• Title/Summary/Keyword: lightning arresters

Search Result 84, Processing Time 0.021 seconds

Leakage Current Characteristics of 18kv ZnO Lightning Arresters by Accelerated Aging Test (가속열화시험에 의한 18kV ZnO 피뢰기의 누설 전류 특성 분석)

  • Kim, Ju-Yong;Song, Il-Geun;Kim, Chan-Yeong;Mun, Jae-Deok
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.51 no.2
    • /
    • pp.62-67
    • /
    • 2002
  • This paper provides the results of accelerated aging test of 18kV ZnO lightning arresters to investigate the leakage current characteristics. It was impossible to establish the replacement criterion for field operating lightning arrester because conventional aging test was only focused on the aging of ZnO elements. In general, it is possible to replace the aged arresters before the failure in the field using the leakage current measurement because it must be increased by the aging. But we can not use the method because we don't know the characteristics of the installed lightning arresters. Therefore in this paper we applied operating voltage and accelerating cycle which consists of temperature and humidity to the arresters. Then we measured the variation of total and resistive leakage current and found out the characteristics of the acted lightning arresters.

A Study on Lightning Surges in Underground Distribution Systems

  • Jung Chae-Kyun;Kim Sang-Kuk;Lee Jong-Beom
    • KIEE International Transactions on Power Engineering
    • /
    • v.5A no.2
    • /
    • pp.171-176
    • /
    • 2005
  • The effects of surge arresters for the protection of transmission systems against direct lightning strokes have already been reviewed by many researchers. However, their studies have not encompassed underground cable systems. Therefore, in this paper we investigate the 22.9kV combined distribution systems that have arresters and ground wires. In addition, we analyze the overvoltages on underground distribution cable sections when direct lightning strokes contact the overhead ground wire using EMTP. Finally, we discuss the effect of lightning strokes according to the change of cable length and installation of arresters. This study provides insulation coordination methods for reasonable system design in 22.9kV underground distribution cable systems.

Effective Installations Technique of Grounding Conductors for Metal Oxide Surge Arrestors (배전피뢰기용 접지도선의 효과적인 설치기법)

  • Lee, Bok-Hui;Gang, Seong-Man;Yu, In-Seon
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.51 no.6
    • /
    • pp.253-259
    • /
    • 2002
  • This paper deals with the effects of grounding conductors for metal oxide surge arresters. When surge arresters are improperly installed, the results can cause costly damage of electrical equipments. In particular, the route of surge arrester connection is very important because bends and links of leads increase the impedances to lightning surges and tend to nullify the effectiveness of a grounding conductor. Therefore, there is a need to know how effective installation of lightning surge arresters is made in order to control voltage and to absorb energy at high lightning currents. The effectiveness of a grounding conductor and 18 [㎸] metal oxide distribution line arresters was experimentally investigated under the lightning and oscillatory impulse voltages. Thus, the results are as follows; (1) The induced voltage of a grounding conductor is drastically not affected by length of a connecting line, but it is very sensitive to types of grounding conductor. (2) The coaxial cable having a low characteristic impedance is suitable as a grounding conductor. (3) It is also clear from these results that bonding the metal raceway enclosing the grounding conductor to the grounding electrode is very effective because of skin effect. (4) The induced voltages of grounding conductors for the oscillatory impulse voltages are approximately twice as large as those for the lightning impulse voltages.

Insulation Design of Distribution Systems in Case of the Stroke of Direct Lightning Surge (직격뢰 침입시 배전계통 절연설계)

  • 정채균;김상국;이종범;서재호
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.4
    • /
    • pp.238-247
    • /
    • 2004
  • This paper describes the insulation coordination scheme of line in distribution system when the direct lightning surge strikes. The BIL that is applied to distribution system is not properly considered the performance and operation of arresters. Because of that, the high BIL is being used at partial system. This paper variously analyses the lightning overvoltage of line and equipment with earth of overhead grounding wire and installation types of arrester. From these result. authors examine the rationality of BIL.

Degradation Properties of ZnO Surge Arresters Due to Lightning Impulse Currents (뇌임펄스전류에 의한 ZnO 피뢰기의 열화특성)

  • Lee, Su-Bong;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.4
    • /
    • pp.79-85
    • /
    • 2009
  • This paper describes the degradation properties of ZnO surge arresters impressed by lightning impulse currents. To investigate the deterioration behaviors of ZnO surge arresters due to lightning surges, the 8/20[${\mu}s$], 2.5[kA] standard lightning impulse currents were injected to the ZnO surge arrester under test. The power frequency AC and DC leakage currents flowing through the ZnO surge arresters with and without the injection of lightning impulse currents were measured. As a result, the leakage currents are increased and the asymmetry of the AC leakage current is pronounced as the number of injection of the impulse current increases. The ZnO grain of the surge arrester without the injection of lightning surges are uniform but the ZnO grain of the ZnO surge arrester with the injection of lightning impulse currents are deformed. Also, it was found that the decrease of the $Bi_2O_3$ due to the lightning impulse current leads to the lack of grain boundary layer and the current concentrated by the lack of grain boundary layer play an important role to degrade nonlinear property of ZnO surge arrester blocks.

