2002
  • This paper is to introduce the R&D project called "System Protection with emphasis on Power System Stability". The principal objective of this project is protection aids to system stability. The objects of this project arc as follows. First, drawbacks of classical under frequency load shedding and implementation issues of the rate-of-change of frequency will be described. Secondly, the project discusses the possibilities of voltage instability in power system and how this risk will affect protective relays in real system. Lastly, special protection system is designed to preserve system stability for KEPCO.

  • PDF

Optimization of protection System on the Railway High Voltage power System (철도 고압배전계통의 보호시스템 최적화 방안 연구)

  • 조웅기;창상훈;한성호;김왕곤
    • Proceedings of the KSR Conference
    • /
    • 2002.10b
    • /
    • pp.989-994
    • /
    • 2002
  • In case the fault occurs in railway high voltage power supply network, protective relaying system must selectively detect 1 wire ground fault of grounding or non-grounding system. And this study presents railway high voltage power supply system model using PSCAD/EMTDC Vet 3.08 for circuit analysis and fault studies. In this paper, we propose protection method of non-grounding system of railway high voltage power supply system. The result shows its usefulness.

  • PDF

A Study on SFCL Systems for Future Korean T&D Power System Application Considering Auto Reclosing Actions of Protection System (미래 송배전계통에서의 자동재폐로 동작을 고려한 초전도한류시스템에 관한 연구)

  • Lee Seung Ryul;Kim Jong-Yul;Yoon Jae Young
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.12
    • /
    • pp.580-585
    • /
    • 2005
  • The recovery time of developing SFCL(Superconducting Fault Current Limiter) has an uncertainty. In general, the recovery time is estimated at 1 sec and more, even though the progress of SFCL technology is considered. However, auto reclosing time of circuit breaker is 0.3 or 0.5 sec in Korean power system. It is impossible to apply only one SFCL to power system because the recovery time is over the reclosing time of protection system. This study proposes two new SFCL systems for power system application. The proposed systems consider auto reclosing action for the protection in practical power system and consist of tow parallel SFCLs.

Protection Assessment using Reduced Power System Fault Data

  • Littler, T.B.
    • Journal of Electrical Engineering and Technology
    • /
    • v.2 no.2
    • /
    • pp.172-177
    • /
    • 2007
  • Wavelet transforms provide basis functions for time-frequency analysis and have properties that are particularly useful for the compression of analogue point on wave transient and disturbance power system signals. This paper evaluates the compression properties of the discrete wavelet transform using actual power system data. The results presented in the paper indicate that reduction ratios up to 10:1 with acceptable distortion are achievable. The paper discusses the application of the reduction method for expedient fault analysis and protection assessment.