• Title/Summary/Keyword: inductive SFCL

Search Result 32, Processing Time 0.025 seconds

Simulation for current limiting characteristics of the resistive and inductive SFCL with line-to-ground fault

  • Choi, Hyo-Sang;Hwang, Si-Dole;Kim, Sang-Joon;Han, Byoung-Sung
    • Progress in Superconductivity
    • /
    • v.1 no.1
    • /
    • pp.73-80
    • /
    • 1999
  • We investigated the current limiting characteristics of resistive and inductive SFCLs with 100 $\Omega$ of impedance for line-to-ground faults in the 154 kV transmission system. The fault simulation at the phase angles $0^{\circ}$, $^45{\circ}$, and $90^{\circ}$ showed that the resistive SFCL limits the fault current less than 17 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppresses the current below 14 kA, but with 5 kA of DC component which decreases to zero in 5 cycles. We concluded that the inductive SFCL has higher performance in current limiting effect, but the resistive SFCL was better from the viewpoint of less DC components.

  • PDF

EMTDC simulation for current limiting characteristics of the resistive and inductive SFCL (저항형과 유도형 한류기의 전류제한특성에 대한 EMTDC 해석)

  • 최효상;황시돌;현옥배
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.05a
    • /
    • pp.255-258
    • /
    • 1999
  • We investigated the current limiting characteristics of resistive and inductive SFCLs with 100 $\Omega$ of quench impedance for a single line-to-ground fault. which accounts for about 70% of the total power line faults, in the 154 kV transmission system. The fault simulation at the phase angles 0$^{\circ}$, 45$^{\circ}$, and 90$^{\circ}$ showed that the resistive SFCL limited the fault current less than 15 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppressed the current below 12 KA, but with 3 kA of DC component which decreased to zero in 5 cycles. We concluded that the inductive SFCL had higher performance in current limiting but the resistive SFCL was better from the view point of DC components.

  • PDF

Operating properties of the resistive and inductive SFCL with the three-phase fault (3상 단락사고에 대한 저항형과 유도형 한류기의 동작특성)

  • 최효상;현옥배;김상준
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.11a
    • /
    • pp.209-212
    • /
    • 1999
  • We studied the operating properties of resistive and inductive SFCLS with 100 $\Omega$ of quench impedance for a three-phase-fault in the 154 kV transmission system. The fault simulation at the phase angles 0$^{\circ}$ , 45$^{\circ}$ , and 90$^{\circ}$ showed that the resistive SFCL limited the fault current less than 16 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppressed the current below 11 kA, but with 3-4 kA of DC component which decreased to zero in 5 cycles. We concluded that the inductive SFCL had higher performance in current limiting but the resistive SFCL was better from the view point of DC components.

  • PDF

Current limiting characteristics of the resistive and inductive SFCL in the double line-to-ground fault (2선 지락사고에 대한 저항형과 유도형 한류기의 전류제한특성)

  • Choi, Hyo-sang;Hyun, Ok-Bae;Kim, Sang-Joon;Han, Byoung-Sung
    • Proceedings of the KIEE Conference
    • /
    • 1999.07c
    • /
    • pp.1369-1372
    • /
    • 1999
  • We investigated the current limiting characteristics of resistive and inductive SFCLs with 100${\Omega}$ of Quench impedance for a double line-to-ground fault, in the 154 kV transmission system. The fault simulation at the phase angles $0^{\circ}$, $45^{\circ}$, and $90^{\circ}$ showed that the resistive SFCL limited the fault current less than 17 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppressed the current below 12 kA, but with 3$\sim$5 kA of DC component which decreased to zero in 6 cycles. We concluded that the inductive SFCL had higher performance in current limiting but the resistive SFCL was better from the view point of DC components.

  • PDF

A Study on AC loss Characteristics of Asymmetric non-inductive coils with Combination of Superconducting wires (초전도 선재 조합에 따른 비대칭 무유도성 코일의 교류 손실 특성 연구)

  • Kim, J.S.;Hwang, Y.J.;Na, J.B.;Choi, S.J.;Kim, Y.J.;Lee, J.H.;Lee, W.S.;Chang, K.S.;Ko, T.K.
    • Progress in Superconductivity and Cryogenics
    • /
    • v.13 no.1
    • /
    • pp.17-21
    • /
    • 2011
  • A hybrid superconducting fault current limiter (SFCL) with fast switch had been previously suggested by our research group. To make a hybrid SFCL, different superconducting wires were wound two pancake coils so that two pancake coils had asymmetric configuration. The impedance of the asymmetric non-inductive coils are zero with applied normal current. However during the fault. currents were distributed unequally into the two pancake coils because each superconducting wires have different electrical characteristics. This unequal distribution of current causes effective magnetic flux which generate repulsive force. Fast switch was thus opened by the force applied to the aluminum plate which consists of SFCL. In this paper, the AC loss characteristics of the asymmetric non-inductive coils with combinations of superconducting wires were studied and calculated by related experiments and finite element method (FEM) simulation. From these results, we suggested the appropriate combination of two superconducting wires to be used for the asymmetric non-inductive coils.

