• Title/Summary/Keyword: intumescent coating

Search Result 13, Processing Time 0.03 seconds

An Experimental Study on the Fire Resistance Performance of Intumescent Coating System with Time Elapse (경년변화에 따른 내화도료의 내화성능에 관한 실험적 연구)

  • Kim, Dae-Hoi;Sung, Si-Chang;Choi, Dong-Ho;Park, Soo-Young;Lee, Sea-Hyun;Lee, Jong-Chan
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.61-64
    • /
    • 2008
  • Applying fire resistive coating to steel members is one of the general methods to secure fire resistance performance of steel members. And intumescent coating system is currently one of methods giving fire resistance to steel members. Intumescent coating system for fire resistance, however, has undesirable weaknesses that fire resistance performance of steel members is being deteriorated due to cracks and falling-offs of the coverings as time goes after completion of the coverings to the members. This study is designed to understand changes in fire resistance performance of intumescent coating system through follow-up tests on temperature of unexposed surface for the domestic intumescent coating system.

  • PDF

An Experimental Study on the Fire Resistance Performace of Intumescent Coating System by Environmental Testing Procedure (환경시험방법에 의한 내화도료의 내화성능에 관한 실험적 연구)

  • Park, Soo-Young;Sung, Si-Chang;Choi, Dong-Ho;Kim, Dae-Hoi;Lee, Sea-Hyun;Lee, Jong-Chan
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.69-72
    • /
    • 2008
  • This study is designed to understand changes in fire resistance performance of intumescent coating system through follow-up tests on temperature of unexposed surface for the domestic intumescent coating system by environmental testing procedure.

  • PDF

An Experimental Study on the Durability of Intumescent Coating System with Time Elapse (경년변화에 따른 내화도료의 내구성에 관한 실험적 연구)

  • Choi, Dong-Ho;Sung, Si-Chang;Kim, Dae-Hoi;Park, Soo-Young;Lee, Sea-Hyun;Lee, Jong-Chan
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.65-68
    • /
    • 2008
  • Intumescent coating system for fire resistance has undesirable weaknesses that fire resistance performance of steel members is being deteriorated due to cracks and falling-offs of the coverings as time goes after completion of the coverings to the members. This study is designed to understand changes in durability of intumescent coating system through follow-up tests on bond strength and thickness for the domestic intumescent coating system.

  • PDF

The Research for the Establishment of Test Method of Durability on Intumescent Coating System (내화도료 내구성 평가 방법 설정에 관한 연구)

  • Choi, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.23 no.1
    • /
    • pp.40-47
    • /
    • 2009
  • Applying fire resistive coating to steel members is one of the general methods to secure fire resistance performance of steel members. And intumescent coating system is currently one of methods giving fire resistance to steel members. Intumescent coating system for fire resistance, however, has undesirable weaknesses that fire resistance performance of steel members is being deteriorated due to cracks and falling-offs of the coverings as time goes after completion of the coverings to the members. So it is necessary to understand changes of the durability and the fire resistance performance of intumescent coating system over a time elapse and to reflect such change properly into the building design and construction. This research is performed to present the test method of durability and the maintenance of intumescent coating system through theoretical investigation of the test method of durability and the guide of maintenance & management of intumescent coating system of several countries, including the Britain, United States, Japan.

Temperature on structural steelworks insulated by inorganic intumescent coating

  • Choi, J. Yoon;Choi, Sengkwan
    • Steel and Composite Structures
    • /
    • v.15 no.1
    • /
    • pp.1-14
    • /
    • 2013
  • Predicting the fire resistance of structures has been significantly advanced by full scale fire tests in conjunction with improved understanding of compartmental fire. Despite the progress, application of insulation is still required to parts of structural steelwork to achieve over 60 minutes of fire rating. It is now recognised that uncertainties on insulation properties hinder adaptation of performance based designs for different types of structures. Intumescent coating has recently appeared to be one of most popular insulation types for steel structures, but its design method remains to be confirmed by empirical data, as technical difficulties on the determination of the material properties at elevated temperatures exist. These need to take into account of further physiochemical transitions such as moving boundary and endothermic reaction. The impetus for this research is to investigate the applicability of the conventional differential equation solution which examines the temperature rise on coated steel members by an inorganic intumescent coating, provided that the temperature-dependent thermal/mechanical insulation properties are experimentally defined in lab scale tests.