Analysis of Shielding Effect with Installation Methods of Arresters in Double Circuits Distribution Systems (2회선 배전계통에서 피뢰기 설치방법에 따른 차폐 효과 분석)

  • 정채균;김상국;이종범;정영호
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.2
    • /
    • pp.104-110
    • /
    • 2004
  • This paper describes the lightning overvoltage occurred differently according to installation methods of arresters and overhead grounding wire in case of double circuits distribution systems. First, the analysis models are established considering the severe case between upper and lower distribution line, when the direct lightning surge strikes to the overhead grounding wire. The lightning overvoltage is variously analyzed with the change of grounding interval and resistance, arrester installation interval as well as the magnitude of surge using EMTP. After simulation results are compared with the BIL which is now used at field, the authors propose the methods for suitable shielding in domestic distribution systems.

The Installation Technique of Grounding Electrode Conductors for Metal Oxide Distribution Surge Arresters (배전용 피뢰기의 접지도선 설치기법)

  • Lee, B.H.;You, I.S.;Lee, T.R.;Ahn, C.H.;Youn, J.S.;Youn, H.H.;Kim, J.S.;Kim, J.C.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1718-1720
    • /
    • 2001
  • The route of surge arrester connection is very important because bends and kinds of leads increase the impedance to lightning surges and tend to nullify the effectiveness of a grounding electrode conductor. There is a need to know how effective installation of lightning surge arresters is made in order to control voltage and to absorb energy at high lightning currents. The effectiveness of a grounding conductor and bonding for 18[kV] metal oxide distribution line arresters was experimentally investigated with lightning and oscillating impulse voltages.

  • PDF

A Study on the Analysis of the Lightning Surge Characteristics of Arresters in a 154kV Substation (154kV 변전소에서 피뢰장치의 뇌서지특성 해석)

  • Yun, Chang-Sub;Cho, Han-Goo;Lee, Jong-Beom
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.10
    • /
    • pp.433-439
    • /
    • 2006
  • This paper describes the characteristic evaluation of 154kV lightning arrester developed by domestic technology. To prove the protective ability of lightning arrester developed, various overvoltages were analyzed for A and B arrester were being used now at 154kV air and gas insulation substation, and for arrester developed. The results obtained by the various simulations show that the developed arrester has the effective protective ability and reducing ability of the overvoltage as A and B arrester, nevertheless there are somewhat differences among three kinds of arresters. Accordingly, it is evaluated that the arrester developed by domestic technology secured reliability can be installed actually at 154kV substation. In this paper, EMTP/ATP was used for simulation.

Accelerating aging test of distribution lightning arresters (배전용 피뢰기의 가속열화시험)

  • 김주용;송일근;김찬영;이병성;문재덕
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.07a
    • /
    • pp.596-598
    • /
    • 2000
  • This paper presents a new accelerating aging test facility for distribution lightning arresters. Aging parameters of lightning arrester are moisture ingress, electrical stress and surge absorption and so on. In this system, we applied 13.2kV to 6 samples and controled temperature and humidity of chamber and measured leakage currents of the all samples. Also we developed accelerating aging cycle which consists of -35$^{\circ}C$∼90$^{\circ}C$ temperature and 40%∼90% humidity. Through the aging test we found out the leakage current of aged sample increases rapidly according to the temperature rising. Hereafter we can determine the replacement guide of leakage current for field operating arresters and condition assessment of aged samples through this aging test.

  • PDF

A Study on The Scheme for Omission of lightning Arresters on One-Phase and Overhead Ground Wires in the Power Distribution Lines (배전선 1상의 피뢰기 및 가공지선 생략 방안 연구)

  • 정현수;정창호;김진오;송일근;장완성
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.15 no.2
    • /
    • pp.13-20
    • /
    • 2001
  • This proper presents the characteristics and their schemes for omission of lighting arresters on one-phase and over-head ground wire in the power distribution line. The case studies for Japan were investigated and compared with the cases of Korea. Especially, the EMTP simulation was performed for the omission scheme of lightning arrester's middle phase and the simulation results were described on the feasible problems when omitted. In this paper, it could be concluded that the omission of ground wire may be possible in some cases for the omission of lightning arresters, and in that case, the capacity of the lightning arresters should be Increase.

  • PDF