A study on operating properties of superconducting fault current limiter in the line-to-line fault (선간 단락사고에 대한 초전도 한류기의 동작특성에 대한 연구)

  • Choi, Hyo-Sang;Hyun, Ok-Bae;Kim, Sang-Joon
    • Proceedings of the KIEE Conference
    • /
    • 1999.11b
    • /
    • pp.86-88
    • /
    • 1999
  • We investigated the current limiting characteristics of resistive and inductive SFCLs with $100{\Omega}$ of quench impedance for a line-to-line fault in the 154 kV transmission system. The fault simulation at the phase angles $0^{\circ}$, $45^{\circ}$, and $90^{\circ}$ showed that the resistive SFCL limited the fault current less than 15 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppressed the current below 13 kA, but with $2{\sim}3\;kA$ of DC component which decreased to zero in 6 cycles. We concluded that the inductive SFCL had higher performance in current limiting but the resistive SFCL was better from the view point of DC components.

  • PDF

A Study on Design, Fabrication Techniques and Test Results of 1.2kV 180A Inductive Superconducting Fault Current Limiter by Conduction-Cooled System (전도냉각에 의한 1.2 KV/80 A급 유도형 고온초전도 한류기의 설계, 제작 및 테스트에 관한 연구)

  • 강형구;전우용;이승제;안민철;배덕권;윤용수;고태국
    • Progress in Superconductivity and Cryogenics
    • /
    • v.5 no.2
    • /
    • pp.30-35
    • /
    • 2003
  • The inductive superconducting fault current limiter (SFCLJ limits the fault current with its dc reactor. To fabricate the optimal dc reactor for inductive SFCL, several design and manufacturing technologies are necessary. In this paper, the manufacturing technology for dc reactor and cryogenic cooling method are described in detail. GM-cryocooler was used enlarge the critical current of dc reactor by cooling down the temperature of dc reactor about 20 K. Moreover, the results of short circuit test were described. Finally, the thermal characteristics of conduction-cooled system were discussed and then, sub-cooled nitrogen system was proposed to enhance the thermal stability of dc reactor.

Study on the Characteristics of 30 kVA Inductive High-Tc Superconducting Fault Current Limier (30 kVA급 유도형 고온초전도 한류기의 특성 연구)

  • 이찬주;이승제;강형구;배덕권;안민철;현옥배;고태국
    • Progress in Superconductivity and Cryogenics
    • /
    • v.4 no.1
    • /
    • pp.110-113
    • /
    • 2002
  • The high-tc superconducting fault current limiters (SFCL) are studied worldwide to be classified as resistive type or inductive type such as magnetic shielding type and dc reactor type. This Paper deals with an open core type SFCL, a kind of magnetic shielding type SFCL. We manufactured a 30 kVA open core type SFCL. It was modified from the old one with a rated power of 8 kVA. We stacked four superconducting tubes as magnetic shielding material and used the same primary winding as the old one. The experiments were performed with a maximum source voltage of 1 kV. The results show that the fault current in the source voltage of 1 kVrms was reduced to be about 105 Apeak, which was calculated to be about 22 % of the fault current in the system without an SFCL.

Quench Characteristics of a Inductive Superconducting Fault Current Limiter (유도형 초전도사고전류제한기의 퀜치특성)

  • Choi, K.D.;Lee, S.J.;Kim, D.S.;Lee, J.K.;Kim, D.H.;Cha, G.S.;Hahn, S.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1994.11a
    • /
    • pp.114-116
    • /
    • 1994
  • Recently a superconducting fault current limiter(SFCL) has public attentions for the solution of large fault currents of power systems. Though a SFCL has more effective characteristics than the other current limiting devices, there are many problems to apply it to real power systems. For the analysis of transient fault characteristics of the SFCL, we designed and fabricated a inductive SFCL and tested it in 35V line. The superconducting cable of the SFCL was quenched at lower current(49A) than the designed critical current but it limited the fault current to the lower value(150A) than the one expected without SFCL(250A). And within one period the fault current decreased lower than normal laod current.

  • PDF

Investigation on the inductive and resistive fault current limiting HTS power cable

  • Lee, Sangyoon;Choi, Jongho;Kim, Dongmin;Kwon, Yonghyun;Kim, Seokho;Sim, Kideok;Cho, Jeonwook
    • Progress in Superconductivity and Cryogenics
    • /
    • v.16 no.2
    • /
    • pp.59-63
    • /
    • 2014
  • HTS power cable bypass the fault current through the former to protect superconducting tapes. On the other hand, the fault current limiting (FCL) power cable can be considered to mitigate the fault current using its increased inductance and resistance. Using the increased resistance of the cable is similar to the conventional resistive fault current limiter. In case of HTS power cable, the magnetic field of HTS power cable is mostly shielded by the induced current on the shield layer during normal operation. However, quench occurs at the shield layer and its current is kept below its critical current at the fault condition. Consequently, the magnetic field starts to spread out and it generates additional inductive impedance of the cable. The inductive impedance can be enhanced more by installing materials of high magnetic susceptibility around the HTS power cable. It is a concept of SFCL power cable. In this paper, a sample SFCL power cable is suggested and experimental results are presented to investigate the effect of iron cover on the impedance generation. The tests results are analyzed to verify the generation of the inductive and resistive impedance. The analysis results suggest the possible applications of the SFCL power cable to reduce the fault current in a real grid.