Finite element study on composite slab-beam systems under various fire exposures

  • Cirpici, Burak K.;Orhan, Suleyman N.;Kotan, Turkay
    • Steel and Composite Structures
    • /
    • v.37 no.5
    • /
    • pp.589-603
    • /
    • 2020
  • This paper presents an investigation of the thermal performance of composite floor slabs with profiled steel decking exposed to fire effects from floor. A detailed finite-element model has been developed by representing the concrete slab with steel decking under of it and steel beam both steel parts protected by intumescent coating. Although this type of floor systems offers a better fire resistance, passive fire protection materials should be applied when a higher fire resistance is desired. Moreover, fire exposed side is so crucial for composite slab systems as the total fire behaviour of the floor system changes dramatically. When the fire attack from steel parts, the temperature rises rapidly resulting in a sudden decrease on the strength of the beam and decking. Herein this paper, the fire attack side is assumed from the face of the concrete floor (top of the concrete assembly). Therefore, the heat is transferred through concrete to the steel decking and reaching finally to the steel beam both protected by intumescent coating. In this work, the numerical model has been established to predict the heat transfer performance including material properties such as thermal conductivity, specific heat and dry film thickness of intumescent coating. The developed numerical model has been divided into different layers to understand the sensitivity of steel temperature to the number of layers of intumescent coating. Results show that the protected composite floors offer a higher fire resistance as the temperature of the steel section remains below 60℃ even after 60-minute Standard (ISO) fire and Fast fire exposure. Obtaining lower temperatures in steel due to the great fire performance of the concrete itself results in lesser reductions of strength and stiffness hence, lesser deflections.

Experimental and Numerical Study of the Thermal Decomposition of an Epoxy-based Intumescent Coating (실험과 계산을 통한 에폭시 계열 내화도료의 열분해에 관한 연구)

  • Kim, Yangkyun
    • Fire Science and Engineering
    • /
    • v.30 no.1
    • /
    • pp.31-36
    • /
    • 2016
  • This study investigates the characteristics of thermal decomposition of an epoxy-based intumescent paint using thermogravimetric analysis (TGA) and numerical simulation. A mathematical and numerical model is introduced to describe mass loss profiles of the epoxy-based intumescent coating induced by the thermal decomposition process. The decomposition scheme covers a range of complexity by employing simplified 4-step sequential reactions to describe the simultaneous thermal decomposition processes. The reaction rates are expressed by the Arrhenius law, and reaction parameters are optimized to fit the degradation behavior seen during thermogravimetric (TG) experiments. The experimental results show a major 2-step degradation under nitrogen and a 3-step degradation in an air environment. The experiment also shows that oxygen takes part in the stabilization of the intumescent coating between 200 and $500^{\circ}C$. The simulation results show that the proposed model effectively predicts the experimental mass loss as a function of time except for temperatures above $800^{\circ}C$, which were intentionally not included in the model. The maximum error in the simulation was less than 3%.

INTUMESCENT INORGANIC AND ORGANIC COATINGS

  • Kodolov, V.I.;Mikhalkina, T.M.;Shuklin, S.G.;Bystrov, S.G.;Larionov, K.I.
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1997.11a
    • /
    • pp.130-137
    • /
    • 1997
  • Intumescent inorganic and organic coatings which dintr one from the other by the type of gas formers and the mechanisms of foam formation have been obtained and investigated. Inorganic intumescent coatings are the compositions based on water glass and mineral additives with different dispersity. Mineral additives contain adsorbed and absorbed water and carbonates which are destructed with the carbon dioxide and water evolution during the flame action on coating. The decreasing of mineral additives particle sizes under the mechanical milling with the fraction precipitation promotes the foam coke formation with less defects. Here the main structure of comparing compositions does not change. In organic coatings based on epoxy-polymers the polyammonium phosphate additive is used. It is the cabonization catalyst and the foam agent. The polyammonium phosphate of various dispersity employed is uniformly distributed on the polymeric matrix. The decreasing of the particle sizes leads to the increasing of the fire resistant properties of the intumescent coa-ting. The fire resistant analysis of the coating during more than an hour: the coating back side the temperature on plastic or wooden materials does not exceed 423K, and on metal-573K.

  • PDF

Strength Characteristics of Passive Fire Protection Material Applied Structural Members on Fire Load (수동화재보호 재료가 적용된 구조부재의 화재하중에 대한 강도 특성)

  • Jo, Sang Chan;Yu, Seung Su;Seo, Jung Kwan
    • Journal of the Society of Naval Architects of Korea
    • /
    • v.59 no.1
    • /
    • pp.29-38
    • /
    • 2022
  • In offshore installations, fires cause the structure to lose its rigidity and it leads to structural integrity and stability problems. The Passive Fire Protection (PFP) system slows the transfer rate of fire heat and helps prevent the collapse of structures and fatality. Especially, intumescent epoxy coating is widely used in the offshore industry, and not only is the material cost expensive, but it also takes a lot of time and cost for construction. Several studies have been conducted on the efficient application and optimal design of the PFP system. However, the mechanical properties and the strength of the PFP material have not been considered. In addition, researches on the correlation between the thickness of PFP and the structural behavior were insufficient. Therefore, this study aims to analyze the thermal and mechanical effects of the PFP on the structure when it is applied to the structural member. In particular, it is intended to resolve the change in strength characteristics of the structural members as the thickness of the PFP increases.