• 제목/요약/키워드: grounding resistance

검색결과 246건 처리시간 0.03초

대형접지전극시스템 접지임피던스의 측정 (Measurement of Grounding Impedances in Large-scale Grounding Electrode Systems)

  • 이경훈;최종혁;최영철;이규선;이복희
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2008년도 추계학술대회 논문집
    • /
    • pp.193-196
    • /
    • 2008
  • In these days, large structures are constructed and bonded with ground grid Because the distances between mesh and auxiliary electrodes are not enough in downtown areas, it is very difficult to measure the ground resistance of large scale grounding electrode systems. Actually the auxiliary electrodes for test are installed in grounding grid. This paper present the experimental results of ground resistance and impedance according to the location of auxiliary electrode. As a result, we get much lower resistances and impedances than real values the auxiliary electrodes are placed in the ground grid. In case that the auxiliary electrodes are located in the ground grid the resistances are very low and reactance only is inductive component.

  • PDF

MATLAB 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성 분석 (Transient Grounding Impedance Characteristic Analysis of a Copper Rod-type Grounding Electrode Used for Electric Distribution Systems Using MATLAB Program)

  • 김경철;오경훈;이규진;심건보;최종기
    • 조명전기설비학회논문지
    • /
    • 제23권9호
    • /
    • pp.40-46
    • /
    • 2009
  • 비록 접지저항은 접지전극의 접지성능을 좌우하는 지수이기는 하지만, 과도상태에서는 접지 성능을 반영하지 못한다. 동봉은 배전계통에서 가장 많이 쓰이는 접지전극이다. 본 논문에서는 동봉의 접지 임피던스를 주파수 60[Hz]에서 100[kHz] 범위까지 측정하여 등가 접지임피던스 모델을 구하였다. 뇌격서지가 유입되었을 때 MATLAB 프로그램으로 과도접지임피던스의 수치와 파형을 시뮬레이션하였다.

A Study on Transient Grounding Performance of Ground Rods

  • Yun Dong-Hyeon;Lee Hyeong-Su;Lee Gwan Hyeong
    • 한국산업안전학회:학술대회논문집
    • /
    • 한국안전학회 2002년도 추계 학술논문발표회 논문집
    • /
    • pp.281-285
    • /
    • 2002
  • Although DC ground resistance is a good index of performance for a grounding system, it does not reflect the grounding performance during the transient states. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute performance index due to its dependence on impulse current shape. In this paper, a grounding performance of needle-typed ground rod has been compared with simple ground rod using HIFREQ[1], which is an engineering electro-magnetic code based on MoM (Method of Moment).

  • PDF

연료전지 자동차 세계기술규정의 감전보호기준 연구 (Research on Standards for Protection against Electric Shock in Global Technical Regulations of Fuel Cell Vehicle)

  • 황보천;이규명;유경준
    • 한국수소및신에너지학회논문집
    • /
    • 제21권3호
    • /
    • pp.167-183
    • /
    • 2010
  • This paper analyzes the backgrounds of the standards for protection against electric shock in Global Technical Regulations (GTR) of Fuel Cell Vehicle (FCV). Targets on research were high voltage criteria, safety current, isolation and grounding resistance, time limitation, energy, adequate clearance, and test procedure. Based on human impedance and effect of current in IEC 60479-1, safety of human was examined. Then, isolation and grounding circuit model of FCV were analyzed theoretically. The results give several suggestions: touch voltage less than 25V, AC energy less than 0.0813J, separation considering middle finger length, grounding resistance less than $0.2\Omega$, maximum AC ground voltage of 1V (rms), and isolation resistance between earth and electrical chassis. In MATLAB/Simulink environment, error characteristics of isolation resistance measurement procedure using internal DC sources were analyzed under variations of internal resistance of voltmeter and isolation resistance.

접지선 전류를 시험 전류원으로 활용한 접지저항 측정기법에 관한 연구 (The Measurement of the Grounding Resistance Using the Ground Current of the Distribution System)

  • 강문호
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 학술대회 논문집
    • /
    • pp.293-295
    • /
    • 2004
  • Public utilities adopt the grounding rules ; class I, class II, class III and special class III, and install the grounding electrodes in distribution facilities. To keep the safety of the human and the facilities, Public utilities also manage the value of ground resistance in distribution system biennially. At present the Hook-On meter is normally used to measure the ground resistance although it has ${\pm}5[%]$ measuring error and it can not measure the exact value when the current is over 1[A]. In addition it is very difficult to use the fall-of-potential method in distribution system. In this paper we propose the new measurement method using ground current of distribution system as the current source.

  • PDF

가공송전선로의 철탑 접지저항 저감효과 분석 (Analysis of Grounding resistance reduction effect of Transmission tower)

  • 민병욱;김태영;박봉규;최진성;강연욱;박광욱;배현권
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.453-454
    • /
    • 2011
  • With the transmission line the ratio of lightning breakdown the while whole breaking down is occupying a high share with average 72%, is a tendency which increases continuously. In order decreasing the back flashover faults from like this lightning breakdown, it is very important to maintain grounding resistance of tower below target. In this paper, we synthetically analyzed the grounding resistance reduction effect of tower foundation and standard ground connection from construction site, and investigated efficiency for ways to increase the length of counter poise and expand the size of conductivity concrete materials.

  • PDF

22.9kV-Y 다중접지 배전계통 접지극의 임펄스 응답 특성 실증연구 (A Study On the Impulse Response Behavior of Ground Rods in Power Distribution System)

  • 강문호;장상옥;박상만;하동혁;이흥호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1858-1860
    • /
    • 2003
  • Ground rods as the discharge path are commonly installed to ensure the safety of human beings and facilities from the surge. Accordingly, proper grounding resistance are specified by the grounding types, and the specified resistance are also required to install the lightning protective facilities. it is needed to analyze the difference between these two resistance through the field test. Therefore, in this paper, the impulse response behavior of the ground rods is analyzed by constructing the test facilities and by testing the ground rods in multi-ground power distribution systems. The impulse responses were analyzed, in transient state, by testing the concrete poles as well since the grounding wires are installed in the concrete poles.

  • PDF

변전소 접지설계를 위한 접지전극 주변의 위험전압 측정과 분석 (Measurement and Analysis of the Dangerous Voltage Around Grounding Electrode for Safety in Substation Ground)

  • 손석금;김재철
    • 전기학회논문지P
    • /
    • 제60권4호
    • /
    • pp.214-219
    • /
    • 2011
  • The substation grounding design,"IEEE Guide for Safety in AC Substation Grounding (ANSI / IEEE Std 80)"has been widely used. Substation grounding design and substation grounding resistance of grounding network site to predict the voltage at the risk of a very important task, which is a ground fault current due to the influx of the ground network and due to rise in the Earth's potential can be applied to human dangerous Voltage within safe tolerances be configured to be the ground because the network. IEEE Std. 80 for the substation construction safety equipment on the ground securing the ground electrode and the mesh around the boundary potential distribution in terms of risk analysis by the touch voltage and the reference was to clean up the definition and the basic steps of the voltage of the voltage limits the risk of peripheral grounding electrode Suppression by the simulator through a new secure from dangerous voltage design techniques were presented.

접지제원 변화에 따른 사선 메쉬접지의 특성변화 (According to The changing of the grounding design source, The changes in the Diagonal mesh grounding)

  • 김태훈;최홍규;홍순석;송영주;심용식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2009년도 추계학술대회 논문집
    • /
    • pp.347-350
    • /
    • 2009
  • 기존 접지방식인 격자 메쉬접지와 제안한 방식인 사선 메쉬접지를 비교하였다. 동일 접지설계 제원을 가지고 사선 메쉬접지와 격자 메쉬접지를 비교한 결과, 최대예상 접촉전압, 접지저항, 총 접지도체의 길이 모두 감소하였다. 본문에서는 대지저항률, 매설깊이, 대지전류, 접지도체 단면적의 변화에도 사선 메쉬접지가 기존 격자 메쉬접지에 비해 우수한 성능을 나타내는 것을 시뮬레이션을 통해 증명하였다.

  • PDF

심매설 접지전극에 대한 접지임피던스의 주파수특성 (Frequency Characteristics of Grounding Impedances of the Deeply-driven Ground Rods)

  • 강성만;김태기;김한수;이복희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.1348-1349
    • /
    • 2008
  • Grounding impedance depends on the frequency of current flowing into a grounding system. Especially, the lightning gives a broad frequency spectrum from low frequency up to 1 MHz. So the grounding impedance related to high frequency current like lightning should be measured with high frequency source. In this paper, we described the grounding impedances of deeply-driven ground rods of 10 $\sim$ 48 m long with respect to the frequency of injected currents. For the experiments, we used the wideband power amplifier which can produce sinusoidal voltages with the frequency ranges of DC $\sim$ 250 MHz. As a result, the longer the ground rod is, the lower the ground resistance is. However the grounding impedance of deeply-driven ground rod in the range of higher frequency is significantly increased. As a consequence, it is important to evaluate the high frequency performance of grounding systems for lightning protection.

  • PDF