Leakage Current Characteristics of 18kv ZnO Lightning Arresters by Accelerated Aging Test

가속열화시험에 의한 18kV ZnO 피뢰기의 누설 전류 특성 분석

  • 김주용 (전력연구원 전력계통연구실) ;
  • 송일근 (전력연구원 전력계통연구실) ;
  • 김찬영 (우석대학 전기공학회) ;
  • 문재덕 (경북대학 전기공과)
  • Published : 2002.02.01

Abstract

This paper provides the results of accelerated aging test of 18kV ZnO lightning arresters to investigate the leakage current characteristics. It was impossible to establish the replacement criterion for field operating lightning arrester because conventional aging test was only focused on the aging of ZnO elements. In general, it is possible to replace the aged arresters before the failure in the field using the leakage current measurement because it must be increased by the aging. But we can not use the method because we don't know the characteristics of the installed lightning arresters. Therefore in this paper we applied operating voltage and accelerating cycle which consists of temperature and humidity to the arresters. Then we measured the variation of total and resistive leakage current and found out the characteristics of the acted lightning arresters.

Keywords

References

  1. JEC-217, '酸化亞鉛形避電器', 電氣學會, 1984
  2. 송일근, 김찬영, 김주용, 한재홍, 이병성, '배전기자재의 수명예측 기준제정(최종보고서)', 전력연구원, 2000
  3. ANSI/IEEE C62.11-1987, 'IEEE Standard for Metal Oxide Surge Arrester for AC Power Circuit', IEEE, 1987
  4. IEC 99-4, 'Surge Arresters Part 4: Metal Oxide Surge Arresters wihout Gaps for A.C. Systems', IEC 1991
  5. IEEE std C62.22-1991, 'IEEE Guide for the Application of Metal Oxide Surge Arresters for Alternating-Current Systems', IEEE 1991
  6. 'Type ZM-A, Leakage Current Detector for SORESTER Gapless Surge Arrester', Instruction Manual, Meiden
  7. T. Taniguchi, K. Izumi, 'Application of Polymer Insulating Materials for Surge Arrester Housing', CRIEPI 연구보고서 W89024, 1989
  8. 한전표준구매시방서, '전력용 피뢰기', ES 153-261-282, 